Manual No. H-504 2008-02-15 RETROFIT INSTRUCTIONS FOR GSTC / SETC / NHTC / NHDI / NHSC Inst allation Manual TM.
Page ii 2008-02-15 PROPRIETARY NOTICE This document and the info rmation disclosed herei n are propriet ary data of W AL TER MEIER L TD. Neither this document nor the information cont ained herein shall be reproduced used, or disclosed to others without the written authoriza tion of W AL TER MEIER L TD.
2008-02-15 TABLE OF CONTENTS Subject Page 10-00 LINKS 2 - FIELD INSTALLATION OF A SE-50 1. FIELD INSTALLATION OF A SE-50 SERIES HUMIDIFI ER WITH A LINKS 2 REMOTE PACKAGE . . . . . . . 2 A. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . .
10-00 Page 1 2008-02-02 10-00 LINKS 2 - FIELD INSTALLATION OF A SE-50.
10-00 Page 2 2008-02-02 (1) FIELD INSTALLATION OF A SE- 50 SERIES NORTEC LINKS 2 REMO TE PACKAGE A. STEP 1 - INSTALLATION (1) Mount the LINKS 2 remote package in a convenient location. Note that the remote package does not need to be mounted in close proximity to the humidifier.
10-10 Page 1 2008-02-15 10-10 LINKS 2 - FIELD CONVERSION OF A GSTC/SETC.
10-10 Page 2 2008-02-15 (1) FIELD CONVERSION OF A GS TC/SETC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: A. WIRING THE NORTEC LINKS 2 MODUL E (1) Most of the wiring conn ec.
10-10 Page 3 2008-02-15 B. MOUNTING THE LI NKS 2 ASSE MBLY (1) Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the GS or SE unit. If pilot holes for the mounting screws are not already present on the humidifier frame follow steps 2 and 3.
10-10 Page 4 2008-02-15 C. CONFIGURING TH E HUMIDIFIERS (1) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can be determined by the presence of the Links module.
10-20 Page 1 2008-02-15 10-20 LINKS 2 - FIELD CONVERSION OF A NHTC.
10-20 Page 2 2008-02-15 (1) FIELD CONVERSION OF A NHTC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: Figure 1. Component Identification A. MOUNT THE LINKS 2 ASSEMBLY (1) The Nortec LINKS 2 assembly mounts on the top, right corner of the elect rical compartment.
10-20 Page 3 2008-02-15 Figure 2. Hook Position Figure 3. Assembly Mounting Location Hook Position Hook Position.
10-20 Page 4 2008-02-15 B. CONFIGURING THE H UMIDIFIERS (1) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can be determined by the presence of the Links module.
10-30 Page 1 2008-02-15 10-30 LINKS 2 - FIELD CONVERSION OF A NHDI/SC.
10-30 Page 2 2008-02-15 (1) FIELD CONVERSION OF A NHDI/SC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: Figure 1. Component Identification A. MOUNT THE LINKS 2 ASSEMBLY (1) Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the NHDI or NHSC unit.
10-30 Page 3 2008-02-15 Figure 2. LINKS 2 Bracket Placement B. WIRING THE NORTEC LINKS 2 MODUL E (1) Most of the wiring connections for the Nortec LINKS 2 module will have already been finished at the factory, however, there are a few connections that will need to be made to connect the module to the NHDI/SC series humidifier.
10-30 Page 4 2008-02-15 Figure 3. NHDI LINKS 2 Slave Installation (3) Installation of LINKS 2 Slave Option (a) The LINKS 2 module is capable of supporting up to 8 humidifiers when each unit is equipped with a TTL to RS-485 signal conv erter. The LINKS 2 slave option consists of a small bracket with the signal converter mounted on one side.
10-30 Page 5 2008-02-15 (4) Configuring the Humidifiers (a) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can b e determined by the presence of the LINKS module and should be set to modbus address 1.
WARRANTY (1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collective ly referred to as THE COMPANY), warrant for a period of two years afte r installation or 30 months from manufacturer’s.
Authorized Agent: INST ALLA TION DA TE (MM/DD/YYYY) MODEL # SERIAL # CYLINDER # U.S.A. W alter Meier (Climate USA) Inc. 826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: nortec@humidity .com WEBSITE: www .humidity .com CANADA W alter Meier (Cli mate Canada) Ltd.
Een belangrijk punt na aankoop van elk apparaat Nortec Industries NHSC (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Nortec Industries NHSC heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Nortec Industries NHSC vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Nortec Industries NHSC leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Nortec Industries NHSC krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Nortec Industries NHSC bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Nortec Industries NHSC kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Nortec Industries NHSC . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.