2 IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical outlet.
3 9. The UPS output supply sockets may be electrically live whenever the input power lead is plugged into the mains supply socket. Turning the UPS off does not electrically isolate the internal parts. To isolate the UPS, turn the UPS off then isolate it from the mains supply.
4 INTRODUCTION AND SYSTEM DESCRIPTION Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable.
5 MAJOR COMPONENTS TVSS and EMI/RFI Filters INPUT Dynamic Bypass Rectifier/PFC Inverter OUTPUT DC to DC Converter Battery Battery Charger TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide surge protection, and filter both electromagnetic interference (EMI) and radio frequency interference (RFI).
6 DC TO DC CONVERTER The DC-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
7 Re-plug the power input cable (A) into mains supply socket. Proceed with step 9.For 3000 VA models, a CEE 19 input cable is supplied. Proceed with the next step.
8 RACK-MOUNT CONVERSION DIAGRAMS RACK-MOUNT UPS CONVERSION AND INSTALLATION 1. Unpack the UPS carefully noting the packing method. Retain the box and packing material for possible future shipment. 2. CAUTION: The UPS is heavy (see specifications). Take proper precautions when lifting or moving it.
9 11. Ensure the load equipment is turned off, and plug all loads into the UPS output sockets. 12. For 700-2000 VA models, unplug power input cable from load equipment input socket and plug it into UPS input socket. Re-plug the power input cable into mains supply socket.
10 OPTIONAL BATTERY CABINET(S) INSTALLATION Up to two optional battery cabinets may be connected to the UPS to provide additional run time. Battery cabinets are designed to be placed on either side or beneath the UPS. 1. Unpack the UPS battery cabinet(s) carefully noting the packing method.
11 FERRITE BEAD INSTALLATION Serial Communications Attach the smaller enclosed ferrite bead clamp to the communication cable as shown in the drawing using the following directions: • Open the ferrite bead. • Place the communication cable inside the ferrite bead grove.
12 UPSTATION GXT™ On/Alarm Silence / Manual Battery Tes t Butto n Off/ Bypass Button Fault Indicator Bypass Indicator UPS On Indicator Battery Indicato r AC Input Indicato r Load/Battery Leve l Indi.
13 CONTROLS AND INDICATORS On/Alarm Silence/Manual Battery Test Button This button controls output power to connected load(s) and has three functions: On, Alarm Silence, and Manual Battery Test. Pressing this button will start up the UPS in order to provide conditioned and protected power into the mains socket.
14 UPS On Indicator (Green) The UPS On indicator is illuminated when the UPS inverter is operating and supplying power to your connected loads. Battery Indicator (Amber)The Battery indicator is illuminated when the UPS is operating from the battery system.
15 BATTERY MODE OPERATION Battery mode occurs in event of an extreme input voltage condition or complete mains failure. The battery system supplies power through the DC-DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds.
16 COMMUNICATIONS INTERFACE PORT The UPStation GXT™ UPS contains a standard DB-9 female connector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as f.
17 UPS INTELLIGENT COMMUNICATIONS The UPStation GXT™ UPS has the capability to communicate intelligently with stand alone computers, network workstations, network servers, or UNIX hosts via the DB-9 female connector located at the rear of the UPS.
18 BATTERY REPLACEMENT PROCEDURES CAUTION – A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries: - Turn off and disconnect the UPS from the mains power prior to opening the battery replacement door.
19 8. Carefully stand the UPS upright. Connect the UPS to the mains supply socket and turn on the UPS by pressing the on button. The UPS is ready for normal operation. 9. Dispose of batteries in accordance with your local laws and regulations. FOR 1000 TO 3000 VA RACK/TOWER MODELS: CAUTION: The battery assembly is heavy.
20 RACK / TOWER BATTERY REPLACEMENT Large battery doo r Battery connecto r Large battery doo r Screw hidden b y small battery doo r Small battery doo r Two front rubber fee t Front bezel (cover ) Rear.
21 UPSTATION GXT BATTERY RUN TIMES (Discharge times are at 25° C ambient) Internal Battery (minutes) Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT 10% 52 94 94 169 78 160 101 20% 40 45 45 12.
22 FUSE REPLACEMENT PROCEDURES CAUTION: Before changing the input fuse, turn off the UPS, and unplug the supply lead from the AC input supply and from the UPS. Replace the fuse with the same type and rating. Insert flat blad e screwdriver into slo t and turn fuse holde r to remove / instal l Fuse Holde r Input Fuse Remov e Instal l 1.
23 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT™ develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation.
24 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS is short circuited or overloaded Ensure UPS is off. Disconnect all loads and ensure nothing is lodged in output sockets.
25 SPECIFICATIONS MODEL NUMBER GXT700MT-230 GXT1000MT-230 MODEL RATING VA/W 700 / 490 1000 / 700 DIMENSIONS: mm (in) Unit W x D x H 162 x 430 x 225 (6.4 x 15.6 x 8.9) 162 x 430 x 225 (6.4 x 15.6 x 8.9) Shipping W x D x H 280 x 502 x 362 (11.0 x 19.75 x 14.
26 SPECIFICATIONS MODEL NUMBER GXT1000RT-230 GXT1000RTE-230 MODEL RATING VA/W 1000 / 700 1000 / 700 DIMENSIONS: mm (in) Unit W x D x H 177 x 522 x 430 (7.0 x 19.3 x 16.9) 177 x 522 x 430 (7.0 x 19.3 x 16.9) Shipping W x D x H 340 x 660 x 565 (13.38 x 26.
27 SPECIFICATIONS MODEL NUMBER GXT1500RT-230 GXT2000RT-230 GXT3000RT-230 MODEL RATING VA/W 1500 / 1050 2000 / 1400 3000 / 2100 DIMENSIONS: mm (in) Unit W x D x H 177 x 522 x 430 (7.0 x 19.3 x 16.9) 177 x 522 x 430 (7.0 x 19.3 x 16.9) 177 x 522 x 430 (7.
28 BATTERY CABINET SPECIFICATIONS MODEL NUMBER GXT36VBATT GXT48VBATT GXT96VBATT Used w/ UPS Model 1000RT 1500RT 2000RT/3000RT DIMENSIONS: in (mm) Unit W x D x H 177 x 522 x 430 (7.0 x 19.3 x 16. 9) 177 x 522 x 430 (7.0 x 19.3 x 16. 9) 177 x 522 x 430 (7.
29 LIMITED WARRANTY Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptibl.
30 1050 Dearborn Drive Columbus, OH 43229 614-888-0246 Technical Technical Support U.S.A. 1-800-222-5877 Outside the U.S.A. 614-841-6755 U.K. +44 (0) 1793 553355 France +33 1 4 87 51 52 Germany +49 89 99 19 220 Italy +39 2 98250 1 Netherlands +00 31 475 503333 E-mail upstech@liebert.
Een belangrijk punt na aankoop van elk apparaat Liebert 700-3000 VA (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Liebert 700-3000 VA heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Liebert 700-3000 VA vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Liebert 700-3000 VA leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Liebert 700-3000 VA krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Liebert 700-3000 VA bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Liebert 700-3000 VA kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Liebert 700-3000 VA . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.