TECHNICAL & SER VICE MANUAL CONTENTS 1. P ART NAMES AND FUNCTIONS .......... 2 2. SPECIFICA TION ..................................... 4 3. OUTLINES AND DIMENSIONS .............. 6 4. WIRING DIAGRAM ................................. 7 5 . REFRIGERANT SYSTEM DIAGRAM .
2 1 P ART NAMES AND FUNCTIONS Indoor unit Wireless remote controller ON/OFF TEMP FA N VA N E TEST RUN AUTO ST OP AUTO ST ART h min LOUVER MODE CHECK RESET SET CLOCK MODEL SELECT NOT A VAILABLE CHECK T.
3 3 Wired remote controller °F°C °F°C ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SA T ON OFF Hr AFTER FIL TER FUNCTION ONL Y1Hr. WEEKL Y SIMPLE AUTO OFF P AR-21MAA ON/OFF FIL TER CHECK OPERA TION CLEAR TEST TEMP .
4 2.3 8,000 0.03 0.15 2.6 9,000 0.03 0.15 Note : Unit converter kcal/h = kW × 860 Btu/h = kW × 3,412 cfm = m 3 /min × 35.31 lb = kg/0.4536 *Above specification data is subject to rounding variation.
5 5 Parts name Service Ref. Symbol TH21 TH22 TH23 FUSE MF C1 MV LEV TB2 TB5 TB15 Resistance 30°F/15.8k , 50°F/9.6k , 70°F/6.0k , 80°F/4.8k , 90°F/3.9k , 100°F/3.2k Resistance 30°F/15.8k , 50°F/9.6k , 70°F/6.0k , 80°F/4.
6 OUTLINES AND DIMENSIONS 3 Detailed figure dwg (ABC) (Knockout hole) 5/32(4) 1-31/32(50) 3/32(2.5) 5/8(16) 1-1 1/32(34) 13/32(10) 13/32(10) 1-25/32(45) 5° 3° 31/32(24.4) 45° Knockout hole for left piping 2-1/8(54) 3-19/32(91.5) 1-25/32(45) 3/32(2.
7 WIRING DIAGRAM 4 Mark Meaning LED1 Main power supply Main power supply (indoor unit: 208-230V) power on lamp is lit Function LED on indoor board for service ON OFF 1234 MODELS SW2 P06 ON OFF 1234 MODELS SW2 P08 <Fig. 1> LED2 Power supply for MA-Remote controller Power supply for MA-Remote controller on lamp is lit Legend Symbol I.
8 5 REFRIGERANT SYSTEM DIAGRAM Strainer (#100mesh) Strainer (#100mesh) Strainer (#100mesh) Heat exchanger Room temperature thermistor TH21 Gas pipe temperature thermistor TH23 Liquid pipe temperature thermistor TH22 Gas pipe Liquid pipe Flare Linear expansion valv e Gas pipe PKFY -P06/08NBMU-E { 12.
9 6 MICROPROCESSOR CONTROL PAR-21MAA ON/OFF FILTER CHECK OPERA TION CLEAR TEST TEMP . MENU BACK DA Y MONITOR/SET CLOCK ON/OFF ûF ûC ûF ûC ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SAT ON OFF Hr AFTER FILTER FUNCTION ONLY1Hr . WEEKLY SIMPLE AUTO OFF INDOOR UNIT CONTROL 6-1.
10 Control modes Control details 1-1. Thermo regulating function (Function to prevent restarting for 3 minutes) Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21). Dry thermo ON Room temperature desired temperature + 2°F Dry thermo OFF Room temperature desired temperature 1-2.
11 Control modes Control details Set by remote controller . Remarks 1. Fan Ty p e Fan speed notch 4 speeds type [Low], [Mid2], [Mid1], [High] 2. V ane (up/down vane change) Same as the control perform.
12 Control modes Control details 1-1. Thermoregulating function (Function to prevent restarting for 3 minutes) • Room temperature desired temperature -2°F ···Thermo ON • Room temperature desired temperature ···Thermo OFF 1. Thermoregulating function Remarks 2-1.
13 → Control modes Control details 2. Fan Remarks 2-3. Thermo OFF mode When the thermoregulating function changes to OFF , the indoor fan operates in [Extra low].
14 TROUBLESHOOTING 7 7-1. HOW TO CHECK THE P ARTS PKFY -P06NBMU-E PKFY -P08NBMU-E Parts name Check points Disconnect the connector then measure the resistance with a tester . (At the ambient temperature 50°F~86°F) Disconnect the connector then measure the resistance value with a tester .
15 15 7-1-2. Liner expansion valve 7-1-1. Thermistor 4 Φ 4 3 6 5 Φ 3 2 Φ 2 1 Φ 1 Φ 4 Φ 3 Φ 2 Φ 1 Controller board Drive circuit Connector(CN60) DC12V Brown Red Blue Orange Y ellow White M 4 6 .
16 6 5 4 3 2 1 LED 1k Ω Symptom Check points Operation circuit failure of the micro processor Disconnect the connector on the controller board, then con- nect LED for checking.
17 7-2. Function of Dip switch PKFY -P06NBMU-E PKFY -P08NBMU-E 1 2 3 4 5 6 7 8 9 10 1~6 1 2 3 4 5 6 7 8 Thermistor<Room temperature> position ON OFF Filter clogging detection Provide Not prov id.
18 J41, J42 Wireless remote controller P air No. Jum pe r <Initial setting> P atter n A Setting pattern J41 J42 Indoor controller jumper wire P air No. of wireless remote controller Initial setting A B D C — Cut Cut — — — Cut Cut 0 1 3 2 — — — P air No.
19 7-3. TEST POINT DIAGRAM 7-3-1. Indoor controller board PKFY -P06NBMU-E PKFY -P08NBMU-E CN3A Connected to the MA-Remote controller Between 1 to 3 8.7-13V DC (Pin 1 (+)) CN29 Pipe temperature thermistor/Gas (TH23) CN21 Pipe temperature thermistor/Liquid (TH22) CN90 Connected to the wireless remote controller board (W .
20 12 3 4 56 78 9 10 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 7-3-3. Address board PKFY -P06NBMU-E PKFY -P08NBMU-E SW1 Function setting SW12 Address setting 10ths DIGIT SW1 1 Address setting 1s DIGIT SW14 Branch No.
1. REMOVING THE LOWER SIDE OF THE INDOOR UNIT FROM THE INST ALLA TION PLA TE When there is removing plate (1) Remove the corner box at right lower side of the indoor unit and remove the removing plate from the corner box. (Figure 3) (2) Insert the removing plate at the back side of the corner box to remove the indoor unit.
PHOTOS OPERA TION PROCEDURE 22 3. REMOVING THE INDOOR CONTROLLER BOARD AND INDOOR POWER BOARD (1) Remove the front panel. (Refer to 2) (2) Remove the electrical box cover (screw 4 × 10). (Refer to the Photo 2) INDOOR CONTROLLER BOARD (1) Disconnect the following connectors on the indoor controller board.
PHOTOS OPERA TION PROCEDURE 23 5. REMOVING THE NOZZLE ASSEMBL Y AND DRAIN HOSE (1) Remove the front panel (Refer to 2). (2) Remove the electrical box cover . (3) Disconnect the connector (CN5V) on the indoor controller board. (4) After unhook the right side of the corner box, press the upper left side and remove the corner box.
TM Copyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., L TD. Distributed in Apr . 2009 No. OCH461 PDF 7 Made in Japan New publication, effective Apr . 2009 Specifications subject to change without notice HEAD OFFICE : TOKYO BLDG.
Een belangrijk punt na aankoop van elk apparaat Mitsubishi Electronics OCH461 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Mitsubishi Electronics OCH461 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Mitsubishi Electronics OCH461 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Mitsubishi Electronics OCH461 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Mitsubishi Electronics OCH461 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Mitsubishi Electronics OCH461 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Mitsubishi Electronics OCH461 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Mitsubishi Electronics OCH461 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.