Outdoor Heat Pump 13 SEER R-410A High Effi ciency Split System User’ s Inf ormation/Installation Instructions These units hav e been designed and tested f or capacity and effi ciency in accordance with A.
2.
3 2. Set the ther mostat temper ature to the desired temperature le v el using the temperature selector . Please ref er to the separate detailed thermostat user’ s manual f or complete instructions regarding ther mostat prog ramming.
4 of snow and ice on the heat tr ansfer coil. This is nor mal, and the unit will periodically defrost itself . Dur ing the defrost cycle, the outdoor f an will stop , and the compressor will continue to run and heat the outdoor coil, causing the snow and ice to melt.
5 GENERAL INFORMA TION Read the f ollowing instructions completely before perf or ming the installation. CA UTION: This unit uses refrigerant R-410A. DO NO T under an y circumstances use any other refrigerant besides R-410A in this unit. Use of another refrigerant will damage this unit.
6 outdoor unit must be installed in such a manner that airfl o w through the coil is not obstr ucted and that the unit can be ser viced. Facility Prerequisites — Electrical pow er supplied must be adequate f or proper operation of the equipment.
7 Wire Size based on N.E.C . for 60° type copper con- ductors. COPPER WIRE SIZE — AWG (1% Voltage Drop) Supply Wire Length-Feet Supply Circuit 200 150 100 50 Ampacity 6 8 10 14 15 468 1 2 2 0 468 1.
8 GR W 2 CE O Y Thermostat Green Red Br own G R W 2 Orange Grey OY R C Air Handler Heat Pump OD Section T ypical Heat Pump with Standard Air Handler W 2 C W NO TE: Jumper between W2 and E is required when no OD T -Stat is used.
9 GR W 2 CE O Y Thermostat Green Red White G R Grey O Y R C Air Handler Heat Pump OD Section T ypical Heat Pump with Outdoor Thermostat and Air Handler W 2 C W E A typical installation with a heat pump ther mostat, air handler , and heat pump with an outdoor ther mostat.
10 Functional Chec kout: CA UTION: If equipped with a compressor crankcase heater , wait 24 hours prior to performing a function c heck out to allow f or heating of the compressor crankcase. F ailure to comply ma y result in damage and could cause premature failure of the system.
11 Figure 2. Comfort Alert TM Diagnostics Module POWER ALERT TRIP TRIP LED (Red): indicates there is a demand signal from the ther mostat b ut no current to the compressor is detected by the module . The TRIP LED typically indicates the compressor protector is open or ma y indicate missing supply power to the compressor .
12 T able 1. Interpreting the Diagnostic LEDS Status LED Sta tus LED Description Status LED T roubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” Thermostat demand signal 1 . Compressor protector is open Y is present, but the 2 .
13 T able 2. Module Wiring T r oubleshooting f or any unusual noises . If present, locate and deter mine the source of the noise and correct as necessar y . OUTDOOR THERMOST A T (if supplied) The outdoor ther mostat pre v ents the electrical auxiliar y heat (if used) from operating abo v e a desired set point.
14 13 SEER SPLIT SYSTEM HEA T PUMP ORIFICE USA GE Model System Charge Number Indoor Outdoor R-22 (oz.) 1-1/2 Ton .050 .042 112 2 Ton .055 .045 138 2-1/2 Ton .065 .048 145 3 Ton .073 .052 168 3-1/2 Ton .077 .055 243 4 Ton .080 .058 248 5 Ton .089 .062 248 Restrictor Bore Size (in.
15 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts *Note: All pressures are listed in psig. and all temperatures in deg.
16 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts 024K OUTDOOR TEMPERA TURE ( deg. F ) 70 75 80 85 90 95 100 105 Suc. Press. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press. Dis. T emp . Liq.
17 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts 036K OUTDOOR TEMPERA TURE ( deg. F ) 70 75 80 85 90 95 100 105 Suc. Press. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press. Dis. T emp . Liq.
18 Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Char ts 048K OUTDOOR TEMPERA TURE ( deg. F ) 70 75 80 85 90 95 100 105 Suc. Press. Liq. Press. Dis. T emp . Liq. Press. Dis. T emp. Liq. Press . Dis. T emp. Liq.
19 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 018K O UT DO O R T EM PE RAT URE ( DEG . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Dis c h. S uc. Liquid Disc h. S uc. Liquid Disc h. S uc. Liquid Disc h. S uc .
20 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 030K O UT DO O R T EM P ERAT URE ( DE G . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Disc h. Suc . Liquid Disc h. S uc. Liquid Disc h. Suc . Liquid Dis ch. Suc .
21 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 042K O UT DO O R T EM P ERAT URE ( DE G . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Disc h. Suc . Liquid Disc h. Suc . Liquid Dis ch. Suc . Liquid Disc h. Suc .
22 Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Char ts 060K O UT DO O R T EM PE RAT URE ( DEG . F ) 0 1 02 03 04 05 06 0 S uc. Liquid Dis ch. Suc . Liquid Disc h. Suc . Liquid Dis ch. S uc. Liquid Disc h. Suc .
23.
INST ALLER: PLEASE LEA VE THESE INST ALLA TION INSTR UCTIONS WITH THE HOMEO WNER. 7084100 Specifi cations and illustrations subject to change without notice and without incurring obligations.
Een belangrijk punt na aankoop van elk apparaat Nordyne R-410A (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Nordyne R-410A heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Nordyne R-410A vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Nordyne R-410A leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Nordyne R-410A krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Nordyne R-410A bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Nordyne R-410A kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Nordyne R-410A . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.