AC P owe r Syste ms For Bu sines s-Critic al C ontinuity™ Lieber t ® GX T2U ™ Us er Man ual - 120V , 500-3000V A DISCONTINUED PR ODUCT.
DISCONTINUED P R O D U C T.
i T ABLE OF CONTENTS 1.0 G LOSSARY OF S YMB OLS . . . . . . . . . . . . . . . . . . . . . . . 3 2.0 I NTRODUCT ION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.0 M AJOR C OMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . .
ii 6.0 O PERATING I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . 17 6.1 Normal Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . 17 6.2 Bypass Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . 17 6.3 Battery Mode Operation .
1 I MPORT ANT S AFETY I NSTRUCTIONS SA VE THESE INSTRUCTIONS This manual contains importa nt safe ty instructions. Re ad all safety, installation, and o perating instruction s before opera ting the Uni nter- ruptible Power System (UPS). Adhere to all warnings on the unit and in this manual.
2 This UPS contains no user service able parts except the internal bat - tery pack. The UPS ON/Standby push buttons do not electrically iso- late internal parts. Under no ci rcumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn.
Glossary of Symbols 3 1.0 G LOSSARY OF S YMBOLS Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the u.
Introduction 4 2.0 I NTRODUCTION Congratulations on your choice of the Liebert GXT2U™ Uninterrupt- ible Power System (UPS). It provides con ditioned po wer to microcom- puters and other sensitive electronic equipment. Upon generation, AC power is clea n and stable.
Major Components 5 3.0 M AJOR C OMPONENT S 3.1 T RANSIEN T V OLT AGE S UR GE S UPPRESSION (TVSS) AND EMI/RFI F ILTERS These UPS components provide surge protection and filter both elec- tromagnetic interference (EMI) an d radio frequency interference (RFI).
Major Components 6 3.4 B ATTERY C HARGER The battery charger uti lizes energy from the utility po wer and pre- cisely regulates it to contin uously “float charge” the batteries. The bat- teries are being charged whenev er the Liebert GXT2U is plugge d in, even when the UPS is not turned on.
Major Components 7 3.8 L IEBERT GXT2U, R EAR V IEW Rev . USBCARD Input Fuse / Circuit Breaker AC Input Support Base Output Receptacles External Battery Connector Cooling Fa n USB card be ing fitted in.
Installation 8 4.0 I NST ALLATION 4.1 P REP ARATION 1. Visually inspect the UPS for fr eight damage. Report damage to the carrier and your local deal er or Liebert representative. 2. Decide where to place the Lieber t GXT2U. Install the UPS indoors in a controlled environment, wh ere it cannot be accidentally turned off.
Installation 9 4.3 R ACK -M OU NT UPS C ONVERSION AND I NSTALLATION 1. For slide rail install ations, first remove the top/side fin. Slide the top/side fin forward, then lift it up to remove. If d esired, install the optional rack mount handles th at were shipped wi th the UPS.
Installation 10 3. Determine the height position inside the rack enclosure where you want to mount the UP S or battery cabinet. Install rear member of each bracket assembly into rack enclosure with two (2) M5 screws provided in this kit. (See figure at right.
Installation 11 5. Prepare the UPS or battery cabinet (the “equipment”) for rack mounting by following instructions in the equipment’s user manual. The equipment may require addi tional parts to be added or pa rts to be removed for rack mounting.
Installation 12 8. Secure front of the equipment to rack mounting rails to prevent the equipment from sliding out of position. If secu ring holes are provided on front of the equipment that align with the center holes on return flange of front members, you can use the four (4) extra M5 screws provided in this kit to secure the equipment.
Installation 13 4.4 E XTERNAL B ATTERY C ABIN ET I NST ALLATION Optional Liebert external batt ery cabinets may be connected to the UPS to provide additional battery run ti me. External battery cabinets are designed to be placed all on one si de of the UPS or stacked beneath the UPS.
Controls and In dicators 14 5.0 C ONTROLS AND I NDICATORS 5.1 ON/A LARM S ILENCE /M ANUAL B ATTERY T EST B UTTON This button controls output power to connected load(s) and has three functions: • ON • Alarm Silenc e • Manual Battery Test ON - Pressing this button will start up the UPS in or der to provide conditioned and protected powe r.
Controls and In dicators 15 5.2 S T ANDB Y /M ANUA L B YP ASS B UTTON This button controls output power to connected load(s) and has dual functions : Standby and Manua l Bypass. 5.3 L OAD /B ATTERY L EVEL I NDICATORS (4 G RE EN , 1 A MBER ) The load/battery level indicators have dual functions.
Controls and In dicators 16 5.8 AC I NPUT I N DICATOR L ED (G REEN ) The AC Input indicator LED is il luminated when utilit y power is available and within the inpu t specifications.
Operating Instructions 17 6.0 O PERATING I NSTRUCTIONS 6.1 N ORMAL M ODE O PERATION During normal operation, utility power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads.
Operating Instructions 18 6.3 B ATTERY M ODE O PERATION Battery mode occurs in event of an extreme input voltage condition or com- plete utility fail ure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load.
Communications 19 7.0 C OMMUNICATIONS 7.1 C OMMUNICATIONS I NTERFA CE P ORT The Liebert GXT2U UPS has a standard DB-9 serial port female con- nector located on the rear of th e UPS unit. Several s ignals are pro- vided on this port and are assigned as fo llows: * Maximum voltage and current on pins 1, 7, 8, and 9 is 60 VDC ; 10.
Communications 20 7.2 P INS 4 & 5 - R EMOTE S HU T DOWN ON B ATTERY 1. This pin is functional only when th e UPS is in battery m ode. If the UPS is bein g powered by the utility , Pin 4 will i gnore any sig nal on this pin. 2. Pin 4 requires a 5- 12 VDC signal to shutdown.
Communications 21 7.3 P INS 5 & 6 - A NY -M ODE S HU T DOWN 1. Pin 6 of the 9-pin communication connector is used for “Any-Mode Shutdown” of the UPS output. This con trol input may be used in special applications to disable the UPS output power—both Inverter and Bypass.
Communications 22 7.4 UPS I NTELLIGENT C OMMUNI CATIONS The Liebert GXT2U is equipped with a Liebert IntelliSlot ® port to pro- vide advanced communica tion and monitoring options. Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
Configuratio n Program 23 8.0 C ONFIGURATION P ROGRAM The configuratio n program inclu ded with the Liebert GXT2U line allows modification of several UPS settings tha t were previously unavailable or required custom manufacturing.
Mainten ance 24 9.0 M AINTENANCE The Liebert GXT2U requires very little maintenance. The batteries are valve-regu lated, nons pillable , lead acid an d should be kept charged to obtain th eir designed life. The UPS con tinuously charg es the batteries when connected to the utility supply .
Mainten ance 25 9.1.1 Internal Battery Replacement Proc edures 1. Gently remove the front plastic bezel cover from the UPS. 2. Loosen and remove the four scre ws on the front battery door. Lay the battery door as ide for reassembly. Note: The 3000VA model includes a pull handle to remove this door.
Mainten ance 26 9.2 F USE R EPL ACEMENT 1. Remove the input fuse. 2. Locate the spare input fuse that is included with the UPS. 3. Insert the spare fuse into the fuse holder, and reinstall assembly into the UPS. Twist by hand; rotate clockwise unti l fuse holder locks into position .
Troubleshooting 27 10.0 T ROUB LESHOOTING The information below indicates various symptoms a user may encounter in t he event the Liebert GXT2U develops a prob lem. Use this information to determin e whet her external factors caused the problem and how to re medy the situation.
Troubleshooting 28 Under fault conditi ons, the Fault indi cators will be il luminated indefi- nitely while battery charger is operational, or for a maximum of 5 min- utes while ba ttery charger is not oper ational. If a problem persists, consult your local dealer, Liebert representative or contact the Liebert Worldwide Su pport Group.
Troubleshooting 29 Fault and Bypass indicator LEDs and all load l evel LEDs are illuminated. UPS overloaded or lo ad equipment is faulty. Check load level display and remove non-e ssential loads. Recal culate the loa d and reduce numb er of loads connected to UPS.
Troubleshooting 30 Fault and Bypass indicator LEDs and diagnostic LED C and E are illuminated. UPS shutdown due to a command from the communications port(s). Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system.
Troubleshooting 31 T able 2 Alarm conditions Condition Alarm Battery Mode (utility failure) One short beep every 10 seconds; more than 2 minutes of run time remaining Low Battery Two short beeps every.
Specifications 32 11 . 0 S PECIFICATIONS Model Number GXT2-500RT120 GXT2-700RT120 GXT2-1000RT120 Model Rat ing 500V A/35 0W 700V A / 490W 1000V A / 700W DIMENSIONS - in. (mm) Unit W x D x H 3.5 x 21.5 x 17 (87 x 547 x 430) 3.5 x 21.5 x 17 (87 x 547 x 430) 3.
Specifications 33 S PECIFICATIONS ( CONTINUED ) Model Number GXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 Model Rating 1500V A / 1050W 2000V A / 1400W 3000V A / 2100W DIMENSIONS - in. (mm) Unit W x D x H 3.5 x 21.5 x 17 (87 x 547 x 430) 3.5 x 21.5 x 17 (87 x 547 x 430) 3.
Battery Cabinet Specifications 34 12.0 B ATTERY C ABINET S PECIFICATIONS Model Number GXT2-48VBA TT GXT2-72VBA TT Used With UPS Model GXT2-500RT120 GXT2-700RT120 GXT2-1000RT120 GXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 DIMENSIONS - in. (mm) Unit W x D x H 3.
Battery Run Times 35 13.0 B ATTERY R UN T IMES Load% 500VA 700VA 1000VA 1500VA 2000VA 3000VA Internal Battery (minutes) 10% 494 248 191 144 56 91 20% 181 115 87 53 33 46 30% 107 79 48 38 26 30 40% 83 .
Product Warranty Registration 36 14.0 P RODUCT W ARRANTY R EGISTRATION To register for warranty protection: • Visit the Quick Links section of our Web site at: http://www.
NOTES DISCONTINUED P R O D U C T.
DISCONTINUED P R O D U C T.
DISCONTINUED P R O D U C T.
Ensuring The High A vaila bilit y 0f Mission-Critic al Dat a And Appli c ations. While every precaution has been tak en to ensure the accuracy and complet eness of this lite rature, Liebe rt Corporation assumes no responsibility and disclaims all liability for damages resulting from u se of this inform ation or for any errors or omissions .
Een belangrijk punt na aankoop van elk apparaat Liebert gxt2u (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Liebert gxt2u heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Liebert gxt2u vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Liebert gxt2u leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Liebert gxt2u krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Liebert gxt2u bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Liebert gxt2u kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Liebert gxt2u . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.