Gebruiksaanwijzing /service van het product GXT3-10000T220 van de fabrikant Liebert
Ga naar pagina of 32
AC P ow er For Bu siness-Criti cal C ontinuity™ Li eb er t ® GX T3-10000T220 ™ User Ma nual, 10 kVA, 50/60 Hz, 120/208/220V.
.
i T ABLE OF CONTENTS I MPORT AN T S AFE TY I NSTRUC TIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 I NTRODUCTI ON AND S YSTEM D ESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . .
ii 5.0 M AINTENAN CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 5.1 Test, Replacement and Disposal of Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 I MPORT ANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual con tains important safety i nstructions. Read al l safety and opera ting instructions before operating the uninterrupti ble power system (UPS). Adhere to all warnin gs on the unit and in this manual.
2 ! WARNING Although the Liebert ® GXT3 ™ has been designed and manufactured to ensure safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions: • Turn Off and isolate the Liebert G XT3 before cl eaning it.
3 Leakage Current ELECTROMAGNETIC COM PATIBILITY —The Liebert ® GXT3 ™ complies with the limits for a Class A Digital Device, Pursuant to Part 15 of FCC ru les.
Introduction and System Descriptio n 4 1.0 I NTRODUCTION AND S YSTEM D ESCRIPTION Congratulations on your choice of the Liebert ® GXT3 ™ -10000T220 UPS. It provid es conditioned power to microcomputers and other se nsitive electronic equipment. When generated, AC power is clean and stable .
Introduction and System Descriptio n 5 1.1 Device Overview The following table provides an overview of the various versions of the device: Figure 2 Liebert ® GXT3-10000T220 ™ front and rear vie ws .
Unpacking the UPS an d Site Preparation 6 2.0 U NP ACKING THE UPS AND S ITE P REP ARATION 2.1 Inspection Upon receiving your Liebert ® GXT3-10000T2 20 ™ , examine the packaging for any signs of mishandling or damage. While remo ving shipping materi als, inspect the UPS for damage.
Unpacking the UPS an d Site Preparation 7 2.4 Environment al Conditions Install the Liebert ® GXT3 ™ indoors in a controlled environmen t where it cannot be accidentally turned off. Pla ce it on a level, even surface in an area with unrestricted ai rflow around the uni t.
Installation 8 3.0 I NST ALLATION 3.1 Electrical prep arations Before beginning installation , the input source must be isolated an d locked out to prevent connection during installation. The input circu it breaker on the rear of the UP S m ust be in the Off position.
Installation 9 3.4 External Elect rical Connections The external electrical connections may be accessed by re moving the protective panel on the rear of the UPS (see Figure 2 ) (panel ships loose from fa ctory). Se lect a conduit knockout appropriate for your cabling, based on local electrical codes.
Installation 10 Figure 6 Dual source input su pply—input and output connections Figure 7 Hardwire terminals 3.6.1 Input and Output Connection Requirement s • Any 120V loads mus t be distributed evenly be tween X1-X2, X1 -X4 and X4-X2. Do not conn ect loads between X3-X2 or between X3-X4—these are not standard voltages.
Installation 11 3.7 Connecting Power Cables 1. Open the UPS input breaker. 2. Op en the UPS bypass breaker. 3. Set the maintenance breake r to the Bypass position. 4. Remo ve the electrical connection protective panel, if insta lled, from the rear UPS panel.
Operation 12 4.0 O PERATION 4.1 Block Diagram The Liebert ® GXT3-10000T220 ™ consists of the following main components: • 2 utility inputs wi th separa te breakers—uti lity and bypass • recti.
Operation 13 4.2 Control Panel The Control Panel’s LCD and buttons are used to initiate various UPS operations, tests and commands and to view the status of the UPS. By pressing the Menu Up or Menu Down and Ente r keys , it is possible to scroll through the various menus.
Operation 14 Figure 1 1 Menu tree St a rt W indow Syst em St at us Ma i n Setup Cont rol Cont ras t Set Batt e ry Te s t Al arm Cont rol Tu r n U PS On /Off St at us Log About Versi o n Language T ag .
Operation 15 T able 3 Displayed text—syst em block and main menu Item # and Name Description Status Menu Measure value Unit Output Volt V Output Freq 0.1Hz Output Current A Output Watt W Output VA VA Output Load % Input Volt V L2 Input Volt N/A L3 Input Volt N/A Input Freq 0.
Operation 16 4.2.2 Battery Setup Parameters 4.2.3 W arning Indicators If a warning indicat ion appears, the UPS continues to operate. The warning message altern ates with UPS mode once a second.
Operation 17 4.2.4 Fault Indicators If a fault occurs, the UPS automatically switches to BYPASS mode, ONLY in case of a battery disconnect fault will the original operating mode be maintained. Th e fault message alternates with UPS mode once a second, the red Fault LED illuminates on the control panel and the buzzer sounds continuously.
Operation 18 4.3 Initial UPS St artup Procedure 1. Inspect all power connections to en sure they are correct and secure. 2. Open external circuit breakers/fused di sconnect s to the connected loads. 3. Cl ose all upstream circuit breakers an d fused disconnects.
Operation 19 4.6 Return from Maintenance Byp ass 1. Ensure all switches and circuit brea kers upstream of the UPS are closed. 2. En sure that both input circuit breake rs are in th e On position. 3. Turn the Maintenance breake r from BYPASS to UPS and replace the cover.
Maintenance 20 5.0 M AINTENANCE 5.1 T est, Replacement and Disposal of Batteries The Liebert ® GXT3 ™ is designed to allow the us er to replace the internal ba ttery pack safely. Refer to Table 7 for internal battery pack part numbers for Li ebert GXT3 UPS and Liebert Ext ernal Battery Cabinets: Read all safety cautions before proceeding.
Communication 21 6.0 C OMMUNICATION 6.1 Communication Interface Port The Liebert ® GXT3 ™ UPS has a terminal block on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows. 6.2 Dry Cont act The Dry Contact includes eight pins, as shown an d defined in Figure 12 .
Communication 22 6.2.2 Battery Mode Shut down Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no powe r to the lo ad when the UPS is On Ba ttery. The auxiliary power for the UPS will st ill be active.
Communication 23 6.3.1 Liebert ® MultiLink ® Liebert MultiLink continua lly monitors the UPS and can shut down your computer or server in the event of an extended power failure. Liebert MultiLi nk can also be configured for use without the USB cable when the Liebert IntelliSlot ® SNMP/Web card is installed in the UPS.
Trou bleshooting 24 7.0 T ROUBLESHOOTING If any technical problems should occur, ch eck the f ollowing before contacting Liebert ® technical support: • Is the utility vo ltage pr esent at the UPS i.
Specifications 25 8.0 S PECIFICATIONS Ta b l e 9 L i e b e r t ® GXT3 ™ specifications Model Rating, VA (W) 10,000 (9000) Dimensions, in. (mm) Unit, W x D x H 31.
Specifications 26 T able 10 Battery cabinet specificat ions Model Number GXT3-240TBATTCE Dimensions, W x D x H, in. (mm) Unit 31.5 x 11.81 x 26.57 (800 x 300 x 675) Shipping 41.
Product Warranty Registra tion 27 9.0 P RODUCT W ARRANTY R EGISTRATION To register for warranty protection: • Visit the Quick Links section of Liebert’s Web site at: http://www.liebert.com • Click on Product Warranty Registration and fill in the form.
Ensuring The Hi gh Av aila bilit y Of Mission-Critic al Data And Ap plic ations. Emerson Net work P ower , a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critic al Continuity ™ from grid to chip f or telecommunication networks, data centers, health care and industrial facilities.
Een belangrijk punt na aankoop van elk apparaat Liebert GXT3-10000T220 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Liebert GXT3-10000T220 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Liebert GXT3-10000T220 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Liebert GXT3-10000T220 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Liebert GXT3-10000T220 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Liebert GXT3-10000T220 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Liebert GXT3-10000T220 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Liebert GXT3-10000T220 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.