Gebruiksaanwijzing /service van het product RNC10 van de fabrikant Lifebreath
Ga naar pagina of 36
TI-RNC 0108 Residential Heat Reco very V entilators (HR V) Manufactured with 2 Speed RNC Electr onics Installation Instructions for Heat Reco very V entilators with 2 Speed RNC Electronics RNC Series .
Introduction.........................................................................2 Engineering Data - RNC95 .............................................3-4 Engineering Data - RNC155 ...............................................5 Engineering Data - RNC200 .
3 Removab le Heat Recovery Core Drain P an Drain spout FRONT TOP knockout f or side mounting of EXHA UST return port 6" round collar converted to oval minimum 18 inches (459 mm) required for service access Threaded inserts (4) at corners SUPPL Y Fresh air from outside 5" round collar SUPPL Y Fresh air to building 6" round (conv .
4 RNC95 Specifications The RNC95 HRV (Heat Recovery Ventilator) has been designed to allow the installer to choose between two possible positions on the cabinet for the Stale Air Exhaust (from building) port. Illustrations in this manual show standard (side mounted) port location.
5 Engineering Data - HRV Model RNC155 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor.
6 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor.
7 All units conform to CSA and UL standards Engineering Data - HRV Model RNC10 Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: ___.
8 All units conform to CSA and UL standards Engineering Data - HRV Model RNC20 Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: ___.
9 All units conform to CSA and UL standards Engineering Data - HRV Model RNC5-TPD Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: .
10 All units conform to CSA and UL standards Engineering Data - HRV Model RNC120D Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: .
11 Engineering Data - HRV Model RNC120D FRESH AIR FROM OUTSIDE ST ALE AIR TO OUTSIDE ST ALE AIR FROM BUILDING FRESH AIR TO B UILDING BOTT OM VIEW FOR HORIZONT AL MOUNT SER VICE CLEARANCE FROM BO TTOM OF UNIT IS MINIMUM 3’0” SIDE VIEW FOR HORIZONT AL MOUNT ALL DUCT COLLARS ARE 5” DIAMETER Connect drain hose to spout located in door .
Ventilation Dehumidistat PART NO. 99-116 The High/Low Speed Switch initiates High or Low speed ventilation. This control also has an ON/OFF Switch and a Dehumidistat Dial.
13 Location Selection The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted.
14 Suspending the RNC120D STRAPS AND SCREWS (supplied) JOIST F ASTENERS (not supplied) DET AIL Using full length hanger straps is recommended for vibration contr ol, but can be shorter if required. Horizontal Installation W all Mounting the HR V V er tical Installation The unit must be mounted le vel for pr oper drainage of the condensate pans.
15 Drain Connection (HRV Only) During a defrost cycle, the HRV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The HRV cabinet has prepunched holes for the drain (see below). Insert the drain spout through the hole in the drain pan.
16 The Three Methods of Installation The three methods of installation for the HRV system are the Simplified, Partially Dedicated and Fully Dedicated Installations.
17 The Simplified Installation (Return/Return Method) Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.
18 The Partially Dedicated Installation Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc.
19 The Fully Dedicated Installation Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc.
Intake Weatherhood Requirements • Should be located upstream (if there are prevailing winds) from the exhaust outlet. • At least 6' (2m) from the exhaust weatherhood.
21 Electrical The HRV unit should be plugged into a standard designated (120VAC) electrical outlet with a ground. The outlet should be serviced by a separate 15 amp/120V circuit. An extension cord should not be used with this appliance. A qualified service technician should make any required electrical connections.
22 Red to Red Black to Black Green LED Drive to Green DEH UMI DISTA T Red to Red Orange to Orange Black to Black Dehumidistat Ventilation Control Part No. 99-116 20 Minute Timer (shown in a Decora cover plate)* Red to Red Black to Black Remote Dehumidistat Part No.
23 Recirculating Damper Defrost (4 port models) The recirculating damper defrost HRV has an electronically controlled damper defrost mechanism. The defrost timer is activated when the outside temperature drops below 27°F (- 3°C).
24 It is necessary to have balanced air flow in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit.
25 Air Flow Balancing Place pitot tube a minimum of 18" from blower or elbows Note: Duct connections may vary , depending on model. Outdoors MAGNEHELIC Pitot tube Magnehelic gauge M A GN E HELIC .
26 AccuFlow Gauge Kit 1 - Accu-Flow Balancing Gauge 2 - Connection Hoses 4 - Rubber Fittings 1 - Instruction Page Lifebreath Accu-Flow is designed to quickly and accurately balance the airflows on units equipped with balancing ports. Normally the HRV/ERV would be balanced on high speed.
27 Air Flow Balancing using the Door Ports Models RNC155 and RNC200 Only The door ports ( MODELS RNC155 & RNC 200) are designed to quickly and measure the airflows for balancing.
28 When using the Interface relay contacts to initiate b lower operation on a furnace, cer tain thermostats will initiate the outdoor cooling condenser when R and G are closed. Use this wiring configur ation to pre vent the Interf ace rela y contacts from initializing the condenser unit.
29 Wiring Diagrams Model RNC5-TPD DEFROST DET AILS P1 12 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SP ARE PCB PLUG - IN RED BLACK PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MO TOR ORANGE RED B.
30 Wiring Diagrams RNC120D HRV Control Box DEFROST DET AILS P1 12 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SP ARE PCB PLUG - IN RED BLACK PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MO TOR ORA.
31 RNC3WIRINGDIAGRAM HIGHVOLTAGE 12VLOWVOLTAGE FIELDINSTALLED LEGEND 12VLOWVOLTAGE FANMOTORDETAILS CAPACITOR ORANGE WHITE BLACK GREEN DIRECTMOUNTEDCAPACITOR T6 T.
32 Troubleshooting Poor Air Flow Supply air feels cold Dehumidistat is not Operating Humidity Levels are too High in Winter Condensation is appearing on the windows Humidity Levels are too Low HRV and.
33 1. Inspect Exterior Hoods at least once a month. Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen).
34.
35.
36.
Een belangrijk punt na aankoop van elk apparaat Lifebreath RNC10 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Lifebreath RNC10 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Lifebreath RNC10 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Lifebreath RNC10 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Lifebreath RNC10 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Lifebreath RNC10 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Lifebreath RNC10 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Lifebreath RNC10 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.