PUGH OUTDOOR UNIT MODELS PUGH18AYB PUGH24AYB PUGH30AYB PUGH36AYB PUGH42AYB
APPLIES TO: VOLTAGE PHASE SUFFIX
208/230 VAC 1 PH AYB


DESCRIPTION AND FEATURES 2
OPERATING RANGE 26
SPECIFICATIONS 3
REFRIGERANT CHARGE (R-22 0z.) ADJUSTMENT FOR OPTIMUM PERFORMANCE 27
STANDARD OPERATING DATA 4 - 6
CAPACITY CORRECTION FACTORS FOR VARIOUS PIPE LENGTHS 28
MICROPROCESSOR CONTROL 29 - 30
PERFORMANCE DATA - OPERATING PRESSURES - HEATING 20 - 22
ELECTRICAL 31
DIMENSIONS AND CLEARANCES 23
REFRIGERANT SYSTEM 32
SYSTEM CHARGE 24
PARTS BREAKDOWN 33 - 35
The PUGH condensing units are Heat Pump models that are designed specifically for use with Mitsubishi Electronics PKH, PCH, and PLH MR. SLIM indoor units of matching nominal capacities. Models from 1.5 through 3.5 tons are available.

* Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.
* Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.
* Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.










63 31,457 11.32 2,779 17,356 20,748 25,642 30,536 33,928 60 205
65 32,246 11.42 2,824 15,545 18,937 23,539 28,140 31,532 61 206
67 33,034 11.52 2,869 13,734 17,126 21,435 25,744 29,136 62 207
69 33,823 11.61 2,913 11,923 15,315 19,332 23,348 26,740 63 208
71 34,611 11.71 2,956 10,112 13,504 17,228 20,952 24,344 64 209
63 30,526 10.25 2,979 17,025 20,417 24,740 29,063 32,455 65 237
65 31,429 10.44 3,010 15,316 18,708 23,057 27,056 30,448 67 241
67 31,317 10.66 2,937 13,607 16,999 21,374 25,049 28,441 70 245
69 32,728 10.73 3,049 11,897 15,289 19,340 23,042 26,434 72 245
71 34,139 10.81 3,159 10,188 13,580 17,307 21,035 24,427 74 245
63 29,594 9.31 3,179 16,694 20,086 23,838 27,590 30,982 69 268
65 30,612 9.58 3,195 15,087 18,479 22,575 25,972 29,364 74 275
67 29,600 9.85 3,005 13,479 16,871 21,312 24,354 27,746 79 282
69 31,633 9.93 3,186 11,872 15,264 19,349 22,735 26,127 81 282
71 33,666 10.01 3,363 10,264 13,656 17,387 21,117 24,509 83 281
63 27,069 8.16 3,318 15,720 19,112 22,737 26,362 29,754 72 302
65 28,339 8.41 3,372 14,141 17,533 21,390 24,898 28,290 76 307
67 28,595 8.62 3,319 12,563 15,955 20,044 23,433 26,825 79 312
69 30,373 8.81 3,449 10,984 14,376 18,347 21,969 25,361 81 313
71 32,151 8.99 3,575 9,406 12,798 16,651 20,505 23,897 84 314
63 24,543 7.10 3,457 14,745 18,137 21,636 25,134 28,526 75 336
65 26,066 7.35 3,548 13,196 16,588 20,206 23,824 27,216 77 339
67 27,590 7.60 3,633 11,646 15,038 18,776 22,513 25,905 80 342
69 29,113 7.84 3,712 10,097 13,489 17,346 21,203 24,595 82 344
71 30,636 8.09 3,787 8,547 11,939 15,916 19,892 23,284 84 347

63 31,375 10.90 2,878 25,577 28,969 25,106 21,243 24,635 68 215
65 31,927 11.03 2,895 21,650 25,042 23,179 21,316 24,708 69 216
67 32,479 11.16 2,912 17,722 21,114 21,251 21,389 24,781 70 218
69 33,031 11.28 2,928 13,795 17,187 19,324 21,461 24,853 70 219
71 33,583 11.41 2,943 9,867 13,259 17,397 21,534 24,926 71 220
63 29,459 9.78 3,013 20,869 24,261 26,781 29,301 32,693 71 244
65 30,374 10.13 2,997 18,093 21,485 24,031 27,325 30,717 71 242
67 31,040 10.49 2,958 15,316 18,708 21,282 25,350 28,742 72 241
69 32,079 10.48 3,060 12,540 15,932 19,279 23,374 26,766 74 247
71 33,119 10.47 3,164 9,763 13,155 17,277 21,399 24,791 77 253
63 27,543 8.75 3,148 16,161 19,553 28,456 37,358 40,750 73 272
65 28,821 9.30 3,099 14,536 17,928 24,884 33,335 36,727 73 269
67 29,600 9.85 3,005 12,910 16,302 21,312 29,311 32,703 74 265
69 31,128 9.75 3,193 11,285 14,677 19,235 25,288 28,680 78 275
71 32,655 9.65 3,384 9,659 13,051 17,158 21,264 24,656 82 285
63 25,204 7.69 3,278 15,258 18,650 23,642 28,634 32,026 76 306
65 26,584 8.05 3,300 13,654 17,046 21,720 27,141 30,533 78 306
67 27,715 8.40 3,297 12,050 15,442 19,799 25,649 29,041 79 307
69 29,220 8.51 3,432 10,447 13,839 18,624 24,157 27,549 83 314
71 30,725 8.61 3,567 8,843 12,235 17,450 22,665 26,057 86 321
63 22,865 6.71 3,408 14,354 17,746 18,828 19,909 23,301 79 339
65 24,347 6.95 3,502 12,772 16,164 18,556 20,948 24,340 82 344
67 25,830 7.20 3,590 11,191 14,583 18,285 21,988 25,380 85 348
69 27,312 7.44 3,672 9,609 13,001 18,014 23,027 26,419 87 353
71 28,794 7.68 3,749 8,027 11,419 17,743 24,066 27,458 90 357

63 21,933 12.75 1,720 11,655 15,318 18,074 20,831 24,493 76 219
65 22,107 12.89 1,716 10,139 13,801 16,672 19,542 23,205 78 220
67 22,280 13.02 1,711 8,622 12,284 15,269 18,254 21,916 79 221
69 22,454 13.16 1,707 7,105 10,768 13,866 16,965 20,628 80 222
71 22,627 13.29 1,703 5,588 9,251 12,464 15,677 19,339 81 223
63 20,479 11.28 1,816 11,070 14,732 17,294 19,856 23,518 79 240
65 20,945 11.32 1,849 9,620 13,283 16,185 18,783 22,446 81 245
67 20,740 11.42 1,816 8,171 11,833 15,076 17,710 21,373 83 251
69 21,541 11.73 1,836 6,721 10,384 13,663 16,638 20,300 85 253
71 22,343 12.05 1,854 5,272 8,934 12,250 15,565 19,228 87 256
63 19,025 9.95 1,912 10,484 14,147 16,514 18,880 22,543 82 260
65 19,784 9.98 1,983 9,102 12,764 15,698 18,024 21,686 84 271
67 19,200 10.00 1,920 7,720 11,382 14,883 17,167 20,830 87 281
69 20,629 10.50 1,965 6,337 10,000 13,459 16,310 19,973 90 285
71 22,059 11.00 2,005 4,955 8,618 12,036 15,453 19,116 93 288
63 17,316 8.46 2,047 9,594 13,256 14,962 16,668 20,331 85 299
65 17,907 8.62 2,076 8,297 11,960 14,233 16,202 19,865 87 306
67 17,826 8.75 2,038 7,001 10,664 13,504 15,736 19,398 90 313
69 18,751 9.13 2,054 5,705 9,367 12,471 15,269 18,932 93 317
71 19,677 9.51 2,069 4,408 8,071 11,437 14,803 18,466 95 321
63 15,608 7.15 2,183 8,703 12,366 13,411 14,456 18,119 87 338
65 16,030 7.39 2,169 7,493 11,156 12,768 14,381 18,043 90 342
67 16,451 7.63 2,156 6,282 9,945 12,125 14,305 17,967 93 346
69 16,873 7.87 2,144 5,072 8,735 11,482 14,229 17,892 95 349
71 17,295 8.11 2,133 3,861 7,524 10,839 14,153 17,816 98 353

63 25,376 10.56 2,402 15,758 19,875 23,553 27,230 31,347 67 217
65 26,820 10.95 2,449 14,279 18,395 22,105 25,814 29,930 70 223
67 28,264 11.34 2,493 12,799 16,916 20,656 24,397 28,514 73 229
69 29,709 11.72 2,534 11,319 15,436 19,208 22,981 27,098 76 235
71 31,153 12.11 2,572 9,839 13,956 17,760 21,565 25,681 79 241
63 18,361 9.73 1,886 14,835 18,952 22,428 25,904 30,021 69 243
65 21,015 9.96 2,110 13,370 17,487 21,206 24,603 28,720 72 249
67 26,332 10.06 2,617 11,905 16,022 19,984 23,301 27,418 75 256
69 27,655 10.37 2,668 10,440 14,557 18,440 22,000 26,117 79 262
71 28,979 10.67 2,716 8,975 13,091 16,895 20,699 24,815 82 269
63 11,346 8.28 1,370 13,912 18,029 21,304 24,578 28,695 72 269
65 15,211 8.59 1,771 12,462 16,579 20,308 23,392 27,509 75 275
67 24,400 8.90 2,742 11,011 15,128 19,312 22,205 26,322 78 282
69 25,602 9.14 2,802 9,560 13,677 17,671 21,019 25,136 81 289
71 26,805 9.37 2,859 8,110 12,227 16,030 19,833 23,949 84 296
63 14,732 6.93 2,126 13,032 17,149 20,220 23,290 27,407 74 300
65 17,236 7.29 2,366 11,585 15,701 19,110 22,197 26,313 77 306
67 22,403 7.76 2,888 10,137 14,254 18,001 21,103 25,220 80 313
69 23,576 7.98 2,953 8,689 12,806 16,569 20,010 24,127 83 319
71 24,749 8.21 3,015 7,241 11,358 15,138 18,917 23,034 86 326
63 18,118 6.29 2,881 12,153 16,269 19,135 22,002 26,118 77 331
65 19,261 6.51 2,961 10,708 14,824 17,913 21,001 25,118 80 337
67 20,405 6.72 3,035 9,263 13,380 16,690 20,001 24,118 83 343
69 21,549 6.94 3,105 7,818 11,935 15,468 19,001 23,118 86 350
71 22,693 7.16 3,170 6,373 10,490 14,246 18,001 22,118 89 356

63 29,544 10.17 2,905 17,275 20,651 25,522 30,393 33,769 57 203
65 30,285 10.26 2,952 15,472 18,848 23,428 28,008 31,384 58 204
67 31,025 10.35 2,999 13,670 17,046 21,334 25,623 28,999 59 205
69 31,766 10.43 3,045 11,867 15,243 19,241 23,238 26,615 60 206
71 32,506 10.52 3,090 10,065 13,441 17,147 20,854 24,230 61 207
63 28,669 9.21 3,114 16,945 20,321 24,624 28,927 32,303 62 234
65 29,518 9.38 3,146 15,244 18,620 22,949 26,929 30,305 65 238
67 29,413 9.58 3,070 13,543 16,919 21,273 24,931 28,307 67 242
69 30,738 9.64 3,187 11,841 15,218 19,250 22,934 26,310 69 242
71 32,063 9.71 3,303 10,140 13,516 17,226 20,936 24,312 70 242
63 27,794 8.36 3,323 16,616 19,992 23,726 27,461 30,837 66 265
65 28,750 8.61 3,340 15,016 18,392 22,469 25,850 29,226 71 272
67 27,800 8.85 3,141 13,416 16,792 21,212 24,239 27,615 76 279
69 29,709 8.92 3,330 11,816 15,192 19,258 22,629 26,005 77 279
71 31,619 8.99 3,516 10,216 13,592 17,305 21,018 24,394 79 278
63 25,422 7.33 3,468 15,646 19,022 22,630 26,238 29,614 69 299
65 26,616 7.55 3,524 14,075 17,451 21,290 24,781 28,157 72 304
67 26,856 7.74 3,469 12,504 15,880 19,950 23,323 26,699 76 308
69 28,526 7.91 3,605 10,932 14,309 18,261 21,866 25,242 78 310
71 30,196 8.08 3,737 9,361 12,737 16,573 20,408 23,784 80 311
63 23,051 6.38 3,613 14,676 18,052 21,534 25,016 28,392 72 332
65 24,481 6.60 3,708 13,134 16,510 20,111 23,712 27,088 74 335
67 25,912 6.82 3,797 11,591 14,967 18,687 22,407 25,783 76 338
69 27,342 7.05 3,880 10,049 13,425 17,264 21,103 24,479 78 341
71 28,773 7.27 3,958 8,507 11,883 15,841 19,799 23,175 80 343

63 36,251 10.90 3,326 27,910 31,611 27,396 23,181 26,882 72 219
65 36,889 11.03 3,345 23,624 27,326 25,293 23,260 26,961 73 220
67 37,526 11.16 3,364 19,339 23,040 23,190 23,339 27,041 74 221
69 38,164 11.28 3,383 15,053 18,754 21,087 23,419 27,120 75 223
71 38,802 11.41 3,401 10,767 14,468 18,983 23,498 27,200 75 224
63 34,037 9.78 3,481 22,773 26,474 29,224 31,973 35,675 75 248
65 35,094 10.13 3,463 19,743 23,444 26,223 29,818 33,519 75 247
67 35,863 10.49 3,418 16,713 20,414 23,223 27,662 31,363 76 246
69 37,065 10.48 3,536 13,683 17,385 21,038 25,506 29,208 79 251
71 38,266 10.47 3,655 10,654 14,355 18,853 23,351 27,052 81 257
63 31,823 8.75 3,637 17,635 21,337 31,051 40,766 44,467 77 277
65 33,300 9.30 3,581 15,861 19,563 27,154 36,375 40,077 78 273
67 34,200 9.85 3,472 14,088 17,789 23,256 31,985 35,686 78 270
69 35,965 9.75 3,689 12,314 16,015 20,989 27,594 31,296 83 280
71 37,730 9.65 3,910 10,540 14,241 18,723 23,204 26,905 87 290
63 29,121 7.69 3,787 16,649 20,351 25,798 31,245 34,947 81 311
65 30,715 8.05 3,813 14,899 18,601 23,701 29,617 33,319 82 311
67 32,022 8.40 3,810 13,149 16,851 21,604 27,989 31,690 84 312
69 33,761 8.51 3,966 11,400 15,101 20,323 26,361 30,062 88 319
71 35,499 8.61 4,121 9,650 13,351 19,042 24,732 28,434 91 327
63 26,418 6.71 3,937 15,663 19,365 20,545 21,725 25,426 84 345
65 28,131 6.95 4,046 13,937 17,639 20,249 22,859 26,560 87 349
67 29,844 7.20 4,148 12,211 15,913 19,953 23,993 27,695 90 354
69 31,556 7.44 4,243 10,485 14,187 19,657 25,127 28,829 93 359
71 33,269 7.68 4,332 8,759 12,461 19,361 26,261 29,963 95 363

63 36,029 10.71 3,366 21,312 24,489 28,042 31,595 34,772 55 212
65 36,967 10.91 3,388 18,969 22,146 26,088 30,031 33,208 57 213
67 37,906 11.12 3,409 16,626 19,802 24,135 28,467 31,644 58 214
69 38,845 11.33 3,430 14,283 17,459 22,181 26,903 30,080 59 214
71 39,784 11.53 3,450 11,940 15,116 20,228 25,339 28,516 60 215
63 35,618 9.56 3,727 21,357 24,533 28,130 31,727 34,904 59 244
65 36,810 10.00 3,679 18,855 22,294 26,736 32,109 35,548 61 245
67 38,953 10.43 3,735 16,354 20,056 25,342 32,491 36,192 62 246
69 39,670 10.49 3,781 14,133 17,572 22,917 29,194 32,633 64 248
71 40,386 10.56 3,826 11,912 15,089 20,492 25,896 29,073 66 249
63 35,208 8.61 4,089 21,401 24,578 28,218 31,859 35,036 63 275
65 36,653 9.23 3,971 19,022 22,199 27,384 30,508 33,684 65 277
67 40,000 9.85 4,061 16,083 20,309 26,550 36,515 40,741 67 279
69 40,494 9.80 4,131 14,263 17,440 23,654 27,805 30,982 70 281
71 40,989 9.75 4,202 11,884 15,061 20,757 26,454 29,630 72 283
63 32,918 7.30 4,511 20,501 23,678 27,170 30,662 33,839 66 310
65 34,465 7.70 4,478 18,307 21,484 25,982 29,448 32,625 68 313
67 36,963 8.13 4,547 15,833 19,535 24,793 31,914 35,615 70 315
69 38,034 8.26 4,604 13,919 17,096 22,574 27,020 30,197 73 317
71 39,106 8.39 4,660 11,726 14,902 20,354 25,806 28,983 75 320
63 30,628 6.21 4,934 19,601 22,778 26,122 29,465 32,642 68 346
65 32,277 6.47 4,985 17,593 20,769 24,579 28,389 31,565 71 349
67 33,925 6.74 5,033 15,584 18,761 23,036 27,312 30,489 73 351
69 35,574 7.01 5,076 13,575 16,752 21,494 26,236 29,412 76 354
71 37,223 7.27 5,117 11,567 14,743 19,951 25,159 28,336 79 357









PUGH18AYB 19" (483 mm) 35" (889 mm) 23" (584 mm)
PUGH24AYB 25" (635 mm) 35" (889 mm) 23" (584 mm)
PUGH30AYB 25" (635 mm) 35" (889 mm) 23" (584 mm)
PUGH36AYB 27" (686 mm) 37" (940 mm) 27" (686 mm)
PUGH42AYB 33" (838 mm) 37" (940 mm) 27" (686 mm)

MINIMUM 24” SERVICE ACCESS CLEARANCE ON ONE SIDE 60” OVERHEAD CLEARANCE
CONTROL ACCESS PANEL NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF.

SYSTEM CHARGE
The factory charge in the outdoor unit includes enough charge for the unit and the smallest matched evaporator and 25 feet of line. Some evaporator matches may require some additional charge. See Tabular Data sheet provided in unit lit- erature packet.
If a calibrated charging cylinder or accurate weighing device is available, add refrigerant accordingly.
The “TOTAL SYSTEM CHARGE” must be permanently stamped on the unit data plate.
Compressor damage will occur if system is improperly charged. On new system installations charge system per R-22 charge information label and follow guidelines in this instruction.
Total system charge is determined as follows:
Check flare caps on service ports to be sure they are leak tight. DO NOT OVER TIGHTEN (between 40 and 60 inch - lbs. maximum).
Use one of the following charging methods whenever addi- tional refrigerant is required for the system charge.
Refrigerant charging should only be carried out by a qualified air conditioning contractor.
INDOOR WB
°F 1
55 60 65 70 75 80 85 90 95 100 105 110 115
52 12 10 6
54 14 12 10 7
56 17 15 14 10 6
58 20 18 16 13 9 5
60 23 21 19 16 12 8 6
62 26 24 22 19 16 12 8 5
64 29 27 24 21 18 15 11 9 6
66 32 31 30 24 23 18 15 11 9 6
68 35 33 30 27 24 21 19 16 14 12 9 6
70 35 33 30 28 25 22 20 18 15 13 11 8
72 35 33 30 28 26 24 20 20 17 15 14
74 34 31 30 27 25 23 22 20 18
76 35 33 31 29 27 26 25 23

SUCTION SERVICE VALVE SUPERHEAT
01 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34
61.5 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69
64.2 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71
67.1 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73
70.0 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75
73.0 43 45 47 49 51 53 55 57 59 61 63 63 67 69 71 73 75 77
76.0 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79
79.2 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81
82.4 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83
PSIG (Service Port)

1 Phase 60 Hz 208/230 V
(Rated in accordance with ARI Standard 110)
INDOOR OUTDOOR
FUNCTION AIR INTAKE CONDITION
DB (°F) WB (°F) DB (°F) WB (°F)
80 67 95 75
Standard temperature Maximum temperature Minimum temperature
95 71 115 -
67 57 551
80 75 80 75
70 60 47 43
Heating Standard temperature Maximum temperature Minimum temperature
70 60 17 15
80 67 75 65
Cooling · Maximum humidity

PUGH18,24 3/8 5/8 0.14
PUGH30, 36 1/2 3/4 0.33
PUGH42 1/2 7/8 0.35
FACTORY CHARGE /
ARI RATING POINT ADD CHARGE
MODEL
25 FT 40 FT 55 FT 70 FT
R-22 CHARGE, OZ
PUGH18AYB 56.0 4 8 12
PUGH24AYB 91.0 4 8 13
PUGH30AYB 79.0 4 9 13
PUGH36AYB 85.0 8 15 23
PUGH42AYB 125.0 8 16 23

MODEL
25 ft 40 ft 55 ft 70 ft
PUGH24AYB 1.0 0.992 0.984 0.975
PUGH30AYB 1.0 0.996 0.990 0.985
PUGH36AYB 1.0 0.984 0.967 0.950
PUGH42AYB 1.0 0.991 0.982 0.973

A. The indoor unit constantly monitors the difference between return air temperature and indoor coil temperature. During a call for cooling, if the indoor coil does not become at least nine degrees colder than the return air temperature after approximately ten minutes of operation, the indoor circuit board will shut down the system. The indoor unit will display the problem code “P8” at the indoor unit remote controller and terminate the 12VDC signal to the outdoor unit. B. The “P8” code does not necessarily mean that the outdoor unit has a problem. It simply means that the indoor coil did not become colder or warmer than the return air during a call for cooling or heating. C. If a “P8” code is displayed: i. Turn the indoor remote controller off and back on to reset it. ii. Set the remote controller to a “call” for cooling. iii. At the indoor unit 12VDC control terminals, check to see if 12VDC is present on the #1 and #2 wires.
unit is not the source of the problem and the following should be checked: 1. Check the 12VDC terminals at the outdoor unit for 12VDC. The polarity must be the same as that of the indoor. That is, the control wires must be connected to matching numbered control terminations on the indoor and out- door units (1 to 1, 2 to 2). If the wires are not connected properly, the unit will not be damaged, but it will not oper- ate. a. If no 12VDC signal is present when 12VDC is available at the indoor unit, check for a break/open in the control
wire. b. If 12VDC is present, insure polarity is correct. If polarity is correct and a 12VDC signal is present, check the
LED indicators on the outdoor board. i. Is the “Status” LED lit constantly? If so, the outdoor board is in time delay. Wait for it to expire (make sure the
12VDC signal is still available from the indoor unit). ii. Is the “#2” LED lit? This indicates that the board is receiving 12VDC from the indoor unit.
NO LED: Recheck for 12VDC on the control wires, check for correct polarity and check the wires from the terminal block to the board. LED LIT: The board should be outputting 24 VAC to the compressor contactor and line voltage to the fan (unless in low ambient control). Is the compressor/fan operating? YES: System is OK NO: Is the “Status LED” flashing? NO: Bad outdoor board YES: 2 Flash sequence indicates that the High Pressure Switch is open. 4 Flash sequence indicates that the Low Pressure Safety Switch is open 3. OUTDOOR BOARD FUNCTIONALITY A. High Pressure Safety Switch (HPSS). This switch opens at approximately 400 PSIG and closes at approximately 300 PSIG. There is no bypass on this switch. When the switch opens, the control immediately stops the compressor and outdoor fan. When the switch closes, the system can restart if the indoor unit has not entered a P8 fault code. If the switch opens three times within a one-hour period, the outdoor unit operation is “locked out” and must be serviced. Turning line voltage off and back on to the outdoor unit will reset the lockout. The indoor unit must also be reset to clear the fault code. Turning the remote controller off and back on will reset the indoor unit. B. Low Pressure Safety Switch (LPS). This switch opens at approximately 7 PSI and closes at approximately 22 PSI. The switch is bypassed during the first 3 minutes of cooling operation. If the pressure rises to the “cut in” point, the compressor will restart if the delay has expired and the indoor unit is not in a P8 fault. If the switch opens 3 times within a one-hour period, the outdoor unit will be “locked out” and must be serviced. Turning line voltage off and back on to the outdoor unit will reset the lockout.

C. Low Ambient Temperature Switch (LATS) - The purpose of this switch is to extend cooling operation in low outdoor temperatures as low as 25°. The outdoor unit uses a high side pressure switch to cycle the fan. When pressure drops to 165 PSI (+/-10), the switch opens and the fan stops. When pressure rises to 300 (+/- 10), the switch closes and the fan restarts. A jumper is factory installed in place of the low ambient pressure switch. This jumper must be removed when a low ambient accessory kit is installed. During low ambient cooling operation the indoor unit may initiate an “air defrost” of the indoor coil once during every 16 minutes of continuous cooling operation. This insures that the coil has adequate airflow and should not be considered as a fault. D. Defrost Sensor Switch - The defrost switch is set to close at 35 degrees (+/-7) and opens at 65 degrees (+/-5). The board is factory set with a 60 minute minimum defrost interval and can be reset to 30 or 90 minutes by moving a jumper. When the defrost sensor closes, the defrost timer begins timing out the compressor run time. Once the timer “times out” (30/60/90 minutes) and the switch is closed the reversing valve is shifted and defrost is accomplished. If the room temperature is satisfied during a defrost cycl, the defrosting will continue until the termination temperature is achieved or 10 minutes has elapsed. E. Crankcase Heater (CCH) - A crankcase heater is installed into all PUGH heat pump units to protect the compressor. When line voltage is first applied to the outdoor unit, the control will energize the crankcase heater. The control will continue to energize the CCH until the first call for compressor operation. The control never energizes the CCH during compressor operation. The control will energize the CCH thirty minutes after the compressor turns off. It will then cycle the CCH on for 30 minutes and off for 30 minutes repeatedly until the compressor is again turned on. F. Compressor Contactor (CC) - The compressor contactor is energized with 24VAC when a 12 VDC is input to the out- door unit on control wires 1 and 2 from the indoor unit. This 12 VDC signal is generated and sent from the indoor unit on all calls for compressor operation. G. Outdoor Fan Motor (ODF) - The outdoor fan motor typically operates at the same time as the compressor. However, the fan may be off while the compressor is operating during low ambient cooling conditions as described previously. H. Transformer Input (24VAC) - The secondary side of the transformer supplies 24 volts AC to the circuit board on the “24VAC” terminals. This voltage operates the internal circuits of the board and also provides voltage to the compressor contactor when appropriate. The primary side of the transformer is powered with line voltage from terminals marked “L1” and “L2” on the board. I. Line Voltage - Line voltage is input and output from the circuit board on the terminals marked “L1” and “L2”. There are four terminals marked “L1”. These terminals provide “L1” input to the board and “L1” output to the transformer, crank- case heater and the outdoor fan motor. There are two terminals marked “L2”. One terminal provides “L2” line voltage input to the board. The other provides “L2” output to the transformer. J. Anti-Recycle Delay Timer - The control provides an “anti-recycle delay” of three minutes in the cooling mode. K. Time Shortening - Placing the defrost jumper to the “TEST” position shortens timings of the control to the following values. 1. Anti-Recycle - 36 seconds 2. CCH Cycles - 24 seconds 3. Compressor Run - 1 second 4. Low Pressure Bypass - 12 seconds L. Last Fault Memory Recall. The control maintains a memory of the last fault that occurred. The last fault code can be recalled by moving the defrost jumper to the “TEST” position and observing the “STATUS” LED display. The control stores only the last fault code. The control will reset the fault code memory when the line voltage to the outdoor unit is turned off. M. LED Function. The board has four LED’s which provide the following function: 1. “STATUS” LED indicates normal operation or faults as follows:
LED FLASHES INDICATION OF CONDITION Off Normal Operation, no fault, no “call”
Constant on LED Anti-recycle delay active. If the HPSS or LPS opens, the anti-recycle
will activate for 3 minutes before the fault can be displayed. 1 Flash Sequence Defrost Sensor Closed 2 Flash Sequence High Pressure Safety Switch Open 3 Flash Sequence LATS Open 4 Flash Sequence Low Pressure Safety Switch Open



There are two service ports available to service technicians. One port is located at each of the two base valves.
A. Liquid Line Base Valve Service Port. This port is used to evacuate the refrigerant line set when the ball valve is in the closed position. It may also be used to measure the liquid line pressure or, more accurately, the “saturated line” pressure during normal operation.
B. Suction Base Valve Service Port. This port is also used to evacuate the indoor unit and line set during installation. The ball valve must be closed to evacuate the line set and indoor unit. During normal cooling mode operation this pres- sure port indicates evaporator pressure (minus line set pressure drop). Typical cooling mode pressure readings here are in the range of 55 to 80 PSI during summer operation.
C. Both refrigerant lines must be insulated because the “cooling side” metering device is located in the outdoor unit. Failure to insulate the liquid line, or more accurately the “saturation line”, will result in condensate dripping from the line and poor cooling performance.
D. Metering Devices. A fixed orifice that is located in the liquid base valve meters refrigerant in the cooling mode. If a restriction or a compressor failure occurs this orifice can be easily accessed and cleaned after refrigerant is recovered. It is important to use a back-up wrench on the liquid line base valve connections when accessing the orifice. Failure to do so could loosen the base valve connections and cause a refrigerant leak.

CHARGE COMPENSATOR (Empty in cooling / full in heating)


FIG ITEM DESCRIPTION PUGH018AYB PUGH024AYB PUGH030AYB <
1 1 Compressor, Hermetic 015-02901-004 015-03588-000 015-03424-001 1 2 Accumulator 026-35441-000 026-35441-000 026-35435-000 1 3 Compensator Tank 026-35433-000 026-35433-000 026-35433-000 1 4 Valve, Reversing 025-31931-000 025-31931-000 025-31931-000 1 5 Coil, Solenoid 1456-9761 1456-9761 1456-9761 1 6 Guard, Coil 373-20091-008 373-20091-009 373-20091-009
1 7 Control, Low Pressure (7 psi- open / 22 psi close) 025-38610-000 025-38610-000 025-38610-000
1 8 Filter Drier 1458-0011 1458-0011 1458-0011
1 9 Control, High Pressure (400 psi- open / 300 psi close) 025-33305-048 025-33305-048 025-33305-048
1 10 Distributor 022-09058-000 022-09059-000 022-09010-448 1 11 Sensor, Coil (Liquid Replacement) 025-31994-000 025-31994-000 025-31994-000
1 12 Valve, Liquid (3/8” FL x 3/8” SW) Valve, Liquid (1/2” FL x 3/8” SW)
1 13 Valve, Suction (5/8” FL x 3/4” SW) Valve, Suction (3/4” FL x 3/4” SW)
--- 022-09049-750 1 14 Crankcase Heater 1450-9511 --- --- 1 15 Isolator, Compressor (Pkg. of 4) 9435-1081 9435-1081 9435-1081 1 16 Fastener, Push-in (4 Req’d) 021-18381-000 021-18381-000 021-18381-000 1 17 Base, Pan 2218-1011 2218-1011 2218-1011 1 18 Mesh, Coil Guard Plastic 028-14726-000 028-14727-000 028-14727-000 1 19 Coil, Condenser 373-19800-011 373-19800-013 373-19800-013 1 20 Hubcap 026-39292-000 026-39292-000 026-39292-000 1 21 Motor Mount Kit (Acorn Nuts) 363-90117-700 363-90117-700 363-90117-700 1 22 Guard, Fan 026-35511-018 026-35511-018 026-35511-018 1 23 Motor, Fan 024-26067-010 024-26067-010 024-26020-000 1 24 Wireway, (Electric Channel) 028-13215-000 028-13215-000 028-13215-000 1 25 Blade, Fan (18”) 026-34091-000 026-34092-000 026-34092-000 1 26 Panel, Top 2218-1021/A 2218-1021/A 2218-1021/A 1 27 Plate, Block-Off 2236-1081/B 2242-1081/B 2242-1081/B 1 28 Cover, Electric Box 2218-1151/A 2218-1151/A 2218-1151/A 1 29 Diagram, Wiring 035-18739-001 035-18739-001 035-18739-001 1 30 Block, Terminal 025-38589-003 025-38589-003 025-38589-003 1 31 Electrical Plug 025-33306-006 025-33306-006 025-33306-006 1 32 Ground Lug 025-21798-000 025-21798-000 025-21798-000
1 33 Capacitor, Run (30/5MFD) [RC] Capacitor, Run (35/5MFD) [RC] Capacitor, Run (45/5MFD) [RC]
--- --- 024-25895-000 1 34 Relay 024-24116-000 024-24116-000 024-24116-000 1 35 Transformer (40VA) 025-18452-000 025-18452-000 025-18452-000 1 36 Contactor, Electrical (30 amp) [M] 024-27531-000 024-27531-000 024-27531-000 1 37 Control, Defrost 031-01976-000 031-01976-000 031-01976-000 * 38 Harness, Compressor 025-31884-000 025-31884-000 025-31884-000 * 39 Nameplate, Bezel 035-13508-000 035-13508-000 035-13508-000 * 40 Harness, Wiring (3 Wire)t 373-20055-006 373-20055-006 373-20055-006 * 41 Harness, Wiring (8 Wire) 373-20055-007 373-20055-007 373-20055-007
New replacement parts shown in bold face type at the first printing of parts list dated 4/ 03. Major components and suggested stocking items are shown with shaded item number. “

FIG ITEM DESCRIPTION PUGH036AYB PUGH042AYB <
1 1 Compressor, Hermetic 015-03425-001 015-02773-004 1 2 Accumulator 026-35435-000 026-35435-000 1 3 Compensator Tank 026-35433-000 026-35434-000 1 4 Valve, Reversing 025-31922-000 025-31929-000 1 5 Coil, Solenoid 1456-9761 1456-9761 1 6 Guard, Coil 373-20091-010 373-20091-010
1 7 Control, Low Pressure (7 psi- open / 22 psi close) 025-38610-000 025-38610-000
1 8 Filter Drier 6536-3341 6536-3341
1 9 Control, High Pressure (400 psi- open / 300 psi close) 025-33305-048 025-33305-048
1 10 Distributor 022-09060-000 022-09059-000 1 11 Sensor, Coil (Liquid Replacement) 025-31994-000 025-31994-000 1 12 Valve, Liquid (1/2” FL x 3/8” SW) 022-09063-000 022-09057-000
1 13 Valve, Suction (3/4” FL x 3/4” SW) Valve, Suction (7/8” FL x 3/4” SW)
--- 022-09052-875 1 14 Crankcase Heater --- 025-38695-000 1 15 Isolator, Compressor (Pkg. of 4) 9435-1081 9435-1081 1 16 Fastener, Push-in (4 Req’d) 021-18381-000 021-18381-000 1 17 Base, Pan 2260-1011 2260-1011 1 18 Mesh, Coil Guard Plastic 028-14728-000 028-14731-000 1 19 Coil, Condenser 373-20075-205 373-20075-204 1 20 Hubcap 026-39292-000 026-39292-000 1 21 Motor Mount Kit (Acorn Nuts) 363-90117-700 363-90117-700 1 22 Guard, Fan 026-35511-022 026-35511-022 1 23 Motor, Fan 024-27596-000 024-27596-000 1 24 Wireway, (Electric Channel) 028-13216-000 028-13216-000 1 25 Blade, Fan (18”) 026-34593-000 026-34593-000 1 26 Panel, Top 2260-1021/A 2260-1021/A 1 27 Plate, Block-Off 2260-1081/B 2260-1081/B 1 28 Cover, Electric Box 2218-1151/A 2218-1151/A 1 29 Diagram, Wiring 035-18739-001 035-18739-001 1 30 Block, Terminal 025-38589-003 025-38589-003 1 31 Electrical Plug 025-33306-006 025-33306-006 1 32 Ground Lug 025-21798-000 025-21798-000
1 33 Capacitor, Run (45/5MFD) [RC] Capacitor, Run (60/5MFD) [RC]
--- 024-25033-000 1 34 Relay 024-24116-000 024-24116-000 1 35 Transformer (40VA) 025-18452-000 025-18452-000 1 36 Contactor, Electrical (30 amp) [M] 024-27531-000 024-27531-000 1 37 Control, Defrost 031-01976-000 031-01976-000 * 38 Harness, Compressor 025-31884-000 025-31884-000 * 39 Nameplate, Bezel 035-13508-000 035-13508-000 * 40 Harness, Wiring (3 Wire) 373-20055-006 373-20055-006 * 41 Harness, Wiring (8 Wire) 373-20055-007 373-20055-007
New replacement parts shown in bold face type at the first printing of parts list dated 4/03. Major components and suggested stocking items are shown with shaded item number. “
TO ORDER AUTHORIZED FACTORY REPLACEMENT PARTS - Contact your local Mitsubishi Electric distributor. or visit our website at www.mrslim.com for a Distributor and Dealer listing.
022-09049-750 --- · 024-25895-000 ---

Mitsubishi Electronics 2003 036-21544-001 Rev. B (1103) Supersedes: 036-21544-001 Rev. A (0903)


Specifications are subject to change without notice.