Gebruiksaanwijzing /service van het product 700-2200 VA van de fabrikant Liebert
Ga naar pagina of 26
P OWER P ROTECTION U SER M A NUAL English 700-2200 VA 120 V PowerSure™ Interactive R DISCONTINUED PR ODUCT.
2 IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dange rous voltages, even when the AC cord is disconne cted from the electrical outlet.
3 it, or the safety ground will be re moved. Operate UPS only from a properly grounded 120 VAC outlet (2 wire plu s ground). 9. The UPS is equipped with a grounded NEMA 5-15P or L5-30P input power plug (depending upon model ). Do not defeat the safety purpose of this plug.
4 INTRODUCTION & SYS TEM DESCRIPTION Congratulations on your choice of the Liebert PowerSure™ Interactive Uninterruptible Po wer System (UPS). It provides conditioned power to microcomputers and other sensitive electronic e quipment. Upon generation, AC power is clean and stable.
5 MAJOR COMPONENTS TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide sur ge prot ection and filter Electromagnetic Interference (EMI) and Radio Frequenc y Interference (RFI ). They minimize any surges or interference present in the utility li ne and keep the sensitive equipment protected.
6 MINI-TOWER INSTALLATION 1. Unpack the UPS carefully noting the packi ng method. Retain the bo x and packing material for possible future shipme nt. CAUTION: The UPS is heavy (see spec ificatio ns). Take proper precautio ns when lifting or moving it.
7 RACKMOUNT INSTALLATION 1. Unpack the UPS carefully noting th e packing method. Retain box and p acking material for possible future shipment. CAUTION: The UPS is heavy (see s pecifications). Take the proper precautions when lifting or moving the UPS.
8 CONTROLS AND INDICATORS On/Off Button The On/Off button controls output power to connected load(s). CAUTION: Pressing the On/Off button w hen AC utility is not present will cause the UPS to begin operating from battery. This should not be performe d unless the UPS input is connected to a properly grounded receptacle.
9 POWERSURE™ INTERACTIVE MINI-TOWER 4 26 2 64 2 1 1 3 5 4 3 5 1 6 1 5 3 700 VA 1000 / 1400 VA 2200 VA Faul t I ndi cat or Lo ad/B att er y Lev el I ndi cat ors Alar m Silen ce/ Ba tte ry T es t B ut.
10 POWERSURE™ INTERA CTI VE RACKMOUNT 2200 Model 1 3 4 62 3 6 1 5 5 5 700-1400 Models *700 Model has detachable cord 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inlet 4- Intellislot™ Commun.
11 OPERATION NORMAL MODE OPERA TION During normal operation, utility po wer prov ides energ y to the UPS. The filters and the power conditioning circuit process this power to provide comp uter grade power to connected loads. The UPS maintains the batteries in a fully charged state.
12 BATTERY MODE OPERATION Battery mode occurs in event of extreme input conditions or comp lete utility failure. The battery system along with the bi-directional conv erter generates power for the connected load. During battery mode an alarm so unds every 10 seconds.
13 COMMUNICATIONS INTERFACE PORT The PowerSure™ Interactive UPS contains a standar d DB-9F recepticle loc ated on the rear of the UPS unit. Several si gnals are provid ed on this port and are assign.
14 UPS INTELLIGENT COMMUNICATIONS The PowerSure™ Interactive UPS has the capabi lity to communicate intelli gently with stand alone computers, network workstations, net work servers, or UNIX hosts via the DB-9 female connector locat ed on the rear of the UPS.
15 MINI-TOWER BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replaci ng the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door.
16 MINI-TOWER BATTERY REPLACEMENT 700 VA Model To Disconnect: Gentl y pull wiring away To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing towards connector 1000.
17 RACKMOUNT BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replacin g the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door.
18 Figure 3 Figure 5 Figure 4 Figure 1 Figure 2 Fi g ure 6 Figure 7 DISCONTINUED P R O D U C T.
19 TROUBLESHOOTING The information b elow indicates vario us symptoms a user may encounter in the event the PowerSure™ Interactive UPS dev elo ps a problem. Use this inf ormation to determine whether external factors ca use the problem and ho w to remedy the situation.
20 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS output short circuited or overloaded. Ensure UPS is off. Disco nnect all loads and ensure noth ing is lodged in output r eceptacles. Ensure loads are not de fective or shorted internally. UPS fails to start when On/Off button is pressed Internal fuse is blown, indicating internal fault.
21 POWERSURE™ INTERACTIVE TYPICAL BATTERY DISCHARGE CURVES (Discharge times are at 25° C ambient ) 0 25 50 75 100 0 20 40 60 80 Percent Load R un Ti me (Mi ns ) 0 25 50 75 100 0 20 40 60 80 Percent.
22 AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds; more than t wo minutes of run time remaining Low battery Two short beeps every five seconds.
23 MINI-TOWER SPECIFICATIONS Model Number PS700MT-120 PS1000MT- 120 PS1400MT-120 PS2200MT-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 5.5 x 14.4 x 7.0 (140 x 365 x 178) 6.8 x 17.5 x 8.9 (172 x 447 x 227) 6.
24 RACKMOUNT SPECIFICATIONS Model Number PS700RM-120 PS1000RM-120 PS1400RM-120 PS2200RM-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.
2 5 DISCONTINUED P R O D U C T.
1050 Dearborn Drive Columbus, OH 43229 614-888-0246 Technical Support U.S.A........................... ....................................1-800-222-5877 Outside the U.S.A ..................... ......................614-841-6755 U.K...................
Een belangrijk punt na aankoop van elk apparaat Liebert 700-2200 VA (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Liebert 700-2200 VA heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Liebert 700-2200 VA vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Liebert 700-2200 VA leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Liebert 700-2200 VA krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Liebert 700-2200 VA bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Liebert 700-2200 VA kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Liebert 700-2200 VA . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.