eth1000_large.jpg Using ICC E TH-1000 EtherNet/IP Interface w ith Mitsubishi i Q PLC.
i Contents Contents ..................................................................................................... .............................................................. i FURT HER READING REF ERENCE LI ST ..............................
ii FURTHER RE A DING REFE RENCE LIST ( Mitsub ishi Q Correspond ing MELSE C Comm unication Protocol R eference Manua l SH(NA)-08000 8-K QnUCPU Us er’s Manual C ommunic ation via Built-in Ether net P.
iii This Page is intentionall y left blank!.
1-1 Chapter 1 Introduction This document provides instruc tions and ex amples on how t o configure a s y stem c onsists of Rockwell ControlLogix PLC, an ICC ET H-1000 Gat eway, and Mitsubish i iQ PLC s y stem . An Example of the system configurat ion is shown in Fi gure 1 below.
2-1 Chapter 2 System Overview A Verification Sy stem is used as a test bed for verif ying the steps docum ented in this Quick Start guide. The Verification System is s hown in Figure 2 be low with the IP address ass ignments of al l the devices. Netgear Switch Monitoring Laptop 2 192.
3-1 Chapter 3 Connecting Devices to the Network The steps of configuring th e IP addresses of the ControlLo gix PLC system , the ICC ETH -1000 module, an d the PLC are doc umented in th is chapter. 3.1 Changing th e IP Address of the ControlL ogix System The minimum configuration of a ControlLogix syst em consists of a ControlLogix c hassis (e.
3-2 4. Right-Click on the ENBT M odule and se lect “Module C onfiguration” from the drop down list: 5. Under the “P ort Configur ation” tab, se lect the Net work Configurati on Type to be “Static”, and o ne can m odify the IP ad dress and the Ne twork Mask to the desired values.
3-3 6. Once the n ew I P addres s is set, it is ver y likely ( depending on wha t IP address and Net work m ask were as signed to the E NBT m odule) that the C onfiguration PC wi ll no longer be abl e to comm unicate with the ENBT module.
3-4 2. Click the “Auto Conn ect” b utton, a nd the ETH- 1000 module w ill b e con nected, and the screen will be populat ed with the cur rent information: The proper devic e type is sho wn with a green LED lit showing the co nnection has been established.
3-5 5. After the do wnload, the s ystem wi ll need to be reset fo r the changes to take ef fect. Click “Y es” to the pop-up m essage and the ETH-1000 will go through the r eset sequence 6. After the ET H-1000 system reboot, the screen sho uld show the ne w IP address .
3-6 3.3 Changing th e IP Address es of the iQ PLC Built-in Ethern et Port The f ollowing are steps to c hange the IP a ddress of the iQ PLC Built-in Ethernet Port: 1. Open the GX W orks2 on the C onfiguration PC a nd create a ne w pr oject for the appropriate CPU Module (e.
3-7 c. Click the Open Setting box and enter the first channel as MC Protocol with a proper Host Station Por t number (In th is example, the Port Number is set at Hex 5001) 3.
3-8 3.4 Configuring the External Eth ernet Mod ule in the iQ System W hen app lication requires, an externa l E thernet modul e c an be added to the syst em and comm unicating to the iQ CPU. This sect ion describes the co nfiguration of a QJ7 1E71-100 modu le to be used in the comm unication with a CLX through the ICC ETH-1000 gateway.
3-9 2. At the “Ethern et Operatio n Setting windo w”, one can config ure the IP addre ss of the Ethernet module. a. Set the Com munication Dat a Code to Binar y b. Check the “Enable Online Change” check box c. Select the “ Initial Tim ing” to be A lways wait f or OPEN (Com munication pos sible at ST OP time).
3-10 3. At the Net work Parameter Setting window, click “Open Setting” a nd op en the wind ow be low a nd enter the par ameters as shown: a. Configure the Host Station Port Num ber to matc h the C onnection Object port number configured in the ICC ET H-1000.
4-1 Chapter 4 ControlLogix PLC P roj ect Configuration The configuratio n s teps of a ControlL ogix pr oject are described this Chapter. T hese steps are us ed to comm unicate with an ICC ETH -1000 module. It is assum ed that the user has basic k nowledge in using RSLogix5000 software to perform the basic configurati on steps.
4-2 3. In the “Select Module” pop- up window, cho ose the “Com munications” 4. Then select th e proper m odule 1756 ENBT.
4-3 5. Then s elect the Major Revision level of the ENBT firm ware. In the Verification System, the m ajor revision le vel of the ENBT module is 2. 6. Enter th e proper Name, Slot Location, Revision Level and IP Addres s of the ENBT module. In the Verification System, the module nam e is set at CSC_EIP, the revision firm ware level is 2.
4-4 7. Click “O K” to accept t he configurat ion and m ake no add itional conf iguration changes to the “Connection” t ab. Sim ply click “OK” again to accept the configuration.
4-5 2. Select the “C ommunicatio ns” and expa nd the tree for additional sel ection. 3. Choose the Ethernet-Mod ule Generic Ether net Module 1 Introduction 2 System Overview 3 Devices to the Netwo.
4-6 4. Double C lick on the se lection an d c onfigure the I CC module according ly. T his is a critica l configurat ion step to e nsure the ETH-1000 will w ork properly in the s ystem as the application requires. Please a lso cons ult the ICC ET H-1000 Us er’s Manua l carefull y about t he configur ation of these item s.
4-7 5. Configure the RPI to 10.0 ms. 6. Select “OK” to accept the c onfiguration an d complete the ICC Module C onfiguration. 7. Double c lick on the “Co ntroller T ags” selec tion, and the fo.
4-8 a. 248 integer tags were created for CSC_ICC_ ETH1000_INT :I. These are the t ag locations where I CC will transf er the data to the ControlLog ix us ing Implicit Messag e prot ocol ev ery RPI. b. 248 integer t ags were created f or CSC _ICC_ETH 1000_INT:O.
5-1 Chapter 5 ETH-1000 Configuration The s teps to configur e th e ETH-1000 m odule to work with the ControlLog ix PLC usin g Et herNet/IP Im plicit Messaging and Mitsubish i controllers usin g MC Proto col are docum ented. Configuring the Validation System as sh own in Figur e 2 is used as the exam ple.
5-2 2. Select th e EtherNet/I P t ab of the ICC Conf iguration scr een an d d efine the ICC Database locations where dat a items w ill be exc hanged between the Co ntrolLogix PL C and th e ICC module throug h the Implicit Mess aging protoc ol.
5-3 The database addr esses in the ICC ar e us ed t o address “by te” data locat ions. Thus, 248 wor ds will take up 49 6 database addr esses. 3. Select the “M onitor” tab and c heck the “Dis play Usage ” c heckbox to sho w the DB m emor y loc ations that are conf igured for use by both the Pro duced and Consumed data .
5-4 2. Enter the IP address of the controller that will be co nnected. The IP is 192.16 8.1.40 for this exam ple 3. Enter the Port Number in d ecimal. T he Port is 20481 or 0x 5001 for this exam ple. 4. Hit “Create” af ter the inf ormation is entered a nd the Co nnection Object is shown as below.
5-5 5. Enter the Start ing Point of the Data Registers where the data item s will be written i nto. I n this exam ple, the Starting Poin t is “12268.” 6. Enter the n umber of words to b e transferr ed in the “Nu m W ords” dialog box. In this exam ple, the number of words is “20.
5-6 9. Repeat th e steps 1-8 to de fine the other three s ervice obj ects to perf orm the tran sfers between ICC and iQ PLC. a. Define the Service Object t o read 20 Data Registers to ICC b.
5-7 c. Define the Service Object t o read 10 words of Link Rel ay to ICC 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC Project Configuration 5 ETH-1000 Configuration 6 U.
5-8 5.2.3. Configu ring the Connecti on Object for Q J71E71 Ethernet Modu le Repeat steps docum ented in S ections 5.2.1and 5.2 .2 to configure t he Connec tion and Service objects to comm unicate to the ext ernal Ethernet m odule in the system . 1. Creat a Connecti on Obj ect first with name Connection2.
5-9 5.2.4. Calculating the ICC ET H-1000 DB A ddres ses One of the most important steps in config uring a serv ice objec t is to de termine the D atabase Address that n eeds to be entered.
6-1 Chapter 6 Using EtherNe t/IP Explicit Messaging The ControlLogix PLC can com municate with the Mitsub ishi i Q PLC using E IP Explicit Messaging format through the ICC ETH-1000 gateway. The communication is accom plished throu gh the use of MSG instructions in RSLogix5 000.
7-1 Chapter 7 Terminolog y Implicit (I/O Data) Messaging Connecti ons are established to mo ve appli cation-specifi c I/O data at regular intervals. Th ese conne ctions often are s et u p a s one-t o-many rel ationship s in order to tak e fu ll ad v antage of t he p roducer- consume r m ulticast mod el.
Rev-1 Revisions July 2009 – Document c reated and Rel eased, Vers ion 1.0 October 20 09 – Minor revis ion to wording t hroughout t he docum ent, Version 1.
Een belangrijk punt na aankoop van elk apparaat Mitsubishi ETH-1000 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Mitsubishi ETH-1000 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Mitsubishi ETH-1000 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Mitsubishi ETH-1000 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Mitsubishi ETH-1000 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Mitsubishi ETH-1000 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Mitsubishi ETH-1000 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Mitsubishi ETH-1000 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.