iLD24-UTP , iLD44-UTP Big Display Universal T emperature & Process Contr oller Manual U ser ’ s Guide www .omega.com e-mail: info@omega.com iSeries info: www .
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply . OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
T ABLE OF CONTENTS Part 1: Introduction ............................................................................................ 2 1.1 Description ................................................................................. 2 1.2 Safety Considerations .
LIST OF FIGURES: Figure 2.1 Mounting ............................................................................................... 5 Figure 2.2 Rear Panel Power and Output Connector Labels .............................. 7 Figure 2.3 Rear Panel Input Connector Labels .
NO TES, WARNINGS and CA UTIONS Information that is especially important to note is identified by following labels: • NOTE • W ARNING or CAUTION • IMPORT ANT • TIP NOTE: Provides you with information that is important to successfully setup and use the Programmable Digital Meter .
P ART 1 INTRODUCTION 1.1 Description This device can be purchased as monitor (read process value only) or as a controller . • The iLD Big Display controller offers unparalleled flexibility in process measurement.
1.2 Safety Considerations This device is marked with the international caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility).
1.3 Before Y ou Begin Inspecting Y our Shipment: Remove the packing slip and verify that you have received everything listed. Inspect the container and equipment for signs of damage as soon as you receive the shipment. Note any evidence of rough handling in transit.
5 P ART 2 SETUP 2.1 Mounting Figure 2.1 Mounting.
Mounting iLD Big Display Through Panel: 1. Using the panel cutout diagram shown in your Quick Start Manual, cut an opening in the panel. 2. Remove six (or eight) screws at the back of iLD Big Display to remove back cover .
7 2.2 Rear Panel Connections The rear panel connections are shown in Figures 2.2 and 2.3. Figure 2.2 Rear Panel Power and Output Connections Figure 2.3 Rear Panel Input Connections T able 2.
8 2.3 Electrical Installation 2.3.1 Power Connections Caution: Do not connect power to your device until you have completed all input and output connections. Failure to do so may result in injury! Connect the main power connections as shown in Figure 2.
9 2.3.2 Thermocouple The figure below shows the wiring hookup for any thermocouple type. For example, for T ype K hookup, connect the yellow wire to the TB7(+) terminal and the red wire to the TB8(-) terminal. When configuring your controller , select Thermocouple and Thermocouple T ype in the Input T ype menu (see Part 3).
10 2.3.3 T wo/Three/Four-Wire RTD The figures below show the input connections and input connector jumpers (shown in bold lines) required to hookup a 2-, 3- or 4-wire RTD.
11 2.3.4 Process Current The figure below shows the wiring hookup for Process Current 0 – 20 mA. Figure 2.8 Process Current Wiring Hookup (Internal and External Excitation) When configuring your instrument, select Process T ype in the Input T ype Menu (see Part 3).
12 2.3.6 Wiring Outputs This meter has two, factory installed, outputs. The SPDT Mechanical Relay , SPST Solid State Relay , Pulse and Analog Output Connection are shown below . Figure 2.10 a) Mechanical Relay and SSR b) Pulse and Analog Outputs Wiring Hookup Outputs Wiring Hookup This device may have a programmable communication output.
13 This device may also have an excitation output. Figure 2.12 Excitation Output Excitation is not available if communication option is installed. This device has snubber circuits designed to protect the contacts of the mechanical relays when it switches to inductive loads (i.
14 P ART 3 OPERA TION: Configuration Mode 3.1 Introduction The instrument has two different modes of operation. The first, Run Mode, is used to display values for the Process V ariable, and to display or clear Peak and V alley values.
15 3.2 Menu Configuration It is recommended that you put the controller in the Standby Mode for any configuration change other than Setpoints & Alarms.
16 3.2.1 ID Number SEE ID MENU SELECTION IN CONFIGURA TION SECTION FOR ENABLE/DISABLE OR CHANGE ID CODE. If ID Code is Disabled or set as Default (0000) the menu will skip ID step to Setpoint Menu. If ID Code is set to Full Security Level and user attempts to enter the Main Menu, they will be prompted for an ID Code.
17 3.2.2 Set Points SETPOINT 1: Press a 1) Press a , if necessary until SP1 prompt appears. Press d 2) Display shows previous value of “Setpoint 1”.
18 3.2.3 Configuration Menu Figure 3.2 Flow Chart for Configuration Menu Enter Configuration Menu: Press a 1) Press a , if necessary , until CNFG prompt appear . Press d 2) Display advances to INPT Input Menu. Press a 3) Pressing and releasing a to scroll through all available menus of Configuration section.
19 Input T ype (Thermocouple) ENTER INPUT TYPE MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press d 3) Display flashes T.ç , RTD or PROC (Thermocouple, RTD or Process). If the displayed input type is T.
20 Input T ype (RTD) ENTER INPUT TYPE MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press d 3) Display flashes T.ç , RTD or PROC (Thermocouple, RTD or Process). If the displayed input type is RTD , press a to skip to step 6 ( RTD stops flashing).
21 Input T ype (Process) ENTER INPUT TYPE MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press d 3) Display flashes T.ç , RTD or PROC (Thermocouple, RTD or Process). If the displayed input type is PROC , press a to skip to step 6 ( PROC stops flashing).
22 ENTER READING CONFIGURA TION MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Display advances to RDG Reading Configuration Menu. Press d 4) Display advances to DEC Decimal Point.
23 Reading Configuration (If Process was selected) INPUT/READING (SCALE AND OFFSET) SUBMENU: Input V oltage or Current can be converted or scaled into values appropriate for the process or signal being measured. So, a reading may be displayed, for example, in units of weight or velocity instead of in amperes or volts.
24 Conversion number is a coefficient of conversion between input values and real full display range (10000 counts, shown as 9999). See T able 3.2 below for proper conversion number .
25 3.2.6 Alarm 1 This unit is equipped with two physical outputs that can only be configured as follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2 .
26 ALARM 1 ENABLE/DISABLE SUBMENU: Press b 5) Scroll though the available selection until ENBL displays to use Alarm 1. Press d 6) Display shows STRD stored message momentarily and then advances to ABSo only if it was changed, otherwise press a to advance to ABSo Alarm 1 Absolute/Deviation Submenu.
27 CONT ACT CLOSURE SUBMENU: Press d 11 ) Display flashes previous selection. Press b to N.ç. Normally Closed or N.o. Normally Open. Press d 12) Display shows STRD stored message momentarily and then advances to AçTV only if it was changed, otherwise press a to advance to AçTV Active Submenu.
28 ALARM ENABLE/DISABLE A T POWER ON: Press d 15) Display flashes previous selection. Press b to ENBL enable or DSBL disable. Press d 16) Display shows STRD stored message. momentarily and then advances to ALR.L only if it was changed, otherwise press a to advance to the ALR.
29 3.2.7 Analog Output (Retransmission) Analog Output can be configured as Retransmission or Control outputs. In this section we will discuss Retransmission Output.
30 ANALOG OUTPUT ENABLE/DISABLE SUBMENU: Press b 5) Scroll though the available selection until ENBL displays to use Analog Output Retransmission (output proportional to the input signal).
31 Accuracy of Analog Output board is +/-1% of FS (Full Scale) when following conditions are satisfied: 1. The input is not scaled below 1% of Input FS (10 mV @ 1 V or 0.2 mA @ 20 mA input ranges). 2. Analog Output is not scaled below 3% of Output FS (300 mV @ 10 V or 0.
32 3.2.8 Alarm 2 This unit is equipped with two physical outputs that can only be configured as follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2 .
33 ALARM 2 ENABLE/DISABLE SUBMENU: Press d 5) Display flashes previous selection. Press b until ENBL displays to use Alarm 2. Press d 6) Display shows STRD stored message momentarily and then advances to ABSo only if it was changed, otherwise press a to advance to ABSo Absolute/Deviation Submenu.
34 LOOP BREAK TIME V ALUE SUBMENU: Press d 7) Display flashes 1 st digit of previous Loop V alue. Press b & c 8) Press b and c buttons to enter a new Loop V alue (0 to 99.59). Press d 9) Display shows STRD stored message momentarily and then advances to R.
35 THERMOCOUPLE FIELD CALIBRA TION SUBMENU: RTD and Process are perfectly calibrated. This section is applicable to Thermocouple (TC) calibration only . Be sure that the TC being used to calibrate the meter is of the type selected in the TC submenu. Place the TC in an ice-bath (or other 0°C / 32°F environment).
36 3.2.10 Output 1 Alarm 1 and Output 1 or Analog Output (Retransmission) share the same contacts on the rear panel connector . If Alarm 1 or Analog Output (Retransmission) is Enabled , Output 1 is automatically Disabled .
37 ENTER OUTPUT 1 MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a , if necessary , until Display advances to OUT1 Output 1 Menu. Press d 4) Display advances to SELF Self Submenu.
38 MAXIMUM/PERCENT HIGH SUBMENU: Specify in percent, the maximum value (99) for control output. If the output is analog proportional (Current or V oltage), then the maximum voltage or current, in percent, is specified. If the output is time proportional (Relay , SSR, or Pulse), then the maximum duty-cycle, in percent, is specified.
39 ACTION TYPE SUBMENU: The error that results from the measurement of the Process V ariable may be positive or negative since it may be greater or smaller than the Setpoint. If a positive error should cause the instrument output to increase (i.e. cooling), it would be called Direct Acting .
40 If Anti Integral (Anti Windup) Submenu “Enabled” , this feature allows the error term outside the proportional band to be calculated and accumulated for integration. This may be an important feature in applications where fast response time is desirable.
41 RESET SETUP SUBMENU: Press d 33) Display flashes 1 st digit of the previous I REST Reset value. Press b & c 34) Press b and c buttons to enter a new “Reset” value. Press d 35) Display shows STRD stored message momentarily and then advances to RATE only , if it was changed, otherwise press a to advance to RATE Rate Setup Submenu.
42 DAMPING F ACTOR SUBMENU: Press d 42) Display flashes the previous “Damping Factor” selection. Press b 43) Scroll through the available selections: 0000 , 0001 , 0002 , 0003 , 0004 , 0005 , 0006 , 0007 .
43 3.2.1 1 Output 2 Output 2 and Alarm 2 share the same contacts on the rear panel connector . If Alarm 2 is Enabled , Output 2 is automatically Disabled . Figure 3.10 Flow Chart for Output 2 ENTER OUTPUT 2 MENU: Press a 1) Press a , if necessary , until CNFG prompt appears.
44 ACTION TYPE SUBMENU: The error that results from the measurement of the Process V ariable may be positive or negative since it may be greater or smaller than the Setpoint. If a positive error should cause the instrument output to increase (i.e. cooling), it would be called Direct Acting .
45 CYCLE TIME SUBMENU: Press d 15) Display flashes 1 st digit of the previous “Cycle T ime” value. Press b & c 16) Press b and c buttons to enter a new “Cycle T ime” value (1 to 199 seconds).
46 3.2.12 Ramp & Soak Figure 3.1 1 Flow Chart for Ramp and Soak ENTER RAMP AND SOAK MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a , if necessary , until Display advances to RAMP Ramp and SOAK Soak Menu.
47 Ramp & Soak provides users with the flexibility to slowly bring the Process V ariable (PV) to the desired setpoint. Ramp & Soak values are specified in HH.MM format. The Ramp value indicates the time specified to bring the process variable to Setpoint 1 (SP1).
48 3.2.13 ID CODE Figure 3.12 Flow Chart for ID Code ENTER ID CODE MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a , if necessary , until Display advances to ID ID Code Menu.
49 ENTERING OR CHANGING YOUR (DEF AUL T) ID CODE: Enter ID menu (Repeat steps from 1 to 3). Press d 10) Display advances to CH.ID Change ID Code Submenu.
50 3.2.14 COMMUNICA TION OPTION Purchasing the controller with Serial Communications permits an instrument to be configured or monitored from an IBM PC compatible computer using software available from the website or on the CD-ROM enclosed with your shipment .
51 ENTER COMMUNICA TION OPTION MENU: Press a 1) Press a , if necessary , until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a , if necessary , until Display advances to COMM Communication Options Menu. Press d 4) Display advances to C.
52 STOP BIT SUBMENU: Press d 15) Display flashes previous selection for “Stop Bit”. Press b 16) Scroll through the available selections: 1-BIT , 2-BIT . Press d 17) Display shows STRD stored message momentarily and then advances to BUS.F only , if it was changed, otherwise press a to advance to BUS.
53 Press d 25) Display flashes previous selection for “Echo”. Press b 26) Scroll through the available selections: NO, YES. Press d 27) Display flashes STRD stored message momentarily and then advances to STND only if it was changed, otherwise press a to advance to STND Communication Standard Submenu.
54 DA T A FORMA T SUBMENU: Preformatted data can be sent automatically or upon request from the controller . Use the Data Format Submenus to determine what data will be sent in this preformatted data string. Refer to the iSeries Communications Manual for more information about the data format.
55 TEMPERA TURE UNIT SUBMENU: Includes a byte in the data string to indicate whether reading is in Celsius or Fahrenheit. Press d 50) Display flashes previous selection for UNIT .
56 3.2.15 DISPLA Y COLOR SELECTION This submenu allows the user to select the color of the display . Figure 3.14 Flow Chart for Display Color Selection ENTER DISPLA Y COLOR SELECTION MENU: Press a 1) Press a , if necessary , until CNFG prompt appears.
57 ALARM 2 DISPLA Y COLOR SUBMENU: Press d 11 ) Display flashes previous selection for “Alarm 2 Color Display”. Press b 12) Scroll through the available selections: GRN , RED or AMBR .
58 Example 3: Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300, Output 2 = Relay , Setpoint 2 = 200 Alarm 1 & 2 Setup: Deviation, Band, “ALR.
59 Configuration Single-ended Polarity Unipolar Step Response 0.7 sec for 99.9% Decimal Selection None, 0.1 for temperature None, 0.1, 0.01 or 0.001 for process Setpoint Adjustment -1999 to 9999 counts Span Adjustment 0.
60 EXCIT A TION (optional in place of Communication) 24 Vdc @ 25 mA INSULA TION Power to Input/Output 2500 V ac per 1 minute test (RS-232/485, Input or Output) Between Inputs 500 V ac per 1 minute test Approvals See CE Approval Section GENERAL Power 100-240 V ac +/-10%, 50/60 Hz 22.
61 J K T E R S B C N L RTD RTD T able 4.1 Input Properties TC Input T ype Range Accuracy* Iron-Constantan -210 to 760°C 0.4°C -346 to 1400°F 0.7°F -270 to -160°C 1.0°C CHROMEGA ® - -160 to 1372°C 0.4°C ALOMEGA ® -454 to -256°F 1.8°F -256 to 2502°F 0.
62 P ART 5 F A CTOR Y PRESET V AL UES T able 5.1 Factory preset value MENU ITEMS F ACTOR Y PRESET V ALUES NOTES Set Point 1 (SP1) 000.0 Set Point 2 (SP2) 000.0 Input: Input T ype (INPT) TC, type K Reading Configuration (RDG): Decimal Point (DEC.P) FFF .
63 MENU ITEMS F ACTOR Y PRESET V ALUES NOTES Ramp & Soak (RAMP) : Ramp (RAMP) Disable (DSBL) Soak (SOAK) Disable (DSBL) Ramp V alue (RAMP) 00:00 Soak V alue (SOAK) 00:00 ID : ID V alue 0000 Full ID (FULL) Disable (DSBL) Set Point ID (ID.
64 CE APPROV AL INFORMA TION 1. Electromagnetic Compatibility (EMC) This device conforms with requirements of EMC Directive 89/336/EEC, amended by 93/68/EEC.
NO TES 65.
WARRANTY / DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase.
W her e Do I Find Ev er ything I Need f or Pr ocess Measurement and Contr ol? OM EGA…Of Cour se! Shop on line at www.omega.com TEMPERA TURE Thermocouple, R TD & Thermistor Probes, Connec.
Een belangrijk punt na aankoop van elk apparaat Omega ILD24-UTP (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Omega ILD24-UTP heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Omega ILD24-UTP vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Omega ILD24-UTP leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Omega ILD24-UTP krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Omega ILD24-UTP bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Omega ILD24-UTP kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Omega ILD24-UTP . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.