FieldPoint ™ Operating Instructions FP-AI-112 and cFP-AI-112 16-Channel, 16-Bit Anal og Input Modu les These operating instructions descri be ho w to install and use the FP-AI-112 and cFP-AI-112 analog input modules (referred to inclusiv ely as the [c]FP-A I-112).
FP-AI-112 and cFP-AI-112 2 ni.com T o install the FP- AI-112, refer to Figure 1 and complete the follow ing steps: 1. Slide the terminal base key to either position X (used for an y module) or position 1 (used for the FP- AI-112). 2. Align the FP- AI-112 alignmen t sl ots with the guide rails on the terminal base.
© National Instruments Corp. 3 FP-AI-112 and cFP-AI-112 3. Using a number 2 Phillips scre wdriv er with a shank of at least 64 mm (2.5 in.) length, tighten the captiv e screws to 1. 1 N ⋅ m (10 lb ⋅ in.) of torque. The n ylon coating on the screws pre vents them from loosening.
FP-AI-112 and cFP-AI-112 4 ni.com Y ou can use an external power supply to po wer field de vices. Connect the positi ve lead of the e xternal power supply to both V terminals and the negat ive lead to both C termina ls. Ensure that the current through both V terminals can nev er exceed 2 A.
© National Instruments Corp. 5 FP-AI-112 and cFP-AI-112 Caution Cascading power between two modules defeats isolation between those modules. Cascading power from the network module defeats all isolation between modules in the FieldPoint bank.
FP-AI-112 and cFP-AI-112 6 ni.com Input Ranges The input ranges for voltage signals are 0 –1 V , 0 –5 V , 0 –10 V , ± 60 mV , ± 300 mV , ± 1V , ± 5 V , and ± 10 V . T o prevent inaccurate readings, choose an input range such that the signal you are measuring does not exceed either end of the rang e.
© National Instruments Corp. 7 FP-AI-112 and cFP-AI-112 ( number of input range s with 60 Hz filter ) × 0.10 s + ( number of channels with 500 Hz filter ) × 0.
FP-AI-112 and cFP-AI-112 8 ni.com Isolation and Sa fety Guidelines Caution Read the following in formation before attempting to connect the [c]F P-AI-112 to an y circuits that may contain hazardous voltages. This section describes the isolat ion of the [c]FP-AI-112 and its compliance wit h international sa fety standards.
© National Instruments Corp. 9 FP-AI-112 and cFP-AI-112 using 14 A WG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the backplane PE ground terminal.
FP-AI-112 and cFP-AI-112 10 ni.com Effecti ve resolution by inpu t range and filter setting Update period and input band width by filter setting Normal-mode rejection ............. ........ 95 dB Nonlinearity .......... ........... ......... ........ 0.
© National Instruments Corp. 11 FP-AI-112 and cFP-AI-112 T ypical and warranted accuracy b y input range and temperature range Note Full scale is the maximum value of the nominal input range. F or example, for the ± 10 V input range, full scale is 10 V and ± 0.
FP-AI-112 and cFP-AI-112 12 ni.com Physical Char acteristics Indicators ................... ......... ........... ... Green POWER and READY indicators W eight FP-AI-112..... ............. ............ ..... 142 g (5.0 oz) cFP-AI-112 ....... ..........
© National Instruments Corp. 13 FP-AI-112 and cFP-AI-112 Shock and Vibration These specifications apply only to the cFP-AI-112. NI recommends Compact FieldP oint if your application is subject to shock and vibration. Operating vibration, random (IEC 60068-2-64).
FP-AI-112 and cFP-AI-112 14 ni.com CE Compliance This product meets the essentia l requirements of applicable European Directi ves, as amended for CE ma rking, as follows: Lo w-V oltage Directi ve (s afety)...... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) .
© National Instruments Corp. 15 FP-AI-112 and cFP-AI-112 Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • Field.
© 2004 National I nstruments Corp. All rights reser ved. 371330A-01 Jul04 *371330A-01* FieldPoint™, Nati onal Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporati on. Product and company names ment ioned herein are trademarks or trade names of thei r respective companies.
Een belangrijk punt na aankoop van elk apparaat National Instruments FP-AI-112 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen National Instruments FP-AI-112 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens National Instruments FP-AI-112 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding National Instruments FP-AI-112 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over National Instruments FP-AI-112 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van National Instruments FP-AI-112 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de National Instruments FP-AI-112 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met National Instruments FP-AI-112 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.