Gebruiksaanwijzing /service van het product 06/11 50672801 van de fabrikant Lennox International Inc.
Ga naar pagina of 32
06/1 1 506728−01 *2P0611* *P506728-01* Page 1 201 1 Lennox Industries Inc. Dallas, T exas, USA These instruc tions are intended as a general guide and do not supersede local codes in any way. Cons ult authorities hav ing jurisdic tion before installation.
Page 2 506728−01 Model Number Identification P 13 036 − − Unit T ype P = Heat Pump Outdoor Unit Series Nominal Cooling Capacity 018 = 1.5 tons 024 = 2 tons 030 = 2.
Page 3 XP13 SERIES T ypical Unit Parts Arrangement LIQUID LINE FIL TER DRIER (BI−FLOW) FIELD CONNECTION FOR LIQUID LINE SET LIQUID LINE SER VICE V AL VE REVERSING VA LV E FIELD CONNECTION FOR V APOR.
Page 4 506728−01 Caps and Fasteners T orque Requirements IMPORT ANT Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum).
Page 5 XP13 SERIES INSER T HEX−HEAD EXTENSION HERE SER VICE POR T CORE SER VICE POR T CAP SER VICE POR T CORE TO OUTDOOR UNIT STEM CAP (V AL VE STEM SHOWN OPEN) INSER T HEX WRENCH HERE TO INDOOR UNIT BALL (SHOWN CLOSED) SER VICE POR T CORE TO INDOOR UNIT TO OUTDOOR UNIT A To open rotate stem counterclockwise 90°.
Page 6 506728−01 Recovering Refrigerant from Existing System Disconnect all power to the existing outdoor unit at the disconnect switch and/or main fuse box/breaker panel.
Page 7 XP13 SERIES New Out door Unit Placement CAUTION In order to avoid injury , take proper precaution when lif t- ing heavy object s. Remove existing out door unit prior to placement of new outdoor unit. See Unit Dimensions on p age 2 for sizing mounting slab, plat forms or support s.
Page 8 506728−01 LEG DET AIL BASE 2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER Concrete slab use two plastic anchors (hole drill 1/4") W ood or plastic slab no plastic anchor (hole d.
Page 9 XP13 SERIES Removing and Inst alling Panels LOUVERED P ANEL REMOV AL Remove the louvered panels as follows: 1. Remove two screws, allowing the panel to swing open slightly .
Page 10 506728−01 Line Set Requirement s This section provides information on: inst allation of new or replacement line set. Adding Polyol ester oil requirements New or replacement line set installation Using existing line set. ADDING POL YOL ESTER OIL REQUIREMENTS IMPORT ANT Mineral oils are not compatible with HFC−410A .
Page 1 1 XP13 SERIES ANCHORED HEA VY NYLON WIRE TIE OR AUT OMOTIVE MUFFLER-TYPE HANGER STRAP LIQUID LINE TO V APOR LINE W ALL STUD LIQUID LINE NON−CORROSIVE MET AL SLEEVE V APOR LINE − WRAPPED IN .
Page 12 506728−01 Brazing Connections Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves. W ARNING Polyol Ester (POE) oils used with HFC− 410A refr igerant absorb moisture very quickly . It is very important that the refrigerant sys tem be kept closed as much as possible.
Page 13 XP13 SERIES A TT ACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / V APOR LINE SER VICE V AL VES OUTDOOR UNIT LIQUID LINE V APOR LINE LIQUID LINE SERVICE VA LV E SUCTION / V APOR LIN.
Page 14 506728−01 WHEN BRAZING LINE SET TO SER VICE V A L VES, POINT FLAME A W A Y FROM SER VICE V AL VE. LIQUID LINE SERVICE V AL VE LIQUID LINE BRAZE LINE SET W rap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set .
Page 15 XP13 SERIES Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 16 .
Page 16 506728−01 Installing New Indoor Metering Device This out door unit is designed for use in HFC−410A systems that use a check / exp ansion valve metering device (purchased sep arately) at the indoor coil. See t he Lennox XP13 Engineering Handbook f o r app r o v e d ch e c k / exp a n s i on val v e ki t ma t c h − u p s .
Page 17 XP13 SERIES Leak T est Line Set and Indoor Coil IMPORT ANT Leak detector must be cap able of sensing HFC refr igerant. TO V APOR SER VICE V AL VE (ANGLE OR BALL TYPE) HFC−410A MANIFOLD GAUGE SET OUTDOOR UNIT HIGH LOW NITROGEN A Connect an HFC−410A manifold gauge set high pressure hose to the vapor valve service port.
Page 18 506728−01 Evacuating Line Set and Indoor Coil Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system.
Page 19 XP13 SERIES IMPORT ANT Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns. W ARNING Danger of Equipment Dam age. Avoid deep vacuum operation.
Page 20 506728−01 Figure 14. T ypical Unit Wiring Diagram.
Page 21 XP13 SERIES Figure 15. T ypical Factory Wiring Unit Start−Up IMPORT ANT If unit is equipped with a crankcase heater , it should be energized 24 hours before unit st art−up to prevent compressor damage as a result of slugging. UNIT ST ART−UP 1.
Page 22 506728−01 Service and W eigh In Refrigerant for Outdoor Unit s Delivered V oid of Charge The following procedures are only required if it has been determine that the new out door unit is void of charge. Skip to the next section if refrigerant charge is present.
Page 23 XP13 SERIES WEIGH−IN CHARGING LIQUID LI NE SET DIAMETER OUNCES PER 5 FEET (GRAMS PER 1.5 METERS) ADJUST FROM 15 FEET (4.6 METERS) LINE SET* 3/8" (9.5 MM) 3 OUNCE PER 5’ (85 GRAMS PER 1.5 M) *If line length is greater than 15 feet (4.6 meters), add this amount.
Page 24 506728−01 Optimizing System Refrigerant Charge This section provides instructions on optimizing the system charge. This section includes: Optimizing procedure Adjusting indoor airflo.
Page 25 XP13 SERIES 1. Check liquid and vapor line pressures. Comp are pressures with either second−st age heat or cooling mode normal operating pressures listed in table 4. T able 4 is a general guide and expect minor pressures variations. Significant pressure dif ferences may indicate improper charge or other system problem.
Page 26 506728−01 APPROVED MA TCHED SYSTEM COMPONENTS, T ARGETED SUBCOOLING (SC) V ALUES AND ADD CHARGE V ALUES Listed below are the approved matched system component s (air handlers and indoor coils), t argeted subcooling and add charge values for the XP13.
Page 27 XP13 SERIES Liquid Pressure Model Number Heating Cooling ºF (ºC)* 20 (−7) 30 (−1) 40 (4.5) 50 (10) 60 (16) 65 (18) 70 (21) 75 (24) 80 (27) 85 (29) 90 (32) 95 (35) 100 (38) 105 (41) 11 0 .
Page 28 506728−01 System Operation IMPORT ANT Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig.
Page 29 XP13 SERIES Compressor Delay (P5) The defrost control has a field−selectable function to reduce occasional sounds that may occur while the unit i s cycling in and out of the defrost mode.
Page 30 506728−01 Maintenance DEALER Maintenance and service must be performed by a qualified installer or service agency . At the beginning of each cooling season, the system should be checked as follows: Outdoor Unit 1. Clean and inspect the outdoor coil.
Page 31 XP13 SERIES Thermostat Operation See the thermost at homeowner manual for instructions on how to operate your thermost at. Heat Pump Operation Y our new Lennox heat pump has several characteristics that you should be aware of: Heat pumps satisfy heating demand by delivering large amount s of warm air into the living sp ace.
Page 32 506728−01 S tart−Up and Performance Checklist Job Name Job no. Date Job Location City S t ate Installer City S t ate Unit Model No. Serial No.
Een belangrijk punt na aankoop van elk apparaat Lennox International Inc. 06/11 50672801 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Lennox International Inc. 06/11 50672801 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Lennox International Inc. 06/11 50672801 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Lennox International Inc. 06/11 50672801 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Lennox International Inc. 06/11 50672801 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Lennox International Inc. 06/11 50672801 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Lennox International Inc. 06/11 50672801 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Lennox International Inc. 06/11 50672801 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.