Gebruiksaanwijzing /service van het product 195DCS van de fabrikant Lifebreath
Ga naar pagina of 32
® CLEAN • FRESH • AIR * LEA VE FOR HOMEOWNER NOTE: Due to ongoing research and product development, specifications, ratings and dimensions are subject to change without notice.
2 T able of Content s Introduction................... ...... .......................................... 2 W arranty ....................................................................... 2 ERV Questions & Answers .................................
3 ER V Questions & Ans wers What is the difference between an HRV and an ERV? The core in an HRV (Heat Recovery Ventilator) transfers heat from one air stream to the other.
4.
5 Removably Heat Recovery Core Drain Pan Drain spout FRONT TOP knockout for side mounting of EXHAUST return port 6" round collar converted to oval minimum 18 inches (459 mm) required for service access Threaded inserts (4) at corners SUPPLY Fresh air from outside 5" round collar SUPPLY Fresh air to building 6" round (conv.
6 DATE: __________________________ PROJECT: __________________________________________ MECHANICAL CONTRACTOR: _____________________________ Model 155MAX ENGINEERING DA T A THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams.
7 PERFORMANCE HVI CERTIFIED Net supply airflow in cfm (L/s) against external static pressure E.S.P cfm L/s @ 0.1” (25 Pa) 232 (109) @ 0.2” (50 Pa) 223 (105) @ 0.
8 Model MAX TOP ENGINEERING DA T A THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor.
9 Model 195DCS 49 " (1245) ST ALE AIR TO OUTSIDE FRESH AIR TO INSIDE 14 3/4" (375) 19" (483) Ports 7" (178 mm) CONDENSATE DRAINS BLOWERS *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
10 Model 300DCS 49 " (1245) ST ALE AIR TO OUTSIDE FRESH AIR TO INSIDE 14 3/4" (375) 19" (483) Ports 7" (178 mm) CONDENSATE DRAINS BLOWERS *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
11 Model 200ER V ® CLEAN • FRESH • AIR ENGINEERING DA T A LATENT RECOVERY/MOISTURE TRANSFER CORE The cross-flow energy recovery core transfers heat and water vapour between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor.
12 Model 200ER VD ® CLEAN • FRESH • AIR ENGINEERING DA T A LATENT RECOVERY/MOISTURE TRANSFER CORE The cross-flow energy recovery core transfers heat and water vapour between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor.
Oper ating the ControlAir 15 Plugging in the HRV/ERV energizes the unit. A self test function will be performed every time the HRV/ERV is energized (refer to “Self Test” for more details). After the self test has completed successfully the HRV/ERV will default to Speed 1.
14 T o select mode of oper ation for ControlAir 15 Press and hold the fan selection button on the Control Pad. After 5 seconds the control will begin to cycle each mode holding each for 2 seconds. Release the button when the desired mode of operation is reached.
15 ControlAir 15 OPTION AL REM OTE CONTROLS 0011 NEW! AIR SENTR Y™ AIR QUALITY SENSOR LOCATION: Kitchen, basement, work place (connect 1/unit only). • Digital Air Quality Monitor. • Status light indicates fan speed. • Increases ventilation to remove odours and contaminants.
16 Some models have a built-in dehumidistat (an optional remote wall mount dehumidistat can be installed, see Optional Remote Controls), to control harmful, excess humidity during the heating season . The dehumidistat operates in % of RH (relative humidity) with 80 being high and 20 being low .
17 95 MAX Port Specifications The 95 Max Heat Recovery Ventilator (HRV) has been designed to allow the installer to choose between two possible positions on the cabinet for the INDOOR EXHAUST (return from building) port. Illustrations in this manual show standard (side mounted) port location .
18 INS T ALLA TION Location The HRV/ERV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV/ERV would be located in the mechanical room or an area close to the outside wall where the weatherhoods will be mounted.
INS T ALLING AIR DUCTS A well designed and installed ducting system will allow the HRV/ERV to operate at its maximum efficiency. Always try to keep duct runs as short and straight as possible. See Installation Diagrams for various installation options.
20 SUPPL Y AIR DUCTING In homes without a forced air furnace, fresh air should be supplied to all bedrooms and living areas, excluding bathrooms, kitchen and utility areas. It should be supplied from high wall or ceiling locations. Grilles that diffuse the air comfortably such as the Techgrille™ are recommended.
21 DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN (Stale air drawn from key areas of home) Forced Air Furnace Outdoors *Unit is normally balanced on HIGH speed with furnace blower ON. EXHAUST AIR from various parts of home.
22 Simplified Installation Option 1 (Return/Return Method) Note: Option 1 is the pr eferred / r ecommended method when doing a simplified installation. Example diagram only - duct configuration may change depending on model *Unit is normally balanced on HIGH speed with furnace blower ON.
23 Simplified Installation Option 2 (Supply/Return Method) RETURN AIR DIRECT CONNECTION of both the HRV/ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE Outdoors Cool Air Return NOTES: 1. Furnace blower may be required to operate when ventilation from HRV/ERV is required.
24 Fully Dedicated System Example diagram only - duct configuration may change depending on model Please Note: It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.
25 It is necessary to have balanced air flows in an HRV/ERV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit.
26 Push and turn with slotted screwdriver. Damper automatically locks when pressure is released. When connecting ductwork to the collar, take note where screws are located. Screws should be located no further than 1/2” from outside edge of collar, so as not to impede operation of the damper.
27 1. Inspect Exterior Hoods at least once a month. Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen).
28 1. Inspect Exterior Hoods at least once a month Make sure exhaust and fresh air supply hoods are not blocked up or restricted by leaves, grass, or dirt. WARNING: Blockage of hoods may cause an imbalance. 2. Clean Air Filters Four T imes a Y ear The standard filters equipped with your ERV are removable and washable.
S Y MPTOM CA USE SOLUTION Poor Air Flows Supply air feels cold Dehumidistat is not Operating Humidity Levels are too High Condensation is appearing on the windows Humidity Levels are too Low HRV/ERV a.
30 T echnical Bulletin When using the ControlAir 15 r elay contacts to initiate blower operation on a furnace, certain thermostats will initiate the outdoor cooling condenser when R and G are closed. Use this wiring configuration to stop the ControlAir15 relay contacts from initializing the condenser unit.
31 FAN MOTOR GRN T12 T13 CAPACITOR WHITE BLK RED WHITE ORG YEL DIRECT MOUNTED CAPACITOR T9 T10 T11 T12 T13 T14 T5 T4 T3 GROUND DOOR SWITCH WHITE BLACK HIGH VOLTAGE 12V LOW VOLTAGE FIELD INSTALLED LEGE.
511 McCormick Blvd. London, Ontario N5W 4 C Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.c o Website: www.lifebreath.co m .
Een belangrijk punt na aankoop van elk apparaat Lifebreath 195DCS (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Lifebreath 195DCS heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Lifebreath 195DCS vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Lifebreath 195DCS leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Lifebreath 195DCS krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Lifebreath 195DCS bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Lifebreath 195DCS kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Lifebreath 195DCS . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.