PV500 - 22A 08 - 98 1 Section 22A INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER B40 OIL BURNER 1.0 thru 10.0 gph CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a seasonal or annual combustion check - out be performed by a qu alified service agency to ensure safe and efficient operation.
PV500 - 22A 08 - 98 2 Section 22A PVI FIREPOWER B40 OIL BURNER ELECTRICAL 1. Wiring to the unit should conform to the National Electrical Code or the code legally authorized to your locality. A fused disconnect switch should be used for water heater control.
PV500 - 22A 08 - 98 3 Section 22A PVI FIREPOWER B40 OIL BURNER START - UP (Refer to Figure 22 - 1 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. The wiring diagram, located on the backside of the cover, will show the controls used in our circuitry.
PV500 - 22A 08 - 98 4 Section 22A PVI FIREPOWER B40 OIL BURNER START - UP (con't) After purging is complete, terminal 3 energizes the oil valve and terminal 4 energizes the ignition transformer. The flame is then established and the VDC reading on the meter should read a steady 14 - 18 VDC for photocell or 4 - 6 VDC for UV amplifiers.
PV500 - 22A 08 - 98 5 Section 22A PVI FIREPOWER B SERIES OIL BURNER START - UP (con't) 20. Record the following information for future use: a) Air shutter position ________________ b) Oil supply pressure ____________PSIG c) Stack draft _________________" W.
PV500 - 22A 08 - 98 6 Section 22A PVI FIREPOWER SINGLE STAGE B SERIES OIL BURNER ADJUSTMENTS AIR ADJUSTMENT Loosen the locking screw and move the knob (A) along the scale (B) to the position wanted and tighten the screw. Check the air adjustment by making a flue gas analysis.
PV500 - 22A 08 - 98 7 Section 22A PVI FIREPOWER TWO STAGE B SERIES OIL BURNER ADJUSTMENTS AIR ADJUSTMENT First stage : Set the operating switch on low capacity. Loosen the screw (A) and move the damper ar m (C) along the scale (E) to a position where the flame does not soot nor blow out.
PV500 - 22A 08 - 98 8 Section 22A PVI FIREPOWER NOZZLE POSITION INPUT - GPH NOZZLE POSITION 1.4 1 2.8 3 4.3 4 5.7 2 7.2 2 8.6 4 TABLE 22 - 2 Figure 22A - 8.
PV500 - 22A 08 - 98 9 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER 1. BURNER FAILS TO START: A. Defective on/off or fuel transfer switch. Replace switch. B. Control circuit has an open control contact. Che ck limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 22A 08 - 98 10 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER (con't) 4. OIL FLAME IGNITES, BUT THEN FLAME SAFEGUARD CONTROL LOCKS OUT ON SAFETY: A. Flame scanner lens dirty. Remove and clean. B. Scanner si ght tube blocked or dirty.
PV500 - 22A 08 - 98 11 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER (con't) 6. OIL HIGH FIRE INPUT RATE CANNOT BE ACHIEVED: A. Oil nozzle size too small. Remove nozzle and check marking. Replace with correct size nozzle. B.
Een belangrijk punt na aankoop van elk apparaat PVI Industries B40 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen PVI Industries B40 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens PVI Industries B40 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding PVI Industries B40 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over PVI Industries B40 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van PVI Industries B40 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de PVI Industries B40 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met PVI Industries B40 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.