Th i s m an ua l m us t o nl y b e u se d b y a qualified heating installer / serv ice technician. Read all instructions, including this manual, the SYNC Installation and Operation Man ual, and the SYNC Serv ice M anual, before installing. Perform steps in the order given.
2 Contents 1. INST ALLA TION Program Installation ..................................................... 3 USB Installation............................................................ 3 Program Setup ....................................................
PC Program Instructions 1 Installa tion Prog r am installa tion There are tw o programs available for programming and monitoring the SYNC boilers. SITECS937L ab is used to monitor the operation of the boiler and program a few display- related parameters .
4 1 Installa tion Star ting the prog ram T o start one of the programs, double-click on the ic on (if you put it on your desktop), or click on Start, then Programs, and select the program you wish to start. See FIG 1-1 and FIG 1-2 abov e. There are tw o access levels for this program.
2 Sta tus Scr een 5 Figure 2-1 SMART TOUCH S tatus Screen T o monitor and r e cor d the oper ation of the heater , click on the Status tab along the top of the Main Scr een w indow (FIG. 1-1, page 4). W hen using the SITECS937Lab progr am, you will need to choose whic h controller you wish to monitor .
2 Sta tus Scr een 6 At the t op r ight of the window is the Fan Speed status information. I ncluded in the Fan Speed status are Min., Max., and Ignition fan speeds. If Ramp Delay is activat ed, the Ramp Delay limit is sho w n. The target and actual fan speeds are display ed, and if the ac tual speed is within acceptable limits.
7 3 Gr aphics Scr een The Graphics Screen allows y ou to observe the changes in various readings while the heater operates (see FIG. 3-1). N ote that the vertical scale has two numbers for each division.
8 4 F ault Histor y Screen Figure 4-1 Fault History Screen The Fault Hist or y Screen provides historical data about the operation of the SMAR T TOUCH co nt rols.. Click on the Fault history button along the top of the Main Screen window (FIG. 1-1), and then click on Read from Control in the pull-down menu.
9 5 Cascade Screen Figure 5-1 Cascade Screen The Cascade Screen pro v ides the status of the cascade system. The PC must be connect ed to the Leader (address 0-1) appliance. Click on the Cascade button along the top of the Main Scr e en window (FIG. 1-1).
6 P ar ameter s Parameter infor mation screens By acc essing the Parameter I nformation Screens on the SMAR T TOUCH program, the installer can v iew all of the SMAR T TOUCH parameters. The installer can also change certain specific parameters to fine tune the operation of the boiler to the installation.
11 6 P ar ameter s (continued) Changeable par ameter s The following is a brief discussion of the changeable parameters, their default setting s, the range of adjustment, and their location. The title for the par ameters ma y differ slightly from the PC to the boiler displa y .
12 PC Program Instructions 6 P ar ameter s Set 2: Functional Data Set 2 is accessed b y clicking on Parameters at the t op of the Main Scr een window , then clicking on Set 2: Functional Data on the pull-down menu (FIG. 6-1, page 10). Cascade control P arameters 2DJ and 2DK determine the time delays used by the Cascade.
13 PC Program Instructions 6 P ar ameter s (continued) Pa r a m e t e r 2EB sets the pump delay time for the boiler pump after an ov er-temperature c ondition.
14 PC Program Instructions 6 P ar ameter s SH off-on differential (SH off/on df) The SH Off-on Differential sets ho w many degrees below the turn-off temperature the outlet temperatur e has to go before the boiler will turn on. This parameter can be changed b y accessing parameter 4AE .
15 PC Program Instructions 6 P ar ameter s (continued) T ank differential temp This parameter determines how far belo w the tank setpoint the tank sensor temperature must go t o star t a HW call for heat. This setting can be adjusted by accessing parameter 4A T .
16 PC Program Instructions 6 P ar ameter s Cascade Each burner control in the Cascade m ust be given a unique address. This address can be changed by ac cessing parameter 4CC . The Leader (top) burner (to which the thermostat/zone control, system sensor , and system pump (if controlled by the boiler) are c onnected) must be set t o address 0.
17 PC Program Instructions 6 P ar ameter s (continued) Figure 6-10 Parameter Set 4F OA reset water temp at min outdoor temp (4FC) (Reset T Lo Out) W h en the outdoor air t emperature drops to its minimum setting ( 4FC ), the water temperature setpoint will be at this value.
18 PC Program Instructions 6 P ar ameter s Figure 6-1 1 Outdoor Air Reset Curve Figure 6-12 Parameter Set 4G BMS Setpoint at min volt age (BMS setpt min V) If par ameter 4CB is set t o 2, the co ntrol must kno w what minimum setpoint temperature t o use.
19 PC Program Instructions 6 P ar ameter s (continued) Figure 6-13 Save Parameter File Window Storing p arameters on your PC Once y ou have customiz ed the parameters for a particular heater , y ou can store the new settings on your PC.
Revision Notes: Revision A initial release. SYNC-PCP Rev A Printed in the USA 4/10.
Een belangrijk punt na aankoop van elk apparaat Lochinvar 1 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Lochinvar 1 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Lochinvar 1 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Lochinvar 1 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Lochinvar 1 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Lochinvar 1 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Lochinvar 1 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Lochinvar 1 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.