Gebruiksaanwijzing /service van het product BC300 van de fabrikant APC
Ga naar pagina of 36
APC BC300 Series 40kW 208/450/480V User Guide Copyright ©2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor.
2 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Thank You Thank you for choosing the APC BC Series. Please read this User Guide thoroughly prior to using the system as it provides important information on safe and efficient use. The use of this product must comply with national, federal, state, municipal and local codes.
990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 3 Contents: 1.0 Introduction 4 1.1 Display Unit 4 2.0 UPS Stop/Start 5 2.1 UPS Stop (for stand-by) 5 2.2 UPS Start (from stand-by) 5 3.0 Operation 6 3.1 Operation Modes 7 3.2 Using the Keys 8 3.
4 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Introduction 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years.
UPS Stop/Start 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 5 2.0 UPS Stop/Start Only qualified electricians should start up or shut down APC BC300 Series UPS systems, and instructions in the Installation Guide should be followed.
6 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Operation 3.0 Operation The keyboard is used to program and control parameters and to display alarm messages and measured values.
Operation 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 7 3.1 Operation Modes The display automatically indicates which mode the unit is operating in.
8 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Operation 3.2 Using the Keys T able 2: Using the keys Key Function Key Function Scroll up through lists of e.g. parameters, alarms, or events. Display the time and date. If the unit is in the parameter mode, use this key to change the setting of a parameter from “OFF” to “ON.
Operation 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 9 3.3 Displaying Measurements The APC BC300 Series UPS measures several values during operation that you can display by pressing one or two keys.
10 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Operation When two keys are shown, press those keys simultaneously. Keys Sample Display Description Battery temp. 25° C Battery temperature is 77° F (25° C) Output peak curr 19 19 19 Aac Output peak current is 3 x 19 Aac.
Parameter Settings 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 11 4.0 Parameter Settings User parameters allow you to define the UPS settings. You can view and program the parameters listed in Table 2 below. The parameters are easy to access and program: simply follow the five steps below.
12 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Parameter Settings T able 4: P arameter Settings PARAMETER FACTORY SETTING DESCRIPTION Second Language OFF If you select ON, the APC BC300 Series displays all messages in its second language (Spanish).
Alarms and Events 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 13 5.0 Alarms and Events Alarms are indicated by a red light (above the left-hand corner of the display) and a 30-second acoustic signal. An alarm is registered in the alarm log as long as it is present.
14 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Alarms and Events 5.3 Alarm Messages T able 5: P ossible Alarms Alarm Message Description Action Battery MCB is off The battery breaker is open. If bypass voltage is within tolerance, the unit transfers to static bypass operation.
Alarms and Events 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 15 Charge reg. error (reg. = regulator) Failure in charge regulation. The unit transfers to battery until the “Low DC shutdown” alarm occurs; then, it transfers to stand-by and does not supply output voltage.
16 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Alarms and Events High output voltage (This alarm is usually only listed in the events log) The output voltage is higher than the alarm setting. The unit stays in the normal operation mode.
Alarms and Events 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 17 Low DC shutdown (This alarm is normal when the UPS has run on battery for a long time) The UPS has been running on battery power because of a power outage or problems in the AC input.
18 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Alarms and Events Mains is out of tolerance (This alarm occurs during a power outage) The utility (AC input) voltage is too high or too low, so the unit transfers to battery operation. If AC input returns to normal, the unit transfers back to normal operation.
Alarms and Events 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 19 Output is out of tolerance The output voltage is too high or too low (out of tolerance). If the alarm was caused by high output voltage, the unit transfers to static bypass operation if bypass is within tolerance.
20 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Alarms and Events Static switch 1 temp. warning The temperature on the heat-sink for the main static switch is higher than the warning setting. The unit’s status does not change. However, if the temperature continues to rise, the unit will sound a “Static switch 1 temp.
Alarms and Events 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 21 TSM 1 temp. shutdown Inverter module 1 has shut down because the temperature on the heat-sink is higher than the shutdown level. If bypass is within tolerance, the unit transfers to static bypass operation.
22 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Alarms and Events TSM 3 temp. shutdown Inverter module 3 has shut down because the temperature on the heat-sink is higher than the shutdown level. If bypass is within tolerance, the unit transfers to static bypass operation.
Alarms and Events 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 23 5.4 Displaying the Events Log The events log is a list of the last 250 alarms and operational modes.
24 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Maintenance and Testing 6.0 Maintenance and Testing APC recommends a periodic preventive maintenance check every six months. APC also recommends that the cooling fans be replaced every three years.
Maintenance and Testing 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 25 To perform a battery monitor test: 1. Press to display the user parameters. 2. Press or to scroll through parameters until the display shows “Battery monitor test.
26 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Maintenance and Testing a. Display the user parameter list by pressing . b. Use the arrow keys to scroll through the parameters until the display shows “Battery capacity test: xxx.” c. Switch the battery capacity test “OFF” by pressing .
Start-up and Shutdown Procedure 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 27 7.0 Start-up and Shutdown Procedure 7.1 Start-up from Maintenance Bypass This section contains instructions on how to start the UPS from maintenance bypass. The steps in this procedure apply to units with an APC-supplied Maintenance Bypass Panel.
28 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Start-up and Shutdown Procedure This section contains information on how to shut down the UPS from normal operation mode. This procedure applies to units with an APC-supplied Maintenance Bypass Panel.
Specifications 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 29 8.0 Specifications For a complete list of specifications, see the APC BC300 Series Installation Guide.
30 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Specifications For Users in Canada This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Options 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 31 9.0 Options APC offers many options for the APC BC300 Series UPSs. For more information, contact your local APC office. Note that some options only apply to certain models. 9.1 Optional Hardware and Software Features 9.
32 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 Options 9.2.2 Preventive Maintenance Visit Provides a single visit to examine the status and health of the APC system, to ensure proper operation over time.
WARRANTY 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 33 10.0 WARRANTY 10.1 Life Support Policy As a general policy, American Power Conversion (APC) does not recommend the use of any of .
34 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 WARRANTY AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APC’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC’S WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
How to Contact APC 990-1403 User Guide APC BC300 Series 40kW 208/450/480V UPS 35 11.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Tel.: +1 401 789-5735 Fax: +1 401 789-3710 Pre-sales Technical Support +1 877-474-5266 Post-sales Technical Support +1 877-287-7835 Web: www.
36 User Guide APC BC300 Series 40kW 208/450/480V UPS 990-1403 How to Contact APC.
Een belangrijk punt na aankoop van elk apparaat APC BC300 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen APC BC300 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens APC BC300 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding APC BC300 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over APC BC300 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van APC BC300 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de APC BC300 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met APC BC300 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.