Gebruiksaanwijzing /service van het product AIS 3000 van de fabrikant APC
Ga naar pagina of 58
AIS ® 3000 and XR Battery Enclosur e 10-4 0kV A 400V Ope ratio n Ma nual.
.
AIS3 000® & X R Batter y Enclos ure 10-30kVA, 208V, Operati on Manu al – 9 90-196 2 1 AIS ® 3000 and XR Batter y Enclo sur e 10-4 0kV A 4 00V Operat ion Man ual IM POR T ANT S AF ETY IN STRU C.
.
Cont ents AIS® 300 0 & X R Batt ery Enc losure 10-40k VA, 40 0V, Opera tion M anual – 990-22 59 i IMPORTAN T SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1 Warnin g/no te symbol s . . . . . . . . . . . . . . . . . . . . . . . .
ii AIS® 3000 & XR Batte ry Encl osure 10-40k VA, 40 0V, Ope ration Manua l – 99 0-2259 Front Pane l Removal/ I ns tallation . . . . . . . . . . . . . . . . . . . . . . . 18 Rem oval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 400V, Op eratio n Manua l – 990 -2259 iii Appen dix ..... ..... .... ..... ....... ..... ..... ..... ..... ....... ..... .... . 40 UPS Com ponents and Options . . . . . . . . . . . . . . . . . . . .
.
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 1 IMPORT ANT SAFETY INSTRUCTIONS This guide contains impo rtant instructions that should be followed when handling th e UPS, Battery Enclosures, an d Batteries.
IMPORTANT SAFET Y INSTRUCTIONS 2 AIS® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Ge nera l s afet y T wo p eople to lift a component weig hing between 18 - 3 2 kg. Indi cates that a swit ch o r curr ent pr ote ction device is ON .
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 3 Intr oduc tion W elcome to the Operation Manual covering the AIS ® 3000 UPS and the Extended Run Battery Encl osur e (XR E nclo sure ). This manu al p rovid es yo u with a de taile d d escri ption of st art -up, ope ratio n, and tr ouble shoot ing.
4 AIS® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 The AIS 3000 F amily Range 352m m Enc losur es 523m m Enc losur es 10/10 0 Ba s e-T P r ob e AP9619 Netwo.
The AIS 30 00 Family Range AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 5 W ARNING! Only trained persons fam iliar with the construction and oper ation of the equipment, including the electrical an d mechanical hazard s involved, may install and remove system components.
6 AIS® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Start-Up (if ap plicab le) Power appl icati on Set the utility breaker to ON. If your installation includes an XR En closure with a DC disconnect switch, tur n the DC discon nect switc h ON.
St art-Up (i f ap plicable ) AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 7 After system boot-up, the display will atuomatica lly prompt you on how to conf irm /select voltage an d freq uency as sho wn in th e follo wing .
8 AIS® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Operation Modes In a stand-alone installation, the UPS has four differ ent operation modes. If the installation includes a Maintenance Bypass Panel te s t mode will also be available.
Operat ion Modes AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 9 Maintenance bypass The UPS can b e connected to a n external Maintenance Bypass Panel.
10 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 The Display Intr oduction CAUTION! The display provides access to more functions than d escribed in this manual. Those functions sho uld not be accessed without the assistance of APC Custom er Support in ord er to avoid unwan ted load i mpacts .
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 11 Navigat ion Menu-driven user functions If you get beyond the fun ctions described in the m enu tree, do not proceed.
Navigati on 12 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Bas ic disp lay navi gation principl es On the d isplay , press ESC until you ge t to the Overview Screen, whic h provides you with basic system status information.
Navigatio n AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 13 T urn load ON. 1. From the M ain Men u, select Cont r ol and pre ss ENTER 2. Use UP/DOWN key to navigate to Tu r n L o a d O N , and press ENTER 3.
Navigati on 14 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Load and ba tter ies. Load: Perc entage of the load in relation to the total UPS capacity . Bat V oltage: Shows either the positive or ne gative half of the battery voltage (th e lower value of the two will a ppear).
Navigatio n AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 15 Logging From the logg ing screen on the Ma in Menu, you can view the 100 most recent UPS log e vents, and view the log ged details of the events, such as date and time of occurrence, and event nu mber .
Navigati on 16 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Alarm threshold If the load level exceeds the preprogrammed threshold, the UPS will display a warning. Example: T o ch ange the Alarm T hresholds, 1.
Navigatio n AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 17 From the Beeper S etup Menu , select Beeper S etup .
18 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Fr ont Pane l Remova l/Installat ion Removal T o remo ve a Front Pan e l, use a coin or similar , and turn the 2 black lock devices away fro m th e Display to horizontal level.
Fr ont Pan el Removal /Instal lati on AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 19 Installation T o install a Front Panel, insert the two guide taps po sitioned at the bottom of the Front Pan el into the two slots at the bottom of the Enclosure.
20 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Air Filt er Ins pectio n/Rep lace ment Air filt er ins pec tion The UPS and XR Enclosure Front Panels are fitted with air filters on the inside of the Front Panels for extra protection of systems in stalled in environments with conductive dust.
Air Fil ter Inspec tion/Rep lacemen t AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 21 Remo ve t he Fron t Pa nel fr om the Enc losur e. Remove the wing n uts from the plate between upper and lower air filter .
Air Filt er Ins pec tio n/Rep lac emen t 22 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Position the new air filters in the Front Panel, ensu ring that the metal s id e of the air filters f ace out ward s.
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 23 Batt er y Repla cemen t Ge nera l safe ty p rior to mo dule r epl acem ent Battery Module One Battery Module consists of 4 Battery Units (shipping in th e Enclosures).
Batt ery Rep lacemen t 24 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Rem ova l of B atte ry Se cu ring Br ack ets (i f ap plica ble) If your system is eq uipped with Battery Securing Brackets, follow the below procedure to remove the Brackets.
Ba tter y Re plac eme nt AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 25 Battery Module r emoval Follow the below p rocedures if you need to change or ad d a Battery Mo dule, e.
Batt ery Rep lacemen t 26 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Install the Battery Module in the lowest available bay (4 acro ss in 523mm UPS versions, 2 acr oss in 35 2mm U PS vers ions) .
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 27 Ne twork Ma nagem ent C ar d with Envir onm ental Monito r The APC Network Management Card with Environmental Monitor (AP9619) is installed in the UPS as default.
28 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 How to Obt ain Replacemen t Parts T o o btain a replacemen t part, cont act APC Customer Support (see rear cover). 1. In the event of a Battery Module failure, the display m ay show additional “fault list” screens.
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 29 T o tal-Power -Off Pr ocedur e Set the DC disconnect switch on the XR Enclosure (if available) to the OFF position.
Total -Power-Off Procedure 30 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Refer to Seismic Anchoring in the E lectrical Installation Manual for instructions on how to re move Seismic Battery Brackets (if applicable).
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 31 Disp lay Messages /T r oubleshoot ing This section lists the status and alarm m ess ages tha t the UPS might display .
Displ ay Messages /Troub leshooti ng 32 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Load I s No Longer Above Alar m Threshold. The l oad pre viousl y exceede d the ala rm thre shold and the si tuati on has been correc ted eit her bec ause th e load decr eased or the thres hold was incr eas ed.
Displ ay Message s/Troubl eshoot ing AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 33 If a problem persists, note UPS mode l #, serial #, and date purchased before calling APC Customer Support (T ype lab el located on rear cover , bottom section).
34 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Mec hanical By pass Mec hani cal By pass Lev er For increased ava il a bility , the UPS is equipped with an internal mec hanical bypass system providing mains power d irectly to the output, bypassing all UPS electronics.
Mechanica l Bypass AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 35 T urn the Mechanical Bypass L ever upwards to activate the internal mechanical bypass switch. Reinstall the Front Panel The load will now be supported directly by mains power .
36 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Maint enance B ypa ss Pane l Operation pr ocedur e The Mainte nance Bypass Panel (MBP) can be used to completely isolate the UPS in the ev ent of an internal UPS fault.
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 37 LIMITED F ACTOR Y W ARRANTY The limited warranty provided by American Power Conversion Corporation (“A .
LIMITED FACTORY WARRANTY 38 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Dra wing s, d escript ions APC warrants for the W arran ty Period and on the t.
LIMITED FACTORY WARRANTY AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 39 IN NO EVENT SHALL APC, ITS OF FICERS, DIRECTORS, AFFI LIATES OR EMPLOYEES BE LI .
40 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Appen dix UPS Comp onen ts and Opt ions 352m m Enc losur es 523m m Enc losur es 10 /1 0 0B a se -T P ro.
Appendi x UPS Component s and Opt ions AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 41 Sy stem s izes, part Nos.
Appendi x UPS Compon ents and Opt ions 42 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Battery Module One Battery M odule consists of 4 Battery Units (shipping in the UPS Enclosu re).
Appendi x UPS Component s and Opt ions AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 43 Stab il izing B racket Always install the Stabilizing Brackets on the 352mm Enclosure (shipped with the UPS) to en hance the stability o f the Enclosure.
Appendi x UPS Compon ents and Opt ions 44 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 User inte rface Display: user-control interface used to conf igure the functionality , monitor th e system, set alarm thresholds, and to provide audible an d visual alarms.
AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 45 Options Battery Securing Bracket and Floor Anchoring In seismic are as, each Battery Mo dule must be secured with a Battery Securing Br a cket.
Appendi x Opti ons 46 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Extended Run Battery Enclosure (X R Enclos ur e) a nd Batt ery M odule XR Enclosur e weights: 2 Batt ery Modul es 410.8k g 6 Batt ery Modul es (4 of t he modul es are shipp ed separat ely o n a pallet ) 794.
Appendi x Opt ions AIS® 3000 & XR Ba ttery E nclosu re 10-4 0kVA, 40 0V, Op eration Manua l – 990 -2259 47 Part Numbers for XR E nclosur es Part Number for Battery Module XR Enclosur e Enclos u.
Appendi x Opti ons 48 AI S® 3000 & XR B atter y Encl osure 10 -40kVA , 400V , Oper ation M anual – 99 0-2259 Ma inte nance By pass Pan els wi th Po wer D ist ribut ion Capa bility The Mainte nance Bypass Panel provides overcurrent protectio n to the entire UPS sy s te m.
.
*990-2259* APC W orldw ide Custom er Suppo rt Cust omer s uppo rt fo r thi s or any oth er AP C pr oduct is a vaila ble a t no c har ge i n any o f the foll owing ways: • V i sit the APC W eb s ite to access documents in the APC Knowledge Base and to submit cus tomer supp ort re quest s.
Een belangrijk punt na aankoop van elk apparaat APC AIS 3000 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen APC AIS 3000 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens APC AIS 3000 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding APC AIS 3000 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over APC AIS 3000 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van APC AIS 3000 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de APC AIS 3000 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met APC AIS 3000 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.