Gebruiksaanwijzing /service van het product RJNA Series van de fabrikant Rheem
Ga naar pagina of 50
FORM NO . P1 1 -763 R EV . 1 Supersedes F orm No. P1 1 -763 P ACKAGE H EA T P UMP U NITS RJNA- HIGH EFFICIENCY SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] *Unit shown with optional louver panels installed. “CERTIFIED UNDER THE A.R.I. CERTIFICA TION PROGRAM—A.
2 T ABLE OF CONTENTS I nt r od uc ti on .................................................................................................. 3-4 Mo d el Id en t if ic a ti on Op t io ns....................................................................
3 INTRODUCTION These qualit y features are included in the Rhe em Outdoor P acka g e Heat Pumps Evaporator Coil/Filter Access Optional Electric Heater Kit Compressor Access Control Box Access Blower A.
4 INTRODUCTION INTRODUCTION ENGI NEERI NG FEA TURES RJNA- Series P ackage He at Pumps 1. All models fe ature Copeland ® Scr oll ® compressors offering maximum r eliabilit y , ef ficiency , and quiet operati on. 2. One-piece top o ver the indoor se ction with drip lip, dra wn painted b ase pan, and 1 " [25.
5 MODEL IDENTIFICA TION—RJNA- SERIES R JNA—A0 3 6JK 0 0 0 Electric Heat 000 = No Resistance Hea t 010 = 10 kW Resistance Hea t 015 = 15 kW Resistance Hea t 020 = 20 kW Resistance Hea t Drive P ack.
6 OPTIONS—RJNA- SERIES Option Code Low Ambient Reduced Height Baserails AA Side Flow AD AF x AK x Hail Guard x x BD x x CK x x x BX x AL x No Options Freeze Stat Time Delay x BS x F ACT OR Y I NST ALLED OPTION CODES FOR RJNA (3-5 T on) [1 0.6- 1 7 .
7 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A036CK A036CL A036CM A036DK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 37,600 [11] EER/SEER 2 11.
8 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A036DL A036DM A036JK A042CK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 42,500 [12.
9 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A042CL A042CM A042DK A042DL Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.
10 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A042DM A042JK A048CK A048CL Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.
11 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A048CM A048DK A048DL A048DM Cooling Performance 1 Gross Cooling Capacity Btu [kW] 49,500 [14.5] 49,500 [14.
12 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A048JK A060CK A060CL A060CM Cooling Performance 1 Gross Cooling Capacity Btu [kW] 49,500 [14.5] 63,500 [18.
13 GENERAL DA T A—RJNA- SERIES Model RJNA- Series A060DL A060DM A060JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 64,000 [18.8] 64,000 [18.
14 GENERAL DA T A—RJNA- SERIES NOTES: 1 . Cooling Pe r forma nce is rated a t 95° F ambient, 80° F entering dry bulb, 67 ° F entering we t bulb. Gross cap acit y does not include the effect of f an motor he at. ARI capacity is net and include s the ef f ect of fan mot or heat.
COOLING PERFORMANCE D A T A—RJNA-A036 HEA TI NG PERF ORMANCE D A T A—RJNA-A036 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 .
COOLING PERFORMANCE D A T A—RJNA-A0 42 HEA TI NG PERF ORMANCE D A T A—RJNA-A042 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0.
COOLING PERFORMANCE D A T A—RJNA-A0 48 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0 00 BTUH Sens —Sensible capacit y x 1 0 0.
COOLING PERFORMANCE D A T A—RJNA-A060 HEA TI NG PERF ORMANCE D A T A—RJNA -A060 DR —Depression ratio dbE —Entering air dr y bulb wbE—Enter ing air wet bulb T ot al —T ot al capacit y x 1 0.
External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—W et Coil 4.0 [14.07] Low Blower Size/ Motor HP [w] & # of Speeds Nominal Cooling Capacity T ons [kW] 3.
20 AIRFLOW PERFORMANCE—RJNA- SERIES 825 Models RJNA-A036 [10.55 kW] & A042 [12.31 kW]—Heat Pump (13 SEER) External Static Pressure—Inches of Water [kPa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.20] 0.9 [.22] 1.
BEL T -DRIVE AI RFL OW P ERFORMANCE COMPONENT AIR RESI ST AN CE NOTES: 1 . Performance shown with dr y coil, st andard 1" [25.4 mm] filters & side discharge. Add component resistance to determine tot al E.S.P . 2. St andard CFM @ .075 lbs./cu .
ELECTRICAL DA T A – RJNA SERIES Minimum Circuit Ampacity 19/19 Unit Information Unit Operating Voltage Range 187-253 Minimum Overcurrent Protection Device Size 25/25 Maximum Overcurrent Protection Device Size 25/25 Compressor Motor No. 1 Volts 208/230 Phase 3 HP 2.
ELECTRICAL DA T A – RJNA SERIES Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size 22/22 25/25 Maximum Overcurrent Protection Device Size 30/30 Compressor Motor No. 1 Volts 208/230 Phase 3 HP 3.5 RPM 3450 Amps (RLA) 12.4/12.4 Amps (LRA) Unit Information Unit Operating Voltage Range 88/88 187-253 Condenser Motor No.
24 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.
25 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 43/47 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 47/51 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.
26 UNITS WITH HEA TER KITS—RJNA- SERIES * A10C+ * A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50 * A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80/80 * A12C+ 8.4/11.2 28.66/38.21 23.4/27.0 48/52 50/50 60/60 * A15C+ 10.8/14.4 36.84/49.13 30.
27 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DK No Heat — — — 9 15 15 32.
28 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DL No Heat — — — 9 15 15 32.
29 UNITS WITH HEA TER KITS—RJNA- SERIES * A10D+ * A10D+ 9.6 32.75 11.6 24 25 25 * A20D+ 19.2 65.51 23.1 38 40 40 * A12D+ 11.2 38.21 13.5 26 30 30 * A15D+ 14.4 49.13 17.3 31 35 35 *A21D+ 19.2 65.51 23.1 38 40 40 9.6 A036DM No Heat — — — 9 15 15 32.
A036JK No Heat — — — 25/25 30/35 30/35 * A10J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80 * A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 51/55 60/60 60/60 *A11J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80 * A20J+ 14.4/19.2 49.13/65.51 69.3/80.0 112/125 125/125 125/125 * A12J+ 8.
UNIT D IMENS IONS P A CKA GE HEA T PUMPS [ ] Des igna tes Me tric C onv ers ions 31 UNIT DIMENSIONS—RJNA- SERIES.
UNIT D IMENS IONS P A CKA GE HEA T PUMPS [ ] Des igna tes Me tric C onv ers ions BOT TOM VIEW 32 UNIT DIMENSIONS—RJNA- SERIES.
SELECTION PR OCEDURE 1 . Determine cooling and heating requirements at design conditions. Example: T otal cooling capacity ............43,600 BTUH [1 2.78 kW] Sensible cooling capacity ......34,00 0 BTUH [9.96 kW] Condenser ent ering air ..........95°F [35°C] E vaporat or entering air .
Accessory Description Model Application 3 to 5 T on [10.6 to 17.6 kW] Accessory Model No. 3 to 5 T on [10.6 to 17.6 kW] Roofcurb Adapters RJNA- RXRX-BBCDB21 RXRX-BBCDB22 RXRX-BBCDB23 Economizer with S.
Roofcurb Adapters Old Models OLD CURB MODEL ROOFCURB ADAPTER NEW MODEL MEDIUM C ABINET (3 TON [1 1 kW]) 21 SE RI ES RXP A-CA2 1 (1) RXRA-DB21 (2) RXRX -BBCDB21 RJNA (-)SNC, (-)SND, (-)SNE (-)RGE, (-)RGF , (-)RGG (-)PNC, (-)PND EX TRA LARGE CABINET (3.
ROOFCURBS (F ull Perimeter) ■ Rheem’s ne w roofcurb design can be utiliz ed on 3 through 5 t on [1 0.6- 1 7 .6 kW] models. ■ T wo a vailable heights (1 4" [356 mm] and 2 4" [6 1 0 mm]) for ALL models. ■ Quick assembl y corners for simple and f ast assembl y .
[ ] Designates Metric Conversions ■ Fea tu re s Honeywell Cont rols ■ A vailable fact or y installed or field accessory ■ Gear Driv en Direct Drive Actua tor ■ F ully Modulating (0- 1 00%) ■.
Illustration ST -A0903-01 INTEGRAL PO WER EXHA UST FOR EC ONOM IZER (FIELD I NST ALLED ONL Y) RXRX -BFF0 4C—3-5 T on [10.6- 1 7 .6 kW] Models 208-230 V , 1 PH, 60 Hz ■ For RXRD-KECM3 E conomiz er .
DUCT AD APTERS (3 TO 5 TON [1 0.6 TO 1 7 .6 kW] MODELS) Rectangular to Round T ransitions (Downflow) RXMC-CB03 – 1 8" [457 mm] Round A vailable in 1 8 inch round to fit all units. Dr ops into a nd secures to RXK G- Series Roofcurbs. For use with Concentric Diffusers.
SID E DISCHARGE CONCENTR IC DI FFUSER RXRN -F A60 (3 to 5 T on [10.6 t o 1 7 .6 kW] Models) For Use With Duct A dapter (RXMC) Model No. A B C D E F G H I J K Duct Size RXRN-F A60 47 5 / 8 " [1210.
FLUSH MOUNT CONCENTRIC D IFFUSER RXRN -F A70 (3 to 5 T on [10.6 t o 1 7 .6 kW] Models) For Use With Duct A dapter (RXMC) DIMENSION AL D A T A ENGI NEERIN G D A T A Model No.
THERMOST A TS — P A CKA GE HE A T PUMPS RECOMMENDED HEA T P UMP THERM OST A T S Units Without Economizer Honeywell T7300A1005 T8611R1166 T874R T841A1209 T874G1881 Q674F1360 Included Q674F1360 Includ.
43 WIRING SCHEMA TICS—RJNA- SERIES.
44 WIRING SCHEMA TICS—RJNA- SERIES.
45 WIRING SCHEMA TICS—RJNA- SERIES.
46 WIRING SCHEMA TICS—RJNA- SERIES.
47 WIRING SCHEMA TICS—RJNA- SERIES.
48 WIRING SCHEMA TICS—RJNA- SERIES.
49 WIRING SCHEMA TICS—RJNA- SERIES.
GENERAL TERMS OF LI MITED W ARR ANT Y Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Pro vincial, and Local codes, regulations, and practices.
Een belangrijk punt na aankoop van elk apparaat Rheem RJNA Series (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Rheem RJNA Series heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Rheem RJNA Series vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Rheem RJNA Series leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Rheem RJNA Series krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Rheem RJNA Series bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Rheem RJNA Series kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Rheem RJNA Series . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.