
User's Guide
890 USE 103 00 Rev. 1.0




The data and illustrations found in this book are not binding. We reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice, and should not be construed as a commitment by Schneider Electric.
Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us by e-mail at techcomm@modicon.com
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of the Publisher, Schneider Electric.
MODSOFT is a registered trademark of Schneider Electric. The following are trademarks of Schneider Electric.
Borland is a trademark of Borland International, Inc.
PROCOMM is a trademark of Datastorm Technologies, Inc.
DIGITAL and DEC are registered trademarks of Digital Equipment Corporation.
IBM and IBM AT are registered trademarks and IBM XT is a trademark of International Business Machines Corporation.
Microsoft and MS-DOS are registered trademarks of Microsoft Corporation.
Copyright 1995, Schneider Electric Printed in U.S.A.




Chapter 3 Configuring the Modbus Models 25
"#+." +10 .0 +!"(/+2"."!&*%&/% ,0". *2".2&"3+#0%"+*#&$1. 0&+*.+ "// "-1&."!-1&,)"*0 +*#&$1. 0&+*%" '(&/0 +! 1/+.0 . )"0"./ *#+.) 0&+* +1 &((""! +.04," ( 2""2& " !!."// +))1*& 0&+* . )"0"./ +.0.&+.&04 &*'&)"+10 +!") ++/0". +! 1/ !!."// , +*#&$1.&*$0%"+! 1/+.0/ +**" 0&*$+3".#+.0%"+*#&$1. 0&+* "00&*$0%"3&0 %"/ +**" 0&*$0%"".)&* ( +1.+*#&$1. 0&+*+)) *!/ %""# 1(0+*#&$1. 0&+* +1.+*#&$1. 0&+* .""*/ *0".&*$+)) *!/*0+ +1. .""*/ .&*0&*$0%"+*#&$1. 0&+* 2&*$0%"+*#&$1. 0&+* +1. .""* +1. .""* 4+10 /&*$0%" .""* +1. *! .""*/ +1.+. .""* 4+10 /&*$0%"+. .""* +1. .""* +1. .""* 4+10 /&*$0%" .""* "00&*$0%"+! 1/(1/ !!."// "00&*$0%"+!"

%"*0+"00%"+!" +30+"00%"+!" +! 1/+.0*!& 0+.+!"/
Chapter 4 Configuring the Programmable Models 57
"#+." +10 .0 +!"(/+2"."!&*%&/% ,0". *2".2&"3+#0%"+*#&$1. 0&+*.+ "// "-1&."!-1&,)"*0 -1&,)"*0#+. .&0&*$0%" ,,(& 0&+*.+$. ) -1&,)"*0+.+3*(+ !&*$0%" ,,(& 0&+*.+$. ) 2".2&"3+#0%""2"(+,)"*0+#03 ." "2"(+,)"*0+#03 ."&("/ %" *#+.) 0&+*&(" "/0 *!")+*/0. 0&+*+1. "&("/ 1(0&0 /'&*$&* +1. ,,(& 0&+* */0 ((&*$0%""2"(+,)"*0+#03 ." "# 1(0 . )"0"./ */0 (( 0&+*0",/ .", .&*$0%" #+.+3*(+ !&*$ "00&*$0%"+*#&$1. 0&+*3&0 %"/ "00&*$0%"+! 1/(1/ !!."// *!& 0+.+!"/1.&*$+3*(+ !&*$ +.) (+3*(+ !+!"/ ..+.+!"/ "00&*$0%"+!" %"*0+"00%"+!" +30+"00%"+!"
Breite: 185 mm

Chapter 5 Installing the BM85 69
-12!++)-'2(% !0$5!0% .3-2)-'2(% (%+&!-%+.3-2%$.$%+1 !#*.3-2%$.$%+1 .--%#2)-'2(%.5%0!"+%1 .--%#2)-'.5%0 .--%#2)-'.5%0 .--%#2)-'2(%%25.0*!-$ %0)!+!"+%1 .--%#2)-'! )-'+%%25.0*!"+% .--%#2)-'3!+%25.0*!"+%1 .--%#2)-'3!+6!"+% -)21.- )-'+%6!"+%%25.0*1 .--%#2)-' %0)!+.02!"+%1 %!$)-'2(%-$)#!2.01 !-$ -$)#!2.01 .$"31!-$ %0)!+.02-$)#!2.01 .$"31+31.02 2!231-$)#!2.01 22!#()-'$%-2)&)#!2).-!"%+1 .$"31+31.02!"%+ %0)!+.02!0!,%2%01!"%+
Appendix A Compatible Devices and Cables 83
.,/!2)"+%%4)#%1!-$!"+%1 ""0%4)!2).-1 !*)-' 3)#*.--%#2).-1 %4)#%1!-$!"+%1&.0.-&)'30)-'.$"31.021 !"+%1&.0.$"31!12%0%4)#%1 !"+%1&.0.$"31 +!4%%4)#%1 .$"31 !"+% )0)-')!'0!,1 .$"31 .021)-.32 .021)-.32

Glossary 89
Index 98
(&2/$8 /(#&$2*1(.*$5$/0-,-#!20*20 (&2/$8 (1' 6.(" * $3("$0 (&2/$8 (1' 6.(" *-#!20$3("$0 (&2/$ 8$00 &$/ +$-21(,& 1'($*# (&2/$ 8-#!20*20-21(,&1- (,&*$-#!20 * 3$
(&2/$ 8-#!20*20-21(,&1-$14-/)$#-#!20 * 3$ (&2/$ 8/(#&$2*1(.*$5$/##/$00-,3$/0(-, (&2/$ 8-21(,&5 +.*$0 (&2/$8 -#!20-/1 6.$0 (&2/$8 -#!20-#$*0-/1-,%(&2/ 1(-, 4(1"'$0
(&2/$8 6.(" * "/$$,-#!20-/10-,%(&2/ 1(-, (&2/$8 6.(" * "/$$,-#!20##/$00 .,1/($0 (&2/$8 6.(" * "/$$, 3$-/,(1( *(7$1'$-,%(&2/ 1(-, (&2/$ 8 -#!20-#$*0-#!20*20##/$00 4(1"'$0 (&2/$ 8 /-&/ ++ !*$-#$*0-,%(&2/ 1(-, 4(1"'$0
(&2/$ 8 /-&/ ++ !*$-#$*0-#!20*20##/$00 4(1"'$0 (&2/$ 8-2,1(,&(+$,0(-,0 '$*% ,$*-2,1-#$*0 (&2/$ 8-2,1(,&(+$,0(-,0 ")-2,1-#$*0 (&2/$8 $ / ,$* (&2/$8 $ / ,$*
(&2/$8 $ / ,$* (&2/$8 6-21-%1'$,#(" 1-/0 (&2/$8-#!20*20-/1 !$* (&2/$ 8 $/( *-/1 / +$1$/0 !$* (&2/$ 8-#!20 !*$ (/(,&( &/ +0
(&2/$ 8 $/( *-/10 (,-21 -#!20 (&2/$ 8 $/( *-/10 (,-21
Breite: 185 mm



!
!
!
Introducing the BM85 Bridge/Multiplexers 890 USE 103 00 1

#)' )' ' # &"(+#& ' "#& ")'(& #"( $$ ( #"' "(+#& " '$&!! #"( &' #'( #!$)(&'"#( &* '(##!!)" (( ) #)(( $)( #" &'#" ")'(& $ "( (')$$#&(')$(# &'' "# * '(((&"'&&(#! #" ('$&'#" " / ") / "(+#& #" )&( #"'&*
'&$$ ( #"' " )(&"'&& "#$''#"( "')$&* '#&- !'''-$ "(+#& * ' " )# #"$&!! #"( &'( (#""((#( "(+#& ( ) &($#&(#"( #"( &( ) #!!)" ( #"'#$( #"(+#& $(&' #""('*& (-$'# #'(#!$)(&$)('(#( "(+#&
) ( $ "(+#& '" # "( ) # #" & )'"#' ' (('( ' "#( !/& ( $$ ( #"' "+ "(+#& !$ #-'#" -( * '&%) &( # $''
& ..) ( $ ,$&(''#)' )'"#" $* '#)&'& $#&('( (-#)"#" )&'$&( -#&'& * ' "-#)&$$ ( #" !# '&* #&' " / #&) / #)' )'"(+#& '"#&')$$#&(# # #"#)''& * '
)&' #+' # &!#(+##)' )'"(+#& ' # " ( ) & )'& * '#!!)" (+ ( ( $$ ( #"( ) ( & ..) ( $ ,&'

PROGRAMMABLE
PROGRAMMABLE
BP85 BRIDGE
CONTROLLER
CONTROLLER
PLUS
MODBUS PLUS NETWORK
TO OTHER NODES
BM85 BRIDGE MULTIPLEXER
HOST DEVICE
BM85 BRIDGE MULTIPLEXER
NETWORK
ADAPTER
HOST COMPUTER
RS232 OR RS485 SERIAL DEVICES
MODBUS MASTER, SLAVE, OR NETWORKED DEVICES
Figure 1 BM85 Bridge/Multiplexers on Modbus Plus
Introducing the BM85 Bridge/Multiplexers 890 USE 103 00 3

$& #)( ,!## &(''#!*!&%!%)!% # 0# &( +#0# & +)#+)% *-&(")-!* ,(! *.& ) (!#'&(*&% ! +(*!&%) (* (!)*!)& * $& #)(
Modbus Plus Network Cable
NW–BM85–000 (Note 1) Panel or Shelf 115/230 Vac Single Modbus ASCII or RTU
NW–BM85C002 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85D008 19 in Rack 125 Vdc or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85E232 (Note 2) Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85D002 19 in Rack 125 Vdc or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85E485 (Note 3) Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
NW–BM85S232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85S485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
& # ) %( '# . &( % -!%)*##*!&%)
&(* '% #) # $& #)* &**&$)+( !) !** -!* ' ) &('# $ %*&% &(!/&%*#) # (" *)( )+''#! &() +(!% * +%!**&* ) # &( &(** !% !**&, (*!#'% #
Introducing the BM85 Bridge/Multiplexers 890 USE 103 00 4

AC/DC Models # , ') &, + ,.**&$ 0$-# *)0 + & )! !- '& ("-#!)+ )* + -$)( !+)' )+ ,$("& *# , *)0 +# & )(( -,-) ,) % -)(-# + +* ( &+).( $("$,-#+)."#-# & # )(- $(, ( &$( !., -# -$, ,,$ & -)-# ., +
&&)!-# , ') &, 1 *--# ( &,))* + - !+)' ( 1- +( & ,).+ )0 + )(( -,-) ,) % -)(-# + +* ( & +).( $("$,-#+)."#-# & # *)0 +,).+ '.,- !., 1- +( &&2-)-#
DC/DC Models # , ') &,)* + - !+)' )+ ,).+ )0 + )(( -, -) - +'$( &,-+$*)(-# + +* ( &"+).( $("- +'$( &$,*+)/$ # *)0 +,).+ '.,- !., 1- +( &&2-)-#
&& ') &,'.,- )(!$".+ $(- +( &&2!)+2).+ **&$ -$)( !)+ 2). ( )(( --# '!)+)* + -$)($(2).+ **&$ -$)(#$,$, ( ,, +2 ., -# ,$(- +( & )(!$".+ -$)(,* $!$ ,#)0 # , +$ &*)+-0$&&)* + -
#') ,-0), -,)!+ +* ( &,0$- # ,( , - ,,$"(,-# ) .,&.,() + ,,# )-# +, - &&)0,2).-) $-# + )(!$".+ -# .($-)+, -$-$(-)$-,')
Configuring the Modbus Port Models )+-# ) .,, +$ &*)+-') &,2). )(!$".+ -# .($-&) &&2 - , +$ &- +'$( & )(( - -))( )!$-,*)+-,
Configuring the Programmable Port Models )+-# *+)"+ '' & ') &,2). + - ( **&$ -$)(*+)"+ ' 1- +( &&2-)-# ( -# ( )0(&) $--)-# .($- +),,-# ) .,&.,( -0)+%
Setting the RUN Mode # (2).# / *+)* +&2 )'*& - 2).+ )(!$".+ -$)()!-# 2). (, -$-$(-)$-,') !)+)* + -$)($(2).+ **&$ -$)(

Modbus Plus Network Cable
NW–BM85E232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85D002 19 in Rack 125 Vdc or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85E485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
NW–BM85S232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85S485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
# !).+, +$ &*)+-,)(-# , ') &, + *+)"+ '' & 2-# ., +-) ,.**)+- .,-)' )+ , +$ & /$ ,
# , ') &,'.,- )0(&) 0$-# ( 1 .- & **&$ -$)( *+)"+ ' +),,-# ) .,&.,( -0)+%# )0(&) $' " )(- $(, &&)!-# $(- +( &)* + -$(" ) ., 2-# $( &. $(" )''.($ -$)(*+)-) )&,!)+-# , +$ &*)+-,# ( ,# %$("*+)-) )& -+ (,& -$)( -0 (*)+-,' ,, " * % "$(" .!! +,* - )(/ +,$)( ( ++)+# ( &$(" #, +$ &*)+-$( $ -)+$,$( $/$ . &&2 *+)"+ '' & -),#)0-# *)+-,,- -.,$(-# **&$ -$)(
# $' " ( )(- $( &&)!-# , +$ &*)+-* + ' - +,!)+ 1 '*& . + - , ( * +$-2 ,!$1 * + ' - +,&- +( -$/ &2-# $' " ).& *+)/$ &) &*+)-) )& ! .&-* + ' - +, ( ' (.$(" ,2,- '!)+-# ., +-)&) &&2 )(!$".+ -# , +$ &*)+-,-#+)."# - +'$( & -)( )!-# *)+-,
( $-$)(-),- ( + , +$ & /$ ,) .,' ,- +)+,& / /$ , ).& -- # - , +$ &*)+-,$!-# ., +4 !$( ) $( &. , ) .,*+)-) ) ( & +
). ( + - -# **&$ -$)(*+)"+ ')( (33)+ )'* -$ & .,$(") $ )( ,)!-0 + / &)*' (--))&,# , + / $& & !+)') $ )(.,-)' + +/$ ( + ,#$** , * + - &2 !+)'-# - $&,)!-# / &)*' (--))&, + *+)/$ $( -$)(
# ()* + - , !.&&24*+)"+ '' *+) ,,)+$(-# ., + **&$ -$)(# .($- (&) &&2' ( " *+) ,, , -$-,, +$ &*)+-,

%% ##$! % &$ &$ $$$$ # #- ' $%%&$#! #% %# ##*& % $#!# ' % ' ! %$ %(# ##% & %! %$ $(% % $!! % !# # #$$ #%#% %%$ $
BM85 BRIDGE MULTIPLEXER 1 2 3 4
NOTE 2
CONTROLLER
DISPLAY
READER BARCODE
NOTE 1
DEVICE MODBUS
SCALE
NOTE 3
Figure 2 BM85 With Typical RS232/485 Devices
,, &% $$% '$ %!! % $ * % $ %# !# # *%&$# ( % % # $$ &$ &$
&$ $%# #$ ''$ &$%&$#- &$ &$!# % #

Developing the Application #-$*$# *') *()$"/%'$ '""!"$!(-$*"*() +!$%) #) ' %%! ) $#( !#) #$,#!$ ) #)$ ) ( #!*() $%') # $ $'"(( #! # * '!!$) $#%'$)$$!$#+'( $##-$*'(' !%$')%'")'(
$*#')) %%! ) $#%'$ '"$## .. $'$"%) ! *( # $ $#($ ),'+!$%"#))$$!() )'( %%(%')!- '$") ('&* ') *($ $'!# .. +!$%"#) #+ '$#"#), "*()(*%%! -) *('
# ) $#)$ )( #)'#!$# *') $#) ($*(!*(#$ '(("*()(( # ( ($# #()$ ','(, ) ($# ) ''%#!
Downloading the Application $"% !%%! ) $##) #$,#!$)$) *( # *) ! )-(*%%! , ) ) $ $#)$$!( $,#!$ $()#) ("$"%*)') ),(*( $'+!$% # ) %%! ) $#$' (%')$"%*)'
$'$,#!$ # ) $()"*()$#) #$ $# $*(!*( #),$' %)' $'# $"%) ! $()$'$ $# %)' $'# '$ ##!$"%) ! $() #),$' $##) $# (+ !! $') #) + # )-$ ) $()#$-$* #$,#!$#* -$*'%%! ) $#!$!!-) ', (-$*# $,#!$ ))$) ) )( #()!!) $#( )
#) *('%%! ) $# (#()$' #) ), !! ') #-) )'%$,' ('"$+ ) %'")'(' $'') $') #)# #()!!) $#( )) *# )#)'#(%$'))$ ) ( )# #()!!) ', ) $*)'$# *') $#

'$-.$)"*!!$' --/++'$ $).# *!.1 , 0 '*+( ).&$.$- +,*0$ $) .$*) # 0 '*+( )..**'-$) '/
)* % .'$ , ,3*! /.$'$.3,*/.$) -$) '/ $)"!/) .$*)-!*, ( ) "$)"(/'.$+' . -&-$).# ++'$ .$*)
# ,!$' *). $)$)"!/) .$*)+,*.*.3+ -
*(+$' (*)-., .$*)+,*", (1$.#-*/, * -#*1$)" 2 (+' -*!.# /- *!!/) .$*)-$) .3+$ ' ++'$ .$*)
-./.$'$.$ -$) '/ $)"-*/, * .# . 2 , $- # , 1 ,
# 0 '*+( )..**'&$.$--/++'$ *) *(+ .$ ' $-&- , ,$)"$)!*,( .$*)$-"$0 ) '*1
Modicon Customer Service 1–800–468–5342 (North America) 1–508–975–5001 (International)
SR–BM85–S00 BM85 Software Development Kit (Note 1)
SR–BM85–S0R BM85 Software Support Renewal (Note 2)
*(+$' ) '$)&3*/, ++'$ .$*)
*1)'* 3*/, ++'$ .$*).*.#
# &$.$) '/ - 3-*! -*!.1 , 0 '*+( ).. #)$ ' -/++*,.- ,0$ +,*0$ 3* $ *)/-.*( , ,0$ # -/++*,. , ) 1 ' 2. ) - .# -*!.1 , 0 '*+( ). . #)$ '-/++*,.- ,0$ 3*) .# $)$.$ '5 3+ ,$*
Contact Telephone · Part Number Description

Modbus Plus Network Cable
NW–BM85–000 Panel or Shelf 115/230 Vac Single Modbus ASCII or RTU
NW–BM85C002 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85D008 19 in Rack 125 Vdc or 24 Vdc Single or Dual Modbus ASCII or RTU
#)&'& $#&('#"( '!# '')$$#&( # #" #)''& * ' '!# '$* ( #"*&' #"(+" #)' &'''"( &%) &&''#&!('#&)( " !'' '(# #( & #)'$#&('#&(# #)' )'"#'
#)!)'(#" )&( '!# '# "#""( " ( !(# #)' )'#&(#",* ' ",#)&$$ ( #"#)"#( ', #""( " '& (&! " (##" $#&('(( " '+ ( (# #+ # '()$#( $&!(&'"$$ , " $#+&(#( '$ ,'!")'#"( (&! " #&'(( " )$( #" )&( #"
#&( (,$ #)' !'(&' "(!'(&' *#&"(+#&
&#(##
#!!)" ( #"$&!(&')&('(#$ ('$& (,!#
&''!$$ " #&#"*&' #"(+" #)'&'''" #)' )'&#)( "
" ( #"(#( '& $#&(#" )&( #"'( ' #)' )' "#&''!)'('' " ' '#" "'(# &+& '+ ( '#"( &&$"
"( #" )&( #" '"#!$ (( "(&" $&!(&' + &( ",( (&$#+& '&!#* ( $&!(&' &&(( )" ("(&"'$#&((#( "'( ( #"' (" "'( ( &+ ( #)(" )&( #"

BM85 BRIDGE MULTIPLEXER 1 2 3 4
CONTROLLER
NOTE 1
MASTER
NOTE 2
SLAVE
NETWORK
MASTER
NETWORK
NETWORK
SLAVE
SLAVE
NOTE 4
NOTE 3
NETWORK
NETWORK
SLAVE
SLAVE
Figure 3 BM85 With Typical Modbus Devices
! ! & % % ! " !
$ ! """ " # " ! !
$ ! # # ! "" %" " " ! !
$ ! # # " "" ! ! "" %

Description Name BM85 Modbus Plus Bridge/Multiplexer
Part Number NW–BM85–000, NW–BM85C002 NW–BM85E232, NW–BM85S232 NW–BM85E485, NW–BM85S485
Mounting Method Horizontal Surface Platform or shelf, with included mounting brackets
Vertical Surface Panel, with included mounting brackets
Height 2.59 in (66 mm)
Width 11.50 in (292 mm), unit only
14.08 in (358 mm), with mounting brackets
Depth 8.30 in (211 mm)
Weight 5.5 lbs (2.5 kg) net
6.5 lbs (3.0 kg) shipping
AC Power (All AC/DC Models)
Requirements 115/230 Vac +15%. 47 ... 63 Hz 10 W
Access Rear panel power connector with ON/OFF switch
Fuse 1.0 A, 3 AG SB, internal
DC Power (not available on NW–BM85–000)
Requirements 24 Vdc +15%, 10 W
Access Rear panel power connector
Fuse 1.0 A external, customer supplied
Environmental Temperature 0 ... 60 degrees C, operating
–40 ... +80 degrees C, storage
Humidity 0 ... 95%, non–condensing
Altitude 10,000 ft (3 km), maximum
MIL STD 461B CS03
Network Connections NW–BM85–000 Single-cable network only
Introducing the BM85 Bridge/Multiplexers 890 USE 103 00 12

Serial Connections All Models Four DB9S
Serial Parameters NW–BM85–000, NW–BM85C002
Modbus protocol, ASCII/RTU 300–19200 baud odd/even/no parity 1 or 2 stop bits
User defined protocol, RS232 50–19200 baud
User defined protocol, RS485 50–19200 baud
Modicon Customer Service 1–800–468–5342 (North America) 1–508–975–5001 (International)
SR–BM85–S00 BM85 Software Development Kit, 3.5 in and 5.25 in HD disks, Documentation, 90 day Technical Support
SR–BM85–S0R BM85 Software Technical Support Renewal
Development System IBM PC/AT Compatible, 486 or higher recommended, to support Development Environment
Development Environment Borland C/C++ Compiler version 3.1 or higher, BM85 applications use Large model
Download System IBM PC/AT Compatible host with SA85 Adapter, or IBM Micro Channel host with SM85 Adapter 486 or higher recommended 4 MB RAM minimum
Contact Telephone · Part Number Description

Description Name BM85 Modbus Plus Bridge/Multiplexer
Part Number NW–BM85D002, NW–BM85D008
Mounting Method Vertical Standard 19 in Rack
Height 3.47 in (88 mm)
Width 19.00 in (483 mm), mounting panel
18.26 in (464 mm), hole centers
Depth 9.15 in (232 mm)
Weight 5.5 lbs (2.5 kg) net
6.5 lbs (3.0 kg) shipping
Power Requirements 105 to 140 Vdc, or 24 Vdc +15%
Access Rear panel screw terminals
Input Current 0.41 A at 125 V dc
Inrush Current 6 A typical at 125 V dc
Ground Leakage 1 mA at 140 V dc
Fuse External, customer supplied
Environmental Temperature 0 ... 60 degrees C, operating
–40 ... +80 degrees C, storage
Humidity 0 ... 95%, non–condensing
Altitude 10,000 ft (3 km), maximum
27 ... 500 mHz, 10 V/m IEC 801–3, level 3 IEEE/ANSI C37.90.2, 1987
Surge Withstand, Fast Transient
± 2 kV (1 kV on I/O), V3300 generator into 50 ohms. Corresponds to ± 4 kV (2 kV on I/O) into open circuit. IEC 801–4, level 3 IEEE/ANSI C37.90.1 2.3, 1989
Surge Transients 2 kV IEC 801–5, level 3
Electrostatic Discharge 8 kV, ten discharges IEC 801–2, level 3
Surge Withstand, Oscillatory Wave
2.5 kV IEEE 472 IEEE/ANSI C37.90.1 2.2, 1989
Physical Characteristics · EMI, Radiated Susceptibility

Network Connections All Models Single- or dual-cable network
Serial Connections All Models Four DB9S
Serial Parameters NW–BM85D008 Modbus ASCII/RTU protocol 300–19200 baud odd/even/no parity 1 or 2 stop bits
NW–BM85D002 User defined protocol, RS232 50–19200 baud
Modicon Customer Service 1–800–468–5342 (North America) 1–508–975–5001 (International)
SR–BM85–S00 BM85 Software Development Kit, 3.5 in and 5.25 in HD disks, Documentation, 90 day Technical Support
SR–BM85–S0R BM85 Software Technical Support Renewal
Development System IBM PC/AT Compatible, 486 or higher recommended, to support Development Environment
Development Environment Borland C/C++ Compiler version 3.1 or higher, BM85 applications use Large model
Download System IBM PC/AT Compatible host with SA85 Adapter, or IBM Micro Channel host with SM85 Adapter 486 or higher recommended 4 MB RAM minimum
Contact Telephone · Part Number Description



Device Addressing and Message Routing 890 USE 103 00 17

& ! "(& (&!'*"% !)(#'" %&& !" ) &* ') ) !(! $(%&&"'*!! ( ' # !'*"% &! " !'%"(% (&) &) & %&&"'%%"&&% (&) &, , !%"(' ! #'&" ),'&* ','%#%&!' !!%&&"!'!+' !'*"% &%"(' ! '" "*&!"& !"'%!'*"% &'" %&&(#'""(%!'*"% &*,%" '"% !' !!"
%"(' !#' & !'"(& (& &&% & ' & &!'%" '"% !' !!"
MESSAGE FRAME
ROUTING
PATH
START END
EXAMPLE:
ROUTING ADDRESS 1
ROUTING ADDRESS 1 = 25 ROUTING ADDRESS 2 = 20 ROUTING ADDRESS 3 = 12 ROUTING ADDRESSES 4, 5 = 0 (NO FURTHER ROUTING)
ROUTING ADDRESS 3
ROUTING ADDRESS 4
ROUTING ADDRESS 5
Figure 4 Message Frame Routing Path Field
(% &!+ # " &&%"(' !'"#%"% "!'%" % '%"('%!'*"% &''% " !,% (&!") & &&* %&'%"(''"!" % (&"!' " !'*"% '!""%*%&' &&"!'"% (&' %&&"!'&"!!'*"% &"!% (&"%*%&' &&'" '& ! &' !' "!!"%&&"!'' %!'*"% -%""!'!'&",'& ! ,!"(%'% &&%"(' !
"%#%"% "!'%" %&' &'!"!-%",' !' && %"(' ! &'!'*"% !"%&&"'"!'%" %'"

!$!%&% &)!$ "&$%&+&! !) &"&$% &)!$ !$%%%" %&% ' $ &!) & %% %%% '%#' &+&%$ !& +&"&$ $( !$'%&! '%&!&"" & ! !$* " !$ %%!' &%!$%&&'% !$ & !
Routing to Serial Ports on BM85 Programmable Models!$&"$!$ ! %&'%$"" & ! %&!$ & %&$%% &) !'% '% &%$ "!$&%
Routing to a Single Slave Device on BM85 Modbus Models!$% % (( &!'%"!$&&)!+&%$'%&!$%% &( *&&! %& ! ,$!+&$%%%& ! %& ! ,$!+&%" %&!'%"!$& &$!$%" %&% % ((
BP85 ADDRESS
BM85 ADDRESS
BM85 PORT (1 ... 4)
ZERO ZERO
(1 ... 64)
(1 ... 64)
Figure 5 Modbus Plus Routing to Single Modbus Slave
Routing to a Networked Slave Device on BM85 Modbus Models!$% (( ! !'% &)!$ &!'%"!$&&$+&% $'%&!$%%&( & $+&$! & %& ! ,$! +& $%%% & ! *&&! %& ! ,$! +&%" %&!'%"!$& %& ! ,$!+&%" % &!'%$%%!&% ((
BP85 ADDRESS
BM85 ADDRESS
BM85 PORT (1 ... 4)
ZERO SLAVE ADDRESS
(1 ... 64)
(1 ... 64)
(1 ... 247)
Figure 6 Modbus Plus Routing to Networked Modbus Slave

Programmable Port Models $&( %&$ &""!"$!'( )'&%%! ( $#'($& #( #'( &'' # $#*#( $#'($)'(+#( '& !%$&(' #$)'!)' %%! ( $#%&$ &"")'( #( &$)( # (+#'& !%$&(''+!!'( %( '($$)'!)'#$'
Modbus Port Models $&( $)'%$&("$!'&''$#*&' $#(+#$)'# $)'!)'&''' '%&$* #(!!-''& !$+ ,"%!'&' $+# #( $#
#( & *'"'' ($)'%$&(( $)' &'' '$"%&($# #(!&''"% $&( (%$&( $) #( "%(!)& # -$)& $# )&( $#(# $! )%($ $)'&''' %$ #( # ($ *-(&$)( # %(
#( (!( *&$)( # %( -('& %%! ($( "'' ( &'(-( ' #( ( "'' '&$)($)($#$)'!)' ( &'(-( '.&$( "'' $'($$)'%$&( '% #-((+$ ( (%$&( '' # !'!** ( &" # # ( &-('&.&$' ( %$&( '#(+$& $ '!** '-(( &'% '( '!*&''
ATTACH ADDRESS
70 71 74 75 RESERVED NOTE:
ALL ADDRESSES 65 ... 79 ARE RESERVED AT ANY PORT CONFIGURED IN THE ‘SILENT MASTER’ MODE.
ADDRESS
RESERVED
DIRECT ATTACH ADDRESS
RESERVED
Figure 7 Bridge Multiplexer Address Conversion

#0%" !!."//&/&*0%". *$" &." 000 %!!."//0%" )"// $"&/.+10"!0+0%"/," & *+!" !!."// +*0%"(+ ( +! 1/(1/*"03+.'
#0%" !!."//&/&*0%". *$" 00 %!!."//0%" )"// $"&/.+10"!0+ /&*$("!"2& " 0+*"+#0%"(+ (+! 1/,+.0/ !!."//"/ /," ,+.0/ ."/," 0&2"(5
#0%" !!."//&/&*0%". *$" ),(& &000 %!!."//&03&(( "!&2&!"! 53&0%&*0%" %"-1+0&"*0 *!.") &*!".+#0%" !&2&/&+*3&(( " +)"0%"#&./003+ 50"/+#0%"#&2" 50".+10&*$, 0% %&/)"0%+! ((+3/03+("2"(/+#+! 1/(1/ !!."//&*$0%"-1+0&"*0 50"/," &"/ .&!$"(1/ !!."//+*0%"(+ (*"03+.' *!0%" .") &*!". 50"/," &"/0%"!"/0&* 0&+**+!"+*0%"/" +*!*"03+.' %"#&* (0%."" 50"/&*0%".+10&*$, 0%3&(( (3 5/ "6".+/
Silent Master Port Addressing +! 1/,+.0 * " +*#&$1."! / &("*0 /0".*"03+.',+.0* 0%&/ +*#&$1. 0&+*+*"+! 1/) /0".!"2& " *!+*"+.)+."/( 2" !"2& "/ * " +**" 0"!0+0%",+.0%") /0".!"2& " * !!."//&0/ +3**"03+.'//( 2"!"2& "/!&." 0(50 * (/+ !!."//!"2& "/ 0+0%". ,+.0/+*0%"/ )" +.!"2& "/ .+//+! 1/(1/
," & ( +*/&!". 0&+*/ ."*""!"!#+. !!."//&*$&*0%&/ +*#&$1. 0&+* %"&*0"*0&/0+ 2+&! !!."// +*#(& 0/ "03""*/( 2" !!."//"/ 00%" (+ (,+.0 *!+0%". !!."//"/0% 0) 5"4&/0"(/"3%"."
%"/( 2"!"2& "/+*0%"&("*0 /0".,+.0)1/0% 2"1*&-1" !!."//"/ %"5)1/0*+0 "0%"/ )" / *+!" !!."// +*0%" / (+ (+! 1/(1/*"03+.'%"5)1/0 (/+*+0"4&/0 /"*0.&"/&*0%" !!."//) ,,&*$0 ("/0+."!3&0%&*0%" %"+! 1/ !!."//"/ &*0%") /0"./-1".&"/0+0%"/( 2"!"2& "/)1/0*+0) , "5+*!0%" &("*0 /0".,+.0*"&0%".0+ *5.+10&*$+*+! 1/(1/*+.0+ *+0%".,+.0+*0%"
%"*0%",+.0&/ +*#&$1."! / /0".,+.0 !!."//"/ *! ."."/".2"!!!."//"/ ." 2 &( ("#+.1/"
%".&!$"1(0&,("4".3&((."/,+*!3&0% +! 1/"4 ",0&+*."/,+*/" 0+ *5)"// $" !!."//"!0+ ."/".2"! !!."//
Device Addressing and Message Routing 890 USE 103 00 21

MODBUS PLUS NETWORK (UP TO 64 NODES)
(NOTE 1)
M
= MODEM
CPU B CPU A BM85 BRIDGE MULTIPLEXER 1 2 3 4
M
MASTER
HOT STANDBY CONFIGURATION
A
SLAVE
BP85 BRIDGE
A
PLUS
NETWORK
SLAVE
M
NETWORK
SLAVE
M
MODBUS PLUS NETWORK (UP TO 64 NODES)
CPU C BM85 BRIDGE MULTIPLEXER 1 2 3 4
ADAPTER
BRIDGE
M
TASKS: 1
MODE
MASTER
B
SLAVE
MASTER
B
NETWORK
SLAVE
M
NOTES:
NETWORK
M
Figure 8 Routing Examples

% "! !$ ! ##

CPU A (Primary) Slave A 5 2 0 0 0
CPU C SA85 (Task 2) 30 2 0 0 0
! " ! !& !!! # " # " ! ! "!

Master A CPU A (Primary) 8 Attach Direct 8 0
CPU C 252 Attach Implicit 252/10 = 25 2 0 0 0
50 50 Attach Mapped 0 3 50 0 0
200 200 Attach Mapped 25 4 3 200 0
Master B CPU C 2 Attach Direct 2 0
CPU A (Primary) 248 Attach Implicit 248/10 = 24 8 0 0 0
200 200 Attach Mapped 0 3 200 0 0
50 100 Attach Mapped 24 5 3 50 0
Master C CPU A (Primary) 248 Attach Implicit 248/10 = 24 8 0 0 0
CPU B (Standby) 71 Attach Mapped 24 40
Slave A 72 Attach Mapped 24 5 2 0 0
Slave B 73 Attach Mapped 4 2 0 0 0
150 74 Attach Mapped 4 3 150 0 0



!%"!% $
%"$ #$
%# "$ " $"#
%" $ %# "$#
%" %"$ #
%" %"$ " #
%""
%" " #
%""
$$ $ %# %#"##
$$ $
%# "$ $ " #
Configuring the Modbus Models 890 USE 103 00 25

! " $ !" # " !! " % !
Modbus Plus Network Cable
NW–BM85–000 Panel or Shelf 115/230 Vac Single Modbus ASCII or RTU
NW–BM85C002 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85D008 19 in Rack 125 Vdc or 24 Vdc Single or Dual Modbus ASCII or RTU
# !"!"# " # " " ! """& #%#! & # " # " " ! '$ " &""!" !" " # " !$ % " % ! $
##!"!"" " # " !#! ! " %"" #" "" " "! ! "$" "" " #! #! "% !%"! $ " " "# "" # "# "! & !"""!!"& # # "" # ! " # " " !" "# """!!" " " ! "" # # "" "!" !""
##!"! !"" #! #! !! " !" !%"! "
" !
!

) )(!$"/, .# ) /-*),.* , ' . ,-3)/1$&&( $.# ,)!.# !)&&)1$(" 0$ -
), +/$0 & (.. ,'$( &1$.# )'* .$ & - ,$ & &
),), +/$0 & (. )'*/. ,*,) / .,/(($(" . ,'$( & '/& .$)(*,)", '-/ # - 1$.# )'* .$ & - ,$ & &
&$-.$(")! )'* .$ & . ,'$( &- ( & -$-*,)0$ $( ** ( $2
)' . ,'$( & '/& .$)(*,)", '--/ # - &&)1 3)/.)-.), .# % 3-.,)% -3)//- $(.) - ,$*.!$& )(3)/, $-%#$- &&)1-3)/.) /*&$ . 3)/,!/./, )(!$"/, .$)(-!,)'.# $-%1$.#)/. # 0$(".)% 3$(.# * , ' . ,- ! ,.).# ) /' (.-!),3)/, '/& .$)(*,)", '!),!/,.# , . $&-
!3)/# 0 *,$(.$(". ,'$( &), *,$(. , )(( . .)3)/, '/& .), 3)/ (*,$(. # , )*3, ), )!3)/, )(!$"/, .$)(#$-1$&& # &*!/&$( ) /' (.$("3)/, )(!$"/, .$)(3*$ &&33)/ (/- 3)/,. ,'$( &-,$(. , (), +/$0 & (.% 3.)*,$(..# # , )*3

$* +(% (&*#$ ) $#( $'$# *' # .$*' () ( )"((.$*' ! ()
')$ %%# - $'! () # $ $"%) !)'" #!+ (#!(!))'" #!#! ) ).$*, !!*( $') $# *') $#
')$) $# )'" #) %'")'(.$*,#))$ *( $' $*(%$')
!+ + '((
$""*# ) $#'")'(
$')' $' ).
$" $$()'
$*(!*( '((!
*'#$ !!%$,')$) ')$) $#
$##).$*')'" #!)$) %$').$*, !!*( $'$# *') $# )').$*')'" #!##."*!) $#%'$ '".$*'*( #
)) (, ) ()$!!$,) $# *') $##%$,'*%) () $# *') $#('#(# .$')$$# *') *# )
')$) $# )) ''%#!'(((, ) ()$ )(#$'(($#.$*'$*(!*(#),$'
')$) $# *'#$ !!%$,')$) ) )(''%#!(, ) )$) "$ $##)) *# ))$) $*(!*(#),$' #)$ ) $*(+ () )( #()!!) $#( ) $''%%!. # %$,'

Port Type (see Section 3.4.2) .$"31!12%0 .$"31+!4% .$"31%25.0* .$"31 )+%-2!12%0%25.0*
Slave Device Address (see Section 3.4.3)
Communication Parameters (see Section 3.4.4) !3$!2% 2./)21.0 !0)27.$%4%-$$.0.-% .,,3-)#!2).-.$%.0
.2%.$%+1 !-$ $.-.2(!4%! 2./)211%22)-' (%1%,.$%+1$%&!3+22. $!2!")215)2(2./)2
Port Priority (see Section 3.4.5)
Link Timeout (see Section 3.4.6) ,3+2)/+%1.&,)++)1%#.-$1
Modem Booster (see Section 3.4.7) %1.0.
Configuring the Modbus Models 890 USE 103 00 29

Master " ! #
Slave " !! #
Network " !! #
Silent Master Network " ! !! #
BM85 BRIDGE MULTIPLEXER
CONTROLLER
1 2 3 4
NETWORK
SLAVE
MASTER
NETWORK
NETWORK
SLAVE
SLAVE
NETWORK
NETWORK
SLAVE
SLAVE
Figure 9 BM85 Modbus Port Types
984–785

%2'$.-02(12-!$"-,%(&30$# 1 -#!311(,&*$1* 4$#$4("$.-02 1* 4$#$4("$ ##0$11+312!$ 11(&,$#2-2'$.-02(,2'$0 ,&$ #$"(+ *
'$ ##0$11(1. 02-%2'$"-,%(&30 2(-,-% .-022-5'("' 1(,&*$1* 4$ #$4("$(1 22 "'$# '(1 ##0$11(1,-2 ..*(" !*$2--#!31+ 12$0 #$4("$1 12'$7#-,-231$ #$4("$ ##0$112(1 *1-,-2 ..*(" !*$2- -#!31,$25-0)$##$4("$1 1+3*2(.*$#$4("$1" ,$6(12-,2'$.-02
-3+3121$2$ "'.-021. 0 +$2$012-"-++3,(" 2$5(2'2'$-#!31 #$4("$-0#$4("$1 22 "'$#2-2'$.-02$%$02-2'$#-"3+$,21%-07-30 #$4("$12-#$2$0+(,$2'$(0. 0 +$2$01-#("-,-#!31#$4("$1 &$,$0 **713..-022'$%-**-5(,&. 0 +$2$01
"' 0 "2$0+-#$ ! 3#-0# 2 !(21 -0 12-. !(21$4$,-##,-. 0(27
-#$*1 ,# #-,-2' 4$ 2-.(21 1$22(,& '$1$+-#$*1#$% 3*22-# 2 !(215(2' 2-.(2
The Purpose of the Parameter '$ 1$04("$12'$%-30-#!31.-021(, 1$/3$,"$2' 27-3" , $12 !*(1'#30(,&"-,%(&30 2(-,!71$22(,&2'$-020(-0(27. 0 +$2$0
Setting the Parameter -31$22'$1$/3$,"$!7 11(&,(,& .0(-0(272-$ "'.-02(,2'$0 ,&$ 5(2' !$(,&2'$'(&'$12.0(-0(27 '$.-022' 2(1 11(&,$# .0(-0(27 5(**!$2'$%(012.-022' 2(11$04("$#-,.-5$03.

The Purpose of the Parameter % !&% $% ) & % *!&( !(!#$ '' %! #$"! %!! $$&%% !&$$ '"!#% *! "" % ! %% !&%' & $)$ '' !( ##!# !( #% *%"#!# & % ! % % %! %! %'
%% !&%' & $%!!$!#%$ !(#' $ * !%'% %! #$"! !# *%!% #! $#$& % ""# %##!#$%% ' %' & $%!! ! ' $%!#$"! *! "" % ! ( '%!( %& % %% !&%!$!# % ' ! % ! !#&$ %"!#%
' &$!& $%%! %$ !($%' %%"!#%( %!&% )$$ ' *' &$!& ! !%%$& !% ! !(
$ '' "#!$$ % !#) " ! %#! #$ %
Setting the Parameter!&$%"!#%$% !&%"# %#$' & %# % !&%' "#$ %$ & % " $! $! $
Configuring the Modbus Models 890 USE 103 00 32

Timeout Examples #.# .#/,*##3 *-)#/$,./#00'+%0)'+(0'*#,102 )1# !&'/ /#",+ ," 1/*#// %#0. +/ !0',+,$ 40#/0,0-,.0"#2'!# +" 40#/$.,*0"#2'!#
. *#0#./ 1"/0 .0" 0 +,- .'04/0,- #.' )!,**1+'! 0',+0'*#5 '0/ */!& . !0#. */$,. 40#/ *,"#/#+"/,+#!& . !0#.-#. 40# ) 2#!,+0.,))#./! +0'*#*/ 0'*# */ ,0 )0'*# 55 5555 */ /# )'+(0'*#,102 )1#,$*/
. *#0#./ 1"/0 .0" 0 - .'04/0,- #.' )!,**1+'! 0',+0'*#5 '0/ */!& . !0#. */535 */$,. 40#/ !& ./ 40#$,. ) 2#!,+0.,))#./! +0'*#*/ 0'*# */ ,0 )0'*# 55 5555 */ /# )'+(0'*#,102 )1#,$ */
. *#0#./ 1"/0 .0" 0 - .'04 /0,- #.' )!,**1+'! 0',+0'*# 5 '0/ */!& . !0#. /#!,+"/535 /$,. 40#/ !& ./ 40#$,. ) 2#!,+0.,))#./! +0'*#*/ 0'*# */ ,0 )0'*# /55 /555*/55 5*/ / /# )'+(0'*#,102 )1#,$ */,. /

How the Parameter Applies to the BM85 #! ##'(&$$ '(# #)'$#&('( (+ #" )&'(+#& $#&('#)+ "( ' "#&!( #"#&"-$#&( -#)+ )' " ' #)'(+#& $#&(
$&!('"#($$ -(#$#&(( ( ' " #" )&' ' " '(& ** $#&(#)"-$''( "#&!( #" #+#&"-$#&(-#)+ )' " '' " '(& *$#&(
The Purpose of the Parameter #! ##'(&$&!(&(&! "' #+( + " #)'#!!"'(#"(+#& ' ** '( #)'$#&(
"( & *'#!!"( ( '&''(#' ** ( #)'"(+#& $#&(&'$#"' ',$(!( ' ** +#!( #'&* #& " " ( &'$#"' "-( )"( #"# "( #!!" '')-( !'(& (+# "'# #!!"'&
( ( '(-$ ##!!"( ' ** + '"&'$#"'(& ( #!$ ('( ( #"&%)'( "( #!!" !'(& * + ('#&( &'$#"'"( ( !!"'#" ( #)'"(+#& ""#($'')"( ( ' *'( #" '"#!$ (" ('&'$#"'& *( &(&"'( #"' "("#&( $#&(!)'(&! "$" " )"( ( (( ! #!.#!!"'') ''(&("'& #!!"'! # #"$ &!! " $" (#' *#"( "( #)'"(+#& "( & ( * - #" ( !#&$'' " " ( #"( & "( &" #'#"'(#! ")('
( ( '(-$# #!!"( ' *+ '"" "#+ !"(#& $(#( #!!""!)'($# (&-( !'(&* (# (&! " ( &%)'(( #" '"#!$ ( #!!" "#+ !"(&'( #)'"(+#& #& $'' " !'' '(##( &* '#"( $#&( + $# ( ' ** $& # -(#(&! " ( #!!" ( #" '"#!$ ( (+ ( "'"( " &'$#"'(# ( #& "( " *
#! ##'(&$&!(& #+'-#)(#'$ -+ #( (+# !( #'+ )'(( #)'$#&(

Setting the Parameter )/ (- & .)), -!),.# ) '))-. ,* , ' . , . (3 - ,$ &*),.# * , ' . ,1$& 0 .# !)&&)1$(" !! .
!3)/- & .)!),.#$-* , ' . ,$( )'$(" )'' ( -1$.#!/( .$)( ) ), , * -- $, .&3.).# -& 0 0$ ..# *),.!.# )'' ( $-!/( .$)( ) .# -& 0 , -*)(- 1$&& , ./,( .).# ),$"$( .),)!.# ) /- )'' ( !. ,.# -& 0 # - )'*& . .# , +/ -. .$)(),1# ($., ./,(- ( 2 *.$)(, -*)(- $( $ .$(" .# .$. ((). )'*& . .# .$)(
& .$(" - /- -.# - )( .3* )!, -*)(- !/( .$)( ) .) /- !.# )'' ( -* $!$ -!/( .$)( ) .# 1$&& * ,!),' )(0 ,-$)(.)!/( .$)( ) !), - ( $(".# )'' ( .) .# -& 0 0$ # 1$&&.# ( /.)' .$ &&3# ( & .# *)&&$(")! .# -& 0 0$ /(.$&.# )'' ( .$)($- )'*& . .1$&&, ./,( .# !$( &, -*)(- .).# ),$"$( .),)!.# )'' ( # *)&&$("*,) -- $-# ( & 3.# ., (-* , (.&3.).# ),$"$( .),
Modem Booster Example *,)", ''$("* ( & )(( . .) ) /-&/-( .1),% )(.,)&& , ( -- -& 0 )(.,)&& ,.# .$-* ,.)! ) /-( .1),% . *),.# * ( & (, '). &3$(. ,,)" . *,)", ' ( -. ,..# -& 0 )(.,)&& ,
!.# ) '))-. ,* , ' . ,$-- ..# ($--/ )'' ( 1$.#!/( .$)( ) # )(0 ,.-.# !/( .$)( ) ( - ( - .# )(0 ,. )'' ( .).# -& 0 # .# (# ( & -*)&&$(")! .# -& 0 , ./,($(" , -*)(- .).# 1# (.# -& 0 0$ - .$)($- )'*& .
).# ),$"$( .$(" 0$ .# , -*)(- ** ,- -.# )( !,)'.# -& 0 !),!/( .$)( ) /,$(".#$-.$' #)1 0 ,(),' &( .1),% ., (- .$)(- ( )(.$(/ .1 ().# , 0$ -$(.# /- , **&$ .$)( ( .# ).# ,-& 0 0$ -)(.# *),.-) /-( .1),%
# ) '))-. ,1$&&(). !/( .$)(1$.# )(.,)&& ,-.# . , $( ') /( .$)( ) $-()., )"($4 3.#)- )(.,)&& ,-$(.# .') )/-#)/& - & ..# ) '))-. ,))*.$)(!), *),..# .1$& 0 )(.,)&& ,- )(( . .).# .*),.-) /-( .1),%

# $) $( %*' $) '$"%*(' ((&)" ( %' '%*) $ ) %*(# (( (' + ) )( %*'%*(&%')( &%') ()" ) )$ %"*&)% $)' () ).%*(& .*' $ %$ *') %$
) "%) %$ $) )" ), .%*,$))%&" ) $)'.
+ .) '%*) $ &)
)" $)'.(& ( %,.%*, "",$)%*(' ((' + )) %*(&%'))% %$+ ') $)% + .) '%*) $ &) )%) () $) %$ + $.%*'&&" ) %$%*) $ $ # )% %*("*($% %$) "%"$ ),%'!%'%$' #%) $ ),%'! (( ($"(% '%*) )% + %$$%) '&%')% )
$%*(# (( (%' $) '%# + )%$ % )(%*( &%')() ( ' () %*(' ((&)" %') )&%'))% $#) ), $) # (( (%*(' (($%*( ' ((()%' $) )" ) %$()! $ #) ( %*$%' #) ($%) %*$' (' "%,$%$) %""%, $ & (
If a Match is Found #) ( %*$) + .) (% #&& '%*) $ '%#) )" $)'., "" &&" )%) # (( $ ), "" ( $)%*)*( $ ) ) '%*) $ ' ' + -#&" (% %,) %*(' ((&)" $ *( )% + "%&'%*) $ &) ( %'%*(# (( (
Table Location Modbus Address Five–Byte Routing Path
01 47 8 0
02 182 20 14 0 0 0
03 27 20 22 5 0 0
04 33 0 3 0 0 0
05 125 0 4 99 0 0
($ -#&" % '%*) $ )%$% %$) "%" %*("*($ ),%'! ) %*(# (( %$) $() () $) %$' (( #) ( %*$ $) )" , ""&&".) '%*) $ &) )%) # (( # (( () *&%$.) &&" ) %$&'% '# $) + ) $% ' ((

&"+!$ #%#(' " ' %#( % (&'# $%# %!! #"'%# %'"#%&"""'*#% " " !' #%#(&%&& ' $$ &' %#(' " $' '#' !&& '* &"''#"# #"' (%%"'#(& (&"'*#% % (&'* %#('' %#( ' % '#"##"' ""'*#%
& #*& #*' ',$#) '' &' "' #"" '%! "' %#(' " #!&& " " !' #%#(& %&& ' $$ &' %#(' " $' '#' !&& !&& &&"''#"##"' (%%"'"'*#% % (& !&& &%#('' %#( ' % '#"# #"' "+'"'*#% ',$#) '"#'%! "& #*(%' %%#(' " &$$ "# &"#' %% (& ' !&& &%#(''#"##"' %"'*#% ."# & " #% '*#% $'%' !&& &$',' $'%"$#&''#$$ ' #"'& %("" " "' $'%
& #*&%#(' " '#& " & )) #""#' %$#%'# ' &! " " !' #%#(&%&&' * $$ ,' %#(' " $' '#' !&& -%# "' %&','&$ & "'%" %#(' " '#"#' %#(& $#%' ",'&$ &$#%'#%'!(&' )#" , & " & )) #""'&' %! " " ,'&%-%#&
& #*&%#(' " '#"'*#% & )) #""#' % $#%'#' &! ' #(&!&& #"' "&" %&' %#(' " $' &$$ -%# "' %&','&$ & "'%" %#(' " '#"#' %#(&$#%' ",'&$ &$#%' ' %,'&$ && ) ) %&& #"' "'*#% '' '$#%' %! " " ,'&!(&'#"' "-%#&
If a Match is Not Found "%&&!' &"#'#(" "' ' ' #(&%&& "' !&& * #")%',' "'#%#(' " $' (& " ' !' #&&% #* %&( ' " $' " ' %'#' #(& (&"'*#% #%'#& " & )) #""''#"#' % #(&$#%'#' % ( ' $ +%
' !&& #"' "&"%&& "' %" ! '* &"''#' #(& (&"#' ' '%&"' # #(& (&"'*#%
#%+!$ ' !&& #"' "(&%&& '* &"''#' #(& (&) '"#

# - , -- - , , - ,0 ( '/-. (). /-
!.# ' -- " )(. $(- ( , --$( .# , (" $.1$&& , -- .) -$("& ) /--& 0 0$ .)( )!.# ) /-*),.- , -- - -* $!3*),.- , -* .$0 &3
), 2 '*& $!.# ' -- " )(. $(- , -- $.1$&& ,)/. .).# 0$ .*),.
#)!.# , -- - -* $!$ -)(&3 -$("& *),. ( ((). /- .) , -- ) /-( .1),%)! 0$ - . *),. ) , -- 0$ )( ) /-( .1),%.# ) /- , -- *. & '/-. /-
# - , -- - , , - ,0 ( '/-. (). /-
!.# ' -- " )(. $(- ( , --$( .# , (" $.1$&& )(0 ,. .) ,)/.$("* .# - !)&&)1-
$,-..# , --1$&& $0$ 3# +/).$ (. ( , ' $( ,)!.# $0$-$)(1$&& )' .# !$,-..1) 3. -)!.# !$0 3. ,)/.$("* .## , ' $($(".#, 3. -)!.# ,)/.$("* .# 1$&& &1 3- 4 ,)-
), 2 '*& $!.# ' -- " .# , -- .# , -/&.$(",)/.$(" * .#1$&& # !$,-. 3. $-.# +/).$ (.)! .# $0$-$)(.# - )( 3. $-.# , ' $( ,# ' -- " 1$&& - (..)() )(.# &) &) /-&/-( .1),%
!.# ' -- " , --$- .# , -/&.$(",)/.$("* .#1$&& # ' -- " 1$&& ,)/. .)) /-&/-() , -- )(.# &) &( .1),%/,.# ,,)/.$(" * ( -/*)( .# .3* )! 0$ ..# .() , --!() $- ,$ " &/-.# ' -- " 1$&& ,)/. .#,)/"#.# ,$ " .)() )( .# ( 2.( .1),%!() $- ( *. ,.# ' -- " 1$&& *. 3.# . 0$ ( *)-. .)$.- **&$ .$)(. -%
-$(".#$-' .#) /*.) ) /-&/-() - ( , -- #1$.# () , -- !.# - () - , ,$ " &/- 0$ -() - (* --' -- " -.#,)/"#.)() -)( - )( ( .1),%1$.#+/).$ (.- ( , ' $( ,- ) (* --' -- " -.)() - )(.# .( .1),%

Silent Master Port Considerations % %$%#! #% % &$ $%#' # # &$$ ''$ %$ &$ %( # %%! #%$ ($% $%#'% #$$%$ ' '$#% *$( $% #$$ %#'$% %#! #%$ % $ ## $$ &$ &$
% %$%# % %$ ''$ %! #% &$% '& "$$$ * !! % * &$% %%$ $ #$$ % $ &$ &$ %( # * &$% $ %)$%$ %#$ % &$ #$$!% %%* &$%&!(% %
&$#$$$ % $%#$"$% %$ ''$%% %$%#! #% &$% % !* %! #% %% *# &% !% &$ &$ #% %#! #% %

! " # ! ! " ! " ! # ! ! ! " ! "
" ! " ! " " !
NW–BM85–000
SWITCHES
USE RIGHT
SWITCHES
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
UP = 1 DOWN = 2
NW–BM85C002 NW–BM85D008 = MODE:
PORT MODE: CONFIGURE
UP
UP = RUN APPLICATION
RUN
DOWN
(LEAVE IN UP POSITION)
CONFIGURATION PORT:
PARITY:
PORT 1 PORT 2 PORT 3 PORT 4
UP UP
UP
UP DOWN
DISABLED
UP UP DOWN DOWN
UP
BAUD RATE: 9600 2400 1200 300
EVEN DISABLED
UP DOWN
DOWN DOWN
UP UP DOWN DOWN
UP
DOWN
UP DOWN
ODD
DOWN
DOWN

Define the Configuration Port 5)2#(%1!-$$%2%0,)-%2(%/.02#.--%#2.02."%31%$&.0#.--%#2)-' 2(%1%0)!+2%0,)-!+%22(%,&.02(%/.027.35!-22.31%
Set the Configuration Port Parameters (NW–BM85–000) %215)2#(%1 2.,!2#(2(%2%0,)-!+1"!3$0!2%/!0)27,.$%!-$ 12./")21 (%/.02!+5!7131%1 $!2!")21&.0#.-&)'30!2).-
Set the Configuration Port Parameters (NW–BM85C002, D008) %215)2#(%1 2.,!2#(2(%2%0,)-!+1"!3$0!2%!-$/!0)27,.$% (%/.02!+5!7131%1 $!2!")21!-$12./")2&.0#.-&)'30!2).-+5!71 +%!4%15)2#( )-)21 /.1)2).- (% 5)++-.203-3-+%11 15)2#( )1
Connect the Terminal (% /.5%01(.3+$"%.&&!22()12),%.--%#22(%2%0,)-!+2.2(% /.027.3!0%31)-'&.0#.-&)'30!2).-%22(%2%0,)-!+1#.,,3-)#!2).- /!0!,%2%012.,!2#(2(.1%.&2(% .5%03/7.302%0,)-!+!-$ 12!02!-7%,3+!2).-/0.'0!,7.3!0%31)-' .302%0,)-!+1(.3+$"% 03--)-'!-$0%!$7"%&.0%7.3!//+7/.5%02.2(%
Apply Power to the BM85 (%-7.3(!4%1%22(%#.-&)'30!2).-15)2#(%1!-$7.302%0,)-!+)1 0%!$7!//+7/.5%02.2(%
(%#.-&)'30!2).-/.021)-$)#!2.01(.3+$"+)-*!2.-%1%#.-$)-2%04!+1 1(.5)-'2(!22(%#.-&)'30!2).-,.$%)1!#2)4% .302%0,)-!+1(.3+$ $)1/+!72(% 1#0%%-
.30#.-&)'30!2).-1#0%%-1!-$*%7".!0$#.,,!-$1!0%$%1#0)"%$ 12!02)-'!2%#2).-
Configuring the Modbus Models 890 USE 103 00 41

&! &! %!&"& !"" $ ""! # #!" # % !% "
V Select a configuration screen or Help screen 1 ... 8
P Select a port to be configured 1 ... 4
N Enter a Modbus slave device address 1 ... 247
T Enter the port type M = Master S = Slave N = Network X = Silent Master Network
B Enter the baud rate 50, 300, 1200, 1800, 2000, 2400, 3600, 4800, 7200, 9600, 19200
S Enter the stop bits 1 or 2 (Note 1)
R Enter the parity mode N = None O = Odd E = Even
M Enter the communication mode A = ASCII R = RTU
Y Enter the port priority 1 ... 4
L Enter the link timeout value 1 ... 3000, in multiples of 100 ms
F Enter the modem booster selection Y = Yes N = No
W Write the configuration parameters to all four ports
D Initialize all four ports with default parameters
? Display Help for the current configuration screen
E Enter a Modbus address and five–byte routing path into the Modbus Address Map table on the V2 or V3 screen.
When you use this command, enter the following:
where:
– the E command – the table location (1 ... 64) for your entry – the Modbus address (1 ... 255) to be mapped – the five bytes of routing (1 ... 255 in each byte).
E = Modbus Address Map command YY = location (1 ... 64) in the table MM = Modbus address (1 ... 255) XX = each byte (1 ... 255) in the path.
Command Action Range

Parameter Port 1 Port 2 Port 3 Port 4
Port type Master Slave Slave Slave
Slave device address –– 1 1 1
Baud rate 9600
Stop bits 1
Parity mode Even
Communication mode RTU
Port priority 1 2 3 4
Link timeout value –– 600 600 600
Modem booster ––
Configuring the Modbus Models 890 USE 103 00 43

V1 2%3()22#1%%-3.$)2/+!7!-$2%33(%#.,,4-)#!3).-/!1!,%3%12&.1 %!#(/.13
V2 2%3()22#1%%-3.$)2/+!7!-$2%3+.#!3).-2.&3(%.$"42 $$1%22!/3!"+%&.1%!#(/.13
V3 2%3()22#1%%-3.$)2/+!7!-$2%3+.#!3).-2 .&3(%.$"42 $$1%22!/3!"+%&.1%!#(/.13
V4 2%3()22#1%%-3.!5%.1-)3)!+)8%3(% #.-&)'41!3).-
Help Screens: V5, V6, V7, V8.4(!5%&.41%+/2#1%%-23(!37.4#!-!##%22$41)-'#.-&)'41!3).- .4#!-2%+%#33(%%+/2#1%%-2"72%+%#3)-'2#1%%-2 .1 1%22)-'3(% 04%23).-,!1* *%76)++$)2/+!7%+/&.13(% #.-&)'41!3).-2#1%%-7.4!1%#411%-3+742)-'
(%#411%-3+7!#3)5%/.13)2!+6!722(.6-!33(%".33.,+)-%.&7.41 2#1%%-
.2%+%#3!-.3(%12#1%%-&.13(%!#3)5%/.13%-3%1#.,,!-$2 .1 .2%+%#3!-.3(%1/.13%-3%1#.,,!-$2.1
(%-7.4%-3%13(%#.-&)'41!3).-#.,,!-$27.4#!-%-3%13(%,2)-'+7 .1!2!231)-'1%223.#.,/+%3%3(%%-317.#.11%#3 *%7231.*%2)-!-%-317/1%22.#!-#%+!-%-317"%&.1% #.,/+%3)-')3/1%22
Configuring the Modbus Models 890 USE 103 00 44

& $% ! #! ## & $!#! & $ $"& $! ! # ! ! $% # ! #! &! ! & $! "! "
Configuring the Modbus Models 890 USE 103 00 45

MODICON MODBUS BRIDGE/MUX – Ver. 1.0 Copyright (c) 1989 MODICON, Inc., Industrial Automation Systems Group
Modbus Plus Address = 24
PORT NUMBER# 1 2 3 4 [1, 2, 3, 4] PORT TYPE master slave network slave [m, s, n, x] Slave Dev Addr – 1 – 230 [1–247] Baud Rate 9600 1200 2400 9600 [50–19200] Stop Bits 1 2 1 1 [1, 2] Parity even none even even [n, o, e] Mode rtu ascii rtu rtu [a, r] Priority 1 2 3 4 [1–4] Link Timeout – 20 10 600 [1–3000] Modem Booster – yes yes no [y, n]
>>Valid Commands:[V1 V2 V3 V4 P T N B S R M Y L F] Keys:[Enter Esc ?–help]
Active Port 1>> __

-30"300$,2*71$*$"2$#.-02(11'-5,-,2'$!-22-+*(,$-%2'$1"0$$,
.$"(%72'$.-0227.$!7$,2$0(,&5(2'-,$-%2'$%-**-5(,&27.$1 12$0* 4$$25-0)-0 (*$,2 12$0-0$6 +.*$ $,2$02-1$23.2'$"300$,2*7 "2(4$.-02 1 1* 4$.-02(*$,2 12$0.-025(**!$* !$*$# 6+ 12$0-,2'$1"0$$,
-3" , *1-$,2$02'$"-+.*$2$"-++ ,#1$/3$,"$ 1 120(,& 1$. 0 2$#!71. "$1
Example -"-,%(&30$-02 1 * 4$.-02$4("$##0$11 ! 3# 2-.(24$, 0(27 -020(-0(27 1$"-,#1(,)(+$-32 ,#--#$+--12$07-35-3*#$,2$02'$%-**-5(,&"-++ ,#120(,&
Configuring the Modbus Models 890 USE 103 00 47

" !
"
MODBUS ADDRESS MAP FOR [E1–E32] [V2] MAPS: Modbus Address to Destination Address [Port Type: Master]
Table Modbus Destination Address Table Modbus Destination Address Entry Address (5 bytes) Entry Address (5 bytes)
[020]= 021 022 023 024 025 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [124]= 020 004 000 000 000 [000]= 000 [000]= 000 [000]= 000 [126]= 020 006 000 000 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000 [000]= 000
>>Valid Commands:[V1 V2 V3 V4 P E] Keys:[Enter Esc ?–help]
Active Port 1>> __

+ ,! + * & '* '& " -*"& &,*" + '*,! + $ , ('*, + ,! + * & '* '& " -*"& &,*" + '*,!"+('*,
'- &$, *&, ,/ &,! & + * &+-+"& '%%& + &
! $ &,*1 '$-%&"+$"+,"& ' $' ,"'&+"&,! ,$ ', ,!, ,! + * ,$ &,*1$' ,"'&+&',' -+ * ++ +'-%-+, &, * ,! ' -+ * ++ +,!,1'-/&,,'%("&,',! + '& '$-%&
! &1'- ",,! ,$ &,*" +1'- '&',!. ,' '+'"& "& + )- & '* 0%($ 1'- '&',!. ,' '& " -* '* '& " -*"& &',! * &,*1
'- '&',!. ,' "$$$$,! ,$ &,*" +"&,! + * & '* %#"& & &,*1"&,! + * & 1'-/"$$-+ &'%'* ,!& &,*" +1'-%" !, "& ", '&. &" &,,'# (,! %$$'&'& + * &
Example '-+ ,! + * &,$ &,*1,'%(' -+ * ++,',! *'-,"& (,!1'-/'-$ &, *,! '$$'/"& +,*"&
'-%1 "& ", '&. &" &,,'-+ ' -+ * ++"& '&. &,"'&,!, ! $(+1'-,'* % % *!'/ * ++ +* %(( "&1'-*(($" ,"'& '* 0%($ 1'- &-+ ,! ' -+ * ++,' "& %(("& ,' ' -+$-+&' * ++/",!*'-,"& ,!*'- ! *" $-+, * ++&,! +% '&. &,"'&' -+ * ++ /'-$ %(,' ' -+$-+&' ,!*'- !,! +% *" 0%($ +* +!'/&"& ,$ &,*" +&
'%(,! * ++ ++!'/&,& 1'-/'-$ &, *,! '$$'/"& +,*"& +
Configuring the Modbus Models 890 USE 103 00 49

>>Valid Commands:[V1 V2 V3 V4 W D] Keys:[Enter Esc ?–help]
Active Port 1>> __

&!#"%# $!# ' $% #! # # #! # &
# (# #!"# $!# ! #!" # # #!$ #% $" #!# &
### # ( # $!# ! #!" " !"# $" !"" # " ! $! !#"# (! "

" !
NW–BM85–000
USE LOWER
SWITCHES
USE LEFT
1 2 3 4 5 6 7 8
SWITCHES
0 = DOWN
SWITCH POSITION
SWITCH POSITION
ADDRESS
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
0 1 0 1 0 1 0 1
0 1 0 1
0 1
0
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
0 1 0 1 0 1 0 1
0 1 0 1
0 1
1

##" "# ! #!"( $% "" #$ #!( ! !# # $" $" #& ! ##" $" !#"
# " #" #& #% ( $! # "" " &!" # #$ #
" !
!
!( $"##$ ## %!(##( $%"#$ #" $" !# ! #!" $" $" !""""! #" #!
$! &!# #! $ # '! "##" $!# "# # "# !# $! !# $!# " # "##
( $%"## $!# !!# ( !" "# # "#( $ #! " !##$ ## #"# "# #
Configuring the Modbus Models 890 USE 103 00 53

#
! !" ! # # ! ! ! #
Indicators Pattern Hexadecimal Digit
11 PROM checksum error
12 RAM data test error
13 RAM address test error
14 Normal power down event
17 Bad or unexpected interrupt
18 EEPROM checksum error
19 Modbus port loopback error
24 Modbus transmit state error
25 Modbus receive state error
26 ASCII transmit communications state error
27 Transmit underflow error
28 RTU transmit communications state error
29 ASCII receive communications state error
2A RTU receive communications state error
2B Transmit communications state error
2C Receive communications state error
Code (Hexadecimal) Meaning · Code (Hexadecimal) Meaning

2D Modbus state timer event error
2E UART interrupt error
34 Modbus Plus Processor interface error
35 Modbus Plus Processor opcode response error
36 Timeout error waiting for Modbus Plus Processor
81 Master state error
82 Slave state error
83 Unknown routing failure to send
84 ... 8B Port number error
91 Privilege flag not reset
92 Port number error
A2, A3 Unknown function code
Code (Hexadecimal) Meaning · Code (Hexadecimal) Meaning



# # "
$ $% "$ " "%
!" "$ " "%
" %
"" " # " %"!
"" " #! #! !!
" !# %
"" "
Configuring the Programmable Models 890 USE 103 00 57

! "
Modbus Plus Network Cable
NW–BM85E232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85D002 19 in Rack 125 Vdc or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85E485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
NW–BM85S232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85S485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
" # " # $! # # !" " !
# " " " ! " # " # " # " # " # "
" !
!

)1237.4,423#1%!3%7.41 !//+)#!3).-/1.'1!,.13()27.46)++ -%%$3(% 1.'1!,%5%+./,%-3 .&36!1% ..+)3 !13-4,"%12 !-$.1$%1)-')-&.1,!3).-!1%/1.5)$%$)-3(% %#3).-
.46)++!+2.-%%$3(%.1+!-$88#.,/)+%1!35%12).- .1+!3%1 6()#(2(.4+$!+1%!$7"%)-23!++%$)-7.41$%5%+./,%-3#.,/43%1 (% !//+)#!3).-242%3(%!1'%,.$%+ .42(.4+$%-241%3(!33(% .1+!-$!1'%,.$%++)"1!1)%2!1%)-23!++%$
4.2.2 Equipment For Downloading the Application Program
&3%17.4#1%!3%3(% !//+)#!3).-7.4,423$.6-+.!$)33.3(% !#1.22.$"42 +42 .41(!1$6!1%2(.4+$"%!- #.,/!3)"+%.1)#1.(!--%+ .1()'(%11%#.,,%-$%$6)3(!3 +%!23 %'!"73%2.& (%1%04)1%$%04)/,%-3)2$%2#1)"%$)-3(% %#3).-
.4,)'(3&)-$)3,.1%#.-5%-)%-3&.1$%5%+./)-'!-$$%"4'')-'7.41 !//+)#!3).-)&7.442%3(%2!,% &.1$.6-+.!$)-'.6-+.!$)-'#!- "%/%1&.1,%$&1.,6)3()-3(%.1+!-$$%5%+./,%-3%-5)1.-,%-3
(% #.--%#32!- "42(.233..$"42 +42 (% #.--%#32!)#1.#(!--%+"42(.23!#(!$!/3%1)-#+4$%2!$%5)#%$1)5%1 /1.'1!,3(!37.46)++)-23!++$41)-'7.41)-23!++!3).-.&3(%!$!/3%1)-3. 7.41(.23#.,/43%1
.41 $%5%+./,%-32.&36!1%)-#+4$%2!$.6-+.!$43)+)373(!37.4 #!-14-6)3(%)3(%13(% .1
Configuring the Programmable Models 890 USE 103 00 59

(%+ '+ ,% ) '% '# + "% $)% ),' %%" ) ( &'%+ )%(( ().%*'&"$$ $ -#&" (' ( %,$ %') %'"$ $+ '%$# $) %#&" ) %*# $)) %$ ((*&&" , ) ) ! ) ')$*# '($%' ' $ $ %'#) %$' $) ) %$
%*' (% ),' $"* (""% ) + "% $) " ( %'%#& " $ $%,$"% $ .%*'&&" ) %$%*"(% + $((%')# $)% (%*' % " () ).%*$*( ( -#&" (
%""%, $ + "% $) " (' (*&&"
README.DOC Complete BM85 development information text file. View or print this file for current information about your software.
BM85LOAD.EXE The BM85 download utility
MBPSTIM.EXE Data transfer exerciser. Reads registers and writes a single register to a controller over Modbus Plus.
BM85.EXE User–compiled demonstration program to be downloaded. See the descriptions of the test programs below.
BM85.PRJ Borland C++ 3.1 project file to build BM85.EXE
BM85.H Header file containing function prototypes of utility routines
C0BM85.OBJ BM85 startup code
BM85.C Source file for user base demonstration program. Copy the source for a specific test program into this file and compile it. Initially supplied as TEST0.C. See the test programs below.
BM85LIB.LIB Library of utility routines
MBPHOST.SYS Device driver for Modbus Plus network adapter
MBPSTAT.EXE Modbus Plus network management and diagnostic utility
BDRESET.EXE Initializes and enables the Modbus Plus adapter
%*' (!(%$) $$ $ %'#) %$) -) " ( " %$) $( ) " $ %'#) %$%*) + "%& $ %#& " $ $ %,$"% $ .%*' &&" ) %$*( $ ) %'"$ $+ '%$# $)) "(%%$) $($.' $)".*&) $ %'#) %$%*).%*' (% ),' %' $()"" $ ) (% ),' .%*( %*"+ ,) ( " %* #."(%,$))%&' $)%*) '%&.)%*( (' ' $ $ + "%& $ .%*'&&" ) %$
File Name Purpose

%""%- $ " )&(%, )%+( % .#&" )* */%+$+) $ /%+( , "% $* /$")% #% $+) )* )*&(% (#) %( . ( ) $ $* )* $ /%+(
TEST0.C Displays a code on the BM85 LED indicators
TEST1.C Shows Modbus Plus master and slave operation
TEST2.C Demonstrates multitasking using the BM85 indicators
TEST3.C Demonstrates floating point emulator
TEST4.C Simulates process control with multitasking, C++ conventions
TEST5.C Same as TEST4.C, but uses C conventions
TEST6.C RS232 port loopback test
TEST7.C RS232/RS485 port loopback test, long term
TEST8.C Sample large program (240K) for download testing
Using the Test and Demonstration Source Files %+) $/ " ()*%&/ **%* " $# * $#% /* * " %(/%+( &&" * %$$%#& " *%-$"%* . +*" *%* +) $ * +* " */%( .#&" * %-$"%$ (+$- * $* %("$ $, (%$# $*+) $ * %""%- $ ) '+ $
" ((/ $"+ ) +$* %$)* */%+$+) *%%$)*(+* (%+* $ %()) $ $ $%$*(%"" $ #+"* &" *)!)%(* ( )- * $ /%+(&&" * %$+"* *)! $ ) $" %$%%& (* , ) ) $ * , *)!(%+* $ #+)*#! & ( % "")*%$( *(* %$(%+* $ ""%- $ * *(%+* $ *% * (%$* $+ * "" $ *)!%( $" $%* (& $ $ *)!
%+( #%$)*(* %$&(% (#) $ &(%, )%+( .#&" )% * +) % * " ((/)#+"* *)! $ +$* %$) ) % $ )% $ %(&(% (## ()- %( #%( # " (- * * *"$ +

5#34*454&4)&0"4)3".%0"2"-&4&2353&%*.9/52/2,".%%&6&,/0-&.4 &.6*2/.-&.47)&2&6&2"00,*$"#,&
4.4.1 Default Parameters
)&%&6&,/0-&.43/'47"2&*33500,*&%7*4)47/%&'"5,40"2"-&4&23'/2 %/7.,/"%*.(4/9/52 .&0"2"-&4&230&$*'*&3)/74/"$$&339/52 :: %2*6&24)&%&'"5,430&$*'*&33/'47"2&*.4&225046&$4/2 )&/4)&20"2"-&4&2*34)&/%#53,53./%&"%%2&33/'4)&4"2(&4 5.*4'/2%/7.,/"%*.(4)&%&'"5,4*3./%&"%%2&33
'9/52 :: %2*6&2".% "2&3&44/4)&3&0"2"-&4&239/52 *.34",,"4*/.7*,,#&&"3*&2#&$"53&9/5$".#90"330"24/'4)&3&4503&& 4&03 ".% #&,/7
4.4.2 Installation Steps
'9/5)"6&",2&"%9*.34",,&%4)& :: /%#53,53"%"04&2 ".%*43%2*6&2".%)"6&&%*4&%9/52 '*,&4/*.$,5%&" $/--".%7*4)%2*6&20"2"-&4&239/5$".3+*04)*334&0
'9/5)"6&./4*.34",,&%9/52"%"04&2".%%2*6&24)&.9/53)/5,%%/ 3/./7#&'/2&02/$&&%*.(7*4)4)& 3/'47"2&*.34",,"4*/. /,,/74)&*.3425$4*/.3*.4)&(5*%&#//+3500,*&%7*4)9/52"%"04&2
"24/'4)&"%"04&2*.34",,"4*/.02/$&%52&2&15*2&39/54/30&$*'9" 3/'47"2&*.4&225046&$4/2/24/"$$&044)&%&'"5,46&$4/2 '9/5 30&$*'9"6&$4/2/4)&24)".4)&%&'"5,4-"+&"./4&/'4)&6&$4/2 /57*,,.&&%4)*3*.'/2-"4*/.7)&.9/5*.34",,4)& 3/'47"2&
.352&4)"49/52/2,".%::3/'47"2&*3*.34",,&%/.9/52 $/-054&2".%*330&$*'*&%*.9/52 $/--".%/2&8"-0,&*' 4)&$/-0*,&23&8&$54"#,&'*,&3"2&*. :!: :!:4)&.9/52 $/--".%3)/5,%30&$*'94)*30"4)
2&"4&"7/2+*.(%*2&$4/29'/29/52 %&6&,/0-&.4'*,&3".% $/094)&&.4*2&$/.4&.43/'9/52 %&6&,/0-&.4%*3+*.4/4)*3 %*2&$4/2935((&34&%."-&'/24)&.&7%*2&$4/29*3 :!:
Configuring the Programmable Models 890 USE 103 00 62

." 2#2 0-(#!2$'*# 2-1#22!-00#!2"'0#!2-07 . 2&1$-07-30 -0* ,"#,4'0-,+#,2-0#6 +.*#',2 -0* ," #,4'0-,+#,27-3! ,31#2$-**-5',%)#71#/3#,!#
BM85.PRJ Project name
Alt–O D Option directories
(paths) Update the paths for your INCLUDE and LIBRARY directories
-30 ',2#003.2'11#22- 4#!2-0-2& ,
-30 -" 31*31,-"# ""0#11'1-2& ,
." 2#2 ," !-++ ,"*',#1',2 .0-(#!21 +#,32-31#2,#5. 0 +#2#01,2 -0* ,"#,4'0-,+#,27-3! ,31#2$-**-5',%)#71#/3#,!#
Select command line Select the BM85 DOWNLOAD or MBPLUS STIMULATE line
Enter parameters Set the parameters as they are used in your application
Configuring the Programmable Models 890 USE 103 00 63

!! "#& "#" "" "# &"# # #! # & !!$ # ##&" !% $" ' & #!"# """" " $" $" !""
!' $ & ' $! # ' $ $"#"##""# $ $"# " "## !""# !# !"" ! #!' $!$" # & $# #' ! ! "#!$# " !"## #""! ! % # "
$ & # # ##" "# # "# $ # # ! % ## %" ! $" $" #& ! # ! # % #' ' $! & "# # ! ! # & '
#!# & " ## "" $"#"## & ## !$ # # ""## "!" " &!$

USE UPPER
U = UP
SWITCHES
D = DOWN
X = DON’T CARE
1 2 3 4 5 6 7 8
BM85 OPERATION
1 2 3 4 5 6 7 8
RUN APPLICATION STORED IN BM85. SWITCHES 1-7 DEFINED BY USER. U USER DEFINED
X U D D ALLOW DOWNLOAD OF APPLICATION.
X D D D RUN CONTINUOUS INTERNAL TESTS SEE INDICATOR CODES IN THIS CHAPTER.

!
USE LOWER
1 = UP
SWITCHES
0 = DOWN
SWITCH POSITION
SWITCH POSITION
ADDRESS
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
0 1 0 1 0 1 0 1
0 1 0 1
0 1
0
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
0 1 0 1 0 1 0 1
0 1 0 1
0 1
1

# % " "!" " # ! "! ! " " ! #!" ! %!'!" !""#! !
4.8.1 Normal Download Codes
! # %
Port 4 –– Flashing two times per second Ready for downloading
Port 3 –– ON intermittently Receiving download from host
Port 2 –– ON (combined with port 3) Writing to BM85 RAM
Port 1 –– ON (combined with port 3) Erasing BM85 RAM
# !# % "#! !"&" #" " ! '! "" "! # " !
"" #!"% " ! "% & "! !"" " !! %!"' "" ! " " # " "'! %! "" ! %"" % " " # #! ! "" !" " ""$' "!" !"! ""
Indicators Pattern Hexadecimal Digit
Error Code (Hexadecimal) Meaning
F1 BM85 kernel is reloading
F4 Program or task returned to BM85 bootstrap
F8 Program or task called abort()
FD Could not extend heap – program called malloc() or equivalent and had insufficient memory
FE Could not create heap – not enough memory below code area
FF Not enough memory to copy program to RAM area
Indication Meaning

""! !" " !' #$ !! "# " ' " " #! #! "% ""! #! "!
" ! "! "% "$ ' # " !! ! % ! " "# "
" !
!
' #!""# "" $ '""' #$!"# "! #! " " ! #! #! !!!! "! "
# % " " #" & !""! # " !%"" " !" " # " # " !%" " !""
' #$!"" # " "' ! !"" !"' # " ! ""# "" "!" !""
Configuring the Programmable Models 890 USE 103 00 68

Installing the BM85 890 USE 103 00 69

#% ")( , "" %(#%+$* $ %$ %( /%$*") " %(, (* " &$ "%( %( $)*""* %$ $*%)*$( $ (!$)*"".%+(+$ * +) $ * + " $ ) $ * %$ %() " %(&$ "#%+$* $ %( %((!#%+$* $
)) *% $ *%()*%) %- *)%& (* $ )**+)%+( % % #%+$* $ # * %) %+" $"+ &(%& ( )) %(%) (, $ * ) $ *%()
%+) %+"")%&(%, ))*%* +$ *)( (&$ " %() ** $ * )- * )%$$ * $ * " )$) (, $
* * %$) $ %( * ")%+** %& (* $ &%- ( $, (%$# $*$%$$ *%(( '+ ( # $*)
Modbus Plus Network Cable
NW–BM85–000 Panel or Shelf 115/230 Vac Single Modbus ASCII or RTU
NW–BM85C002 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85E232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85E485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
NW–BM85S232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85S485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
%+$* $ # $) %$)% * ) #% ")( ) %-$ $ +(

Horizontal Mounting &++&$*,) & + * $& #*!* !++ .!+ ' * &)$&,%+!% &% &)!0&%+#'#+ &)$&)* # # + ,%!++&) #&. / # - #+#&. -! .!% + !% !+&)*&,%+!% )" +*) *,''#! .!+ + ,%!+ &) * ,)!% !+&%+ &)!0&%+#*,)
Vertical Mounting &)- )+!#$&,%+!% ,* + )" +**,''#! .!+ + ,%!+ &) +!% +&'% # )" +* - +*+ +!%* )+!%+&*#&+*')&-! &%+ ,%!+*&++&$*,) & !+!&%# ) .) !*) (,!) &) * ,)!% + )" +*+&+ &,.!## - +& ,)%!* ) .) &)+!% + ,%!++&/&,)'% #&,)+*) ) (,!) /'!##/ *+% ) $$$ !% *) .*&) (,!-# %+) *+!* +&)/ %*+##+ ,%!++&) #&. / # - #+#&.-! .!% + !% !+&)*
Modbus Plus Network Cable
NW–BM85D008 19 in Rack 125 Vdc or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85D002 19 in Rack 125 Vdc or 24 Vdc Single or Dual RS232 Programmable, User Defined
&,%+!% !$ %*!&%*& + * $& #*) * &.%!%! ,)
"1$&,%+$& #*) *! % &)!%*+##+!&%!%+&*+% ) 1!% )"&,.!## - +& ,)%!* ) .) &)+!% + ,%!++&/&,) )"&,)+*) ) (,!)
%$&,%+ + ,%!+%*,''&)+!+* # /!+* )&%+$&,%+!% +* +!*#! + %&, !%. ! ++ +/&, &%&+ - +&')&-! ) )*,''&)+ .!+ !%+ )"

Allow 4.0 in (102 mm) rear clearance for access to switches, cables, and fuse


3.47 in (88 mm)
18.25 in (464 mm)
19.0 in (483 mm)
TOP VIEW
Allow 4.0 in (102 mm) rear clearance
for access to switches and cables
17.25 in (438 mm)
9.15 in (232 mm)
8.48 in (215 mm)
10.59 in (269 mm)
1.44 in (37 mm)

AC/DC Models,.$%+2!1%24//+)%$6)3(!/.6%1#!"+%.& &3 ,+%-'3(&.1 ./%1!3).- &1., !# .1 !# 2)-'+%/(!2% /.6%1 (% #!"+%#.--%#323.!2.#*%3.-3(%1%!1/!-%+1.4-$)-')23(1.4'(3(% #!"+% (%!#+)-%26)3#()2+.#!3%$.-3(%1%!1/!-%+ (% #.-3!)-2!-!#+)-%&42%3(!3)2!##%22)"+%.-3(%1%!1/!-%+
DC/DC Models ,.$%+2./%1!3%&1.,! $#.1 $#2.41#%.6%1#.--%#32 3.!3%1,)-!+231)/.-3(%1%!1/!-%+'1.4-$)-'3%1,)-!+)2/1.5)$%$ (%$#2.41#%,423"%26)3#(%$!-$&42%$%73%1-!++83.3(%
5.2.1 Connecting AC Power
%33(% /.6%126)3#(3.3(% /.6%1/.2)3).-.--%#33(% 3.3(%/.6%12.41#% %33(%/.6%126)3#(3. 9 9/.6%1 (% 4-)32 )-$)#!3.12(.4+$)++4,)-!3%
%&.1%#.--%#3)-'3(%-%36.1*#!"+%22%33(%/.6%126)3#(3.3(% /.6%1/.2)3).- (%4-)32 )-$)#!3.12(.4+$-.3"%+)3
5.2.2 Connecting DC Power
%33(%%73%1-!+$#/.6%12.41#%3..--%#33(% 3.3(% 2.41#% %33(%$#/.6%12.41#%3. (% 4-)32 )-$)#!3.12(.4+$)++4,)-!3%
%&.1%/1.#%%$)-'6)3(3(%#.--%#3).-.&3(%-%36.1*#!"+%22%33(%$# /.6%12.41#%3. (%4-)32 )-$)#!3.12(.4+$-.3"%+)3
Installing the BM85 890 USE 103 00 74

SERIAL PORT 2
SERIAL PORT 4

AC POWER CONNECTOR
MODBUS PLUS ADDRESS SWITCHES
SERIAL PORT
SWITCHES
Figure 19 BM85–000 Rear Panel
SERIAL PORT 2
SERIA PORT 4
CHANNEL B

AC POWER
MODBUS PLUS
SERIAL PORT 3 SERIAL PORT 1
SWITCH
CHANNEL A
PLUG AND FUSE (UPPER) SERIAL PORT SWITCHES
AC POWER CONNECTOR
(LOWER) MODBUS PLUS ADDRESS SWITCHES
Figure 20 BM85C, BM85E, BM85S Rear Panel
MODBUS PLUS
SERIAL PORT 2
SERIAL PORT 4
CHANNEL B

(LOWER) MODBUS PLUS ADDRESS SWITCHES
Figure 21 BM85D Rear Panel

%(!# $# ! %!#$# !%! % ##" #" ' ($#"#!' % ! !( $
&#
&#
% &% ! $ !(!#! % ) %!%
%#! % $% ! % ! )% % %$%(! $#($
" !
!
" ! ! !
" ! !

5.3.2 Connecting Dual Network Cables
#)!!#(+$& '$##($)'!)'!' # ($( $&&($##($&'$#( &&%#! ')&($ #( ,( $&&(!'#$##($&'
,$)& #'(!! # )!!)# ($##(+$& ( ( '$#!, ' # !!$##(( !($( &&%#! $##($& !) &" #( # $##($& $ $# %&( #)"& #($( $##($&
$##(( '& !%$&(* !'($( $)&$##($&'$#( && %#! ')&($ #( ,( $&&(* !'#$##($&'


Figure 22 Layout of the Indicators
! "% " *&("##+$"%* ))* "#/-! %*! !)'&- ( (&$*! )&+( % "*)"%* (%#'&- ()+''#/")&' (*"% %&($##/
! "% " *&( &%#/"##+$"%* ))* "#/-! %*! !))+ )) +##/ &$'# * "*)"%* (%# " %&)*" )
%*! & +)'&(*$& #) !& +)'&(*"% " *&( #)! )-! % ,#" $ )) ")( ", *"*)'&(* %"%* (%# +#* .")*)% ((&( '** (%") #)! ! ) & )( #")* "% *"&%
%*! '(& ($$# '&(*$& #) !'&(*"% " *&(")'(& ($$# *&)!&-)**+)*!*"))' " " *&*! ''#" *"&%& )( #)! *& )!&-)**+) +("% &-%#& "% ! ) & )( #")* "% *"&%

! * ' "' " ,(*+!(/+,! (. *%% (&&-'" ,"(' +,,-+,,! '( /(* "' " ,(*+ (* ' " '," 1 **(*+(',! ,/(( -+%-+ % ),!+
,! (* "' " ,(*%"'$+ &(& ',*"%1","' " , +,!,& ++ **(*/+ , , (',! ( -+%-+ % ),! +, 1+,, "' " , +!* -%, 0"+,+ ",! *"',! % (*"''( ." ('' , ,(", (&&-'" ,"(' "+%(+,('(' % ),!,! (,! *),! (',"'- +'(*&%%1
! "' " ,(* %+! +* ) ,",". ),, *'+,(+!(/,! '( + (&&-'" ,"('+,,-+(',! ( -+%-+' ,/(*$! ),, *'+*
Six Flashes per Second!"+"+,! '( +'(*&%() *,"' +,, %%'( +(',! ' ,/(*$+!(-% %+!"' ,!"+),, *' ,! "' " ,(*"+ (',"'-(-+%1,! "+'(,,*'+&",,"' (',! ' ,/(*$
One Flash per Second! '( "+( %"' , *#-+, "' )(/ * -)(* , *! *"' & ++ *(&'(,! *'( /",!,! +& ' ,/(*$ * ++ -)%" , * ++ +* '(,%%(/ ',!"++,, ,! '( &('",(*+,! ' ,/(*$ ' -"% +,% ( ,". '( +,* &"'+"',!"++,, (* ". + (' +,! ',, &),+,( (,(",+'(*&%() *,"' +,,
Two Flashes, then OFF for Two Seconds! '( "+! *"' ,! ,($ ' "' )++ &(' (,! *'( + -,"+' . ** "."' ,! ,($ ' ! $,! ' ,/(*$%"'$ (*'() '(* +!(*, "* -",(* ,". , *&"',"('
Three Flashes, then OFF for 1.7 Seconds! '( "+'(,! *"' '1(,! *'( +,"+ %"&"' ,! ,($ ' -, "' "' '((,! *'( ,(/!" !,()++", ! $,! ' ,/(*$%"'$ (*'() '(*+!(*, "* -",(* ,". , *&"',"('
Four Flashes, then OFF for 1.4 Seconds! '( !+! * .%" & ++ *(&'(,! *'( ,!,"+ -+"' ,! +& * +++,!"+'( ! '( * &"'+( %"' "' ,!"++,, +%(' +", (',"'- +,(! *,! -)%" , * ++ ,! -)%" , * ++"+'(,! * (* ". + (' +,! '( ,! ' !' +,( ,! ),, *'( (' %+! . *1+ ('

& " $!&! !&"! !" ! ! ! # % ! $ $!! !"!"
!! !! ! ! " ! ! !!!!"! ! $ !% %
! ! ! " " !$ " % "# !!! %!%!"!% " !
Modbus Plus
Network
Node
Figure 23 Modbus Plus Port Label

MODBUS PORT 1 PORT 2 PORT 3 PORT 4
ASCII / RTU
BAUD RATE
STOP BITS / PARITY
MODEM BOOSTER
Figure 24 Serial Port Parameters Label
TIMEOUT (100’S ms)



Compatible Devices and Cables 890 USE 103 00 83

'$0$ !!/$3( 1(-,0 /$20$#(,1'$#$3("$ ,#" !*$*(01(,&,1'$" !*$ . /1,2+!$/0 (,#(" 1$01' 1 " !*$*$,&1'-.1(-,(0 3 (* !*$ -,1 "15-2/-#("-,#(01/(!21-/%-/%2/1'$/(,%-/+ 1(-,
J375 Modicon Micro 84 Modbus communication option
J474 Modicon 484 Modbus communication option
J478 Modicon Modbus network option
W190 Modicon 584 Modbus cable assembly, AS–W190–XXX
W807 Modicon 884 Modbus cable assembly, AS–W807–XXX
W952 Modicon 984–680 to IBM AT cable assembly, AS–W952–XXX
W953 Modicon 984–680 to P230 cable assembly, AS–W953–XXX
W978 Modicon 984 to Modbus modem cable assembly, AS–W978–XXX
Abbreviation Meaning Equivalent Part
9M9M 9–pin male to 9–pin male Jameco GC9M
25F9M 25–pin female to 9–pin male Jameco AD926
25F25F 25–pin female to 25–pin female Jameco GC25F
X25F9M 25–pin female to 9–pin male, modified
Jameco AD926 remove connection between female pin 8 and male pin 1
# .1$/0 /$ 3 (* !*$%/-+ +$"-*$"1/-,("0 '-/$4 5- # $*+-,1 $*$.'-,$
'$-#!20*20(,*(,$"-,,$"1-/-#("-,. /1 (0 02(1 !*$%-/+ )(,&0(+.*$ 0(,&*$14(01$#. (/.*200'($*#"-,,$"1(-,0 1 0$/( *.-/1
-20$ -#!20*201$/+(, 1(,&"-,,$"1-/ (, 0$/( *" !*$ ..*(" 1(-,
Abbreviation Meaning

,)),4(+&(0 )(01(+&,%",*- 1(!)$#$3("$0 +#" !)$01' 1" +!$20$# %,/",+%(&2/(+&1'$-,/10,+1'$ ,#!20*,#$)0 0$,% + ,/ ",*-21$//$.2(/$0 1$/*(+ )$*2) 1(,+-/,&/ *02"' 0 ,/$.2(3 )$+1,/%2/1'$/(+%,/* 1(,+",+1 "1 1 01,/* $"'+,),&($0+" ,4+$/(3$,)2*!( $)$-',+$
Device Cable and Adapter Combination
DEC VT100 (direct) BM85 – W953 – 25F25F – VT100
DEC VT100 (modem) BM85 – 25F9M – W978 – modem – modem – W978 – 25F25F – VT100
IBM AT (direct) BM85 – W952 – IBM AT
IBM AT (modem) BM85 – 25F9M – W978 – modem – modem – W978 – 25F9F – IBM AT
IBM XT (direct) BM85 – W953 – 25F25F – IBM XT
IBM XT (modem) BM85 – 25F9M – W978 – modem – modem – W978 – 25F25F – IBM XT
Device Cable and Adapter Combination
P230 (direct) BM85 – W953 – P230
P230 (modem) BM85 – 25F9M – W978 – J478 – J478 – P230
IBM AT BM85 – W952 – IBM AT
IBM XT BM85 – W953 – 25F25F – IBM XT
Modvue BM85 – W952 – J347 – Modvue
DEC VAX BM85 – 25F9M with following signals crossed: TX/RX, RTS/ CTS, DTR/DSR – VAX
Device Cable and Adapter Combination
984A/B/X BM85 – W953 – 984
584 BM85 – 25F9M – W190 – 584
884 BM85 – X25F9M – W807 – 884
Micro 84 BM85 – X25F9M – W807 – J375 – Micro 84
484 BM85 – 25F9M – W978 – J478 – J474 – 484
J478 modem BM85 – 25F9M – W978 – J478 – J478 – Controller


Figure 25 Modbus/RS232 Cable Wiring Diagrams

! # ! ! "! ! $

NW–BM85–000 Panel or Shelf 115/230 Vac Single Modbus ASCII or RTU
NW–BM85C002 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85D008 19 in Rack 125 Vdc or 24 Vdc Single or Dual Modbus ASCII or RTU
NW–BM85E232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85D002 19 in Rack 125 Vdc or 24 Vdc Single or Dual RS232 Programmable, User Defined
NW–BM85S232 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS232 Programmable, User Defined
" $ ! " ! ! " ! ! % " ! % " !%

Figure 26 Serial Ports Pinout – Modbus/RS232


Modbus Plus Network Cable
NW–BM85E485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
NW–BM85S485 Panel or Shelf 115/230 Vac or 24 Vdc Single or Dual RS485 Programmable, User Defined
" +( )!&-)*! '"% &% " +(*"&% &(*! '&(* &%% *&() .&+( (" *"% # ) &(.&+(''#" *"&%*! '% # &%% *&(")
! & +)#+)"%#"% &%% *&('(*%+$ ( ")% '*# )+)*"*+* &(% # &%% *&(&+) & +) #+) * ($"%*"% &%% *&( "% *!") ''#" *"&%
5 4 3 2 1
9 8 7 6
Figure 27 Serial Ports Pinout – RS485
Pin BM85 Direction Purpose
1 –– Chassis ground
2 In/Out Receive/Transmit A
3 In/Out Receive/Transmit B
4 ... 9 –– not used

& *% ,!,"& " , +,!, , *% !+ &* ". '** ,$1
&& ,/'*#,! " &," " ,"'&' +,,"'&& *% *'-("& ' ",+,!," &," " +,! *% ++'-* '* +,"&,"'&
% *" &,& * ' '*& '*%,"'&&, * !& " ",$ ' "& ' $(!&-% *" & '&,*'$ !* , *++ +,$"+! 1,! % *" &,"'&$,& * +&+,",-,
! +( ' ,,*&+%"++"'&"&+ *"$ , '%%-&" ,"'&+ ((*'0"%, $1 )-$,',! &-% *' ' $ % &,+",+( * + '&
"&*1" ",! +%$$ +,-&",' ,/!" ! &,&1,"% "& '& ' ,/'('++"$ +,, +* (* + &, 1.$- ' '*
." ,!,"&, * '&& ,+,/''*%'* & ,/'*#+
Bridge Multiplexer
' " '& ." ,!,"&, * '&& ,+' -+$-+& ,/'*#/",! -(,' '-*' -+ ." +'*& ,/'*#+'*-(,' '-* '* + *"$ ." +

% %$ , * * $* (%$$ *)*-%%+)"+)$ *-%(!)
broadband
$ *-%(!%##+$ * %$)# * %)+&&%(* $ #+"* &" * *($)# )) %$ $$ ")+) $ ( '+ $/ , ) %$#+"* &" . $
$ " *( " $$ "+) *%) $%(( , *
carrierband
$ *-%(!%##+$ * %$)# * % $- $ %(#* %$ ) *($)# ** +) $ ) $ " *($)# )) %$ $$ "
%##+$ * %$&* -/ *- $*-%%(#%( , )
coaxial cable
*-%%$+*%(" $- $ $$ (%$+*%( )* ) $" &* $$%+* (%$+*%( )) " " *( ) &(* )* *-%%$+*%()
( +"* &" . (#% ") $ ) #% ")%$* $+) (0 $ &&" * %$&(% (#* *$ $ & $ $*"/%$*(%"&(% )) )** ( %+() ( "&%(*) )) $ %+)"+)$% )%$"/)( '+ (
/" +$$/ ! $ $ ((%( * * %$# * % $- ) $ $ )** %$%#&+* )#* #* ","+ ( , (%#* (# )%$* $*)$) $) *)$ " $* (# ( , $ )** %$( %#&+* )* ,"+ ) *( , )* (# $ %#&( ) **%* ( , ,"+ * *-%,"+ )( '+"* (# )))+# *% , $( , - * %+* ((%(
$ (# %$* $ $ **% *($) (( *- $ , )
$* #% "* "/ (* *&(%, )) (, ) %(*($) (( $ (# )% * *- $$% )% $ *-%(! $ /* )*$( ** )"/ () $ $ , )) #" )* $*% # )) &! *- * ( )) )$ $ %(#* %$ %( ((%( ! $ $" )*%! $) %( )) $ * $ *-%(!$) $)* &! **%* /) "/ ( %(*($)# )) %$*)*-%"% " $* * )( * $ )+"/ () $

DIO Drop Adapter
Distributed I/O
%# %# $' " $$ ##$# "'" ! $#$$ "#! )# "+#! $" !%$**%$!%$ $" $#$# %#$" !" ## $' " # " " $" " " %# %# $' " !$ % $$ !"$##$ #$" $" $ $' " $' " # # " " !$"# ! $$" $! $#$#!$ # !"# $ $' " ( ###%" $!## $ " #
$" #" !" " " &$ $" "(%$
drop cable
%#$ $ $' " &$ $! $ $"% " ! #"& &" %# $#"
" "&$'%# ' $'# #$
end delimiter
$$ #$ ##
EIA
$" %#$"### $
field
" %! $% %#$#$$ &) " $ #%#$#$"$ " ## "##$ " "" "
" %! $% %#$# "$" # ## ##
$$#%#$ $" '$"" '#"& ""$ )
Glossary 91 890 USE 103 00 890 USE 103 00

)+-( -" "(,- (&).- +, . +,-+. -.+ -"-%#'$, -+',-- (++ #/ - +& ,-())+()+#- )+#(+#-2*. . , +& , +#)-(+, ('-#' +& )+& - +, +& ,--., ' )(#'- +,
-2) ( -#').-+ #/ 2'( .,#'! + () - -+', +,( ,.,#'! + () ' (' #!.+ -(+ #/ .)-( 4 #-0(+ ,( %( %').- - +(& "( .)-( ,(.+ '( ,.)-(&1#&.&-(-%( 0(+ ,' ('! - +(& ",(.+ '( ' #' 1 #'-(.)-( #!"- # % , (+ %#/ +2 #'-(, )+- - ,-#'-#(',#'-" + #/#'!'(
-2) ( -(.-).-, '- 2'( .,#'! + () --+', +, ( ,.,#'! + () ' (' #!.+ -(, ' .)-( 4 #- 0(+ ,( %( %.-).- -0"# "#,!%( %%2 +( ,--(%% -#/ '( ,('-" ' -0(+$ ,-#'-#(''( , ' (' #!.+ -( )-(+#!'(+ #' ('! - +(&,) # # ,(.+ '( ,
#!"4% / % -#'$ ('-+(%" )+-( -" /# -"-) + (+&, -" )+(-( (%, (+ #'#'!-" !#''#'!' ' ( +& ,2' "+('#3#'!-" +& -0 ', ' +' + #/ +)+(/# #'! ++(+ " $#'!' #'#'!-" )(+-#('( -" + #/ #' (+&-#('-"-#,-( " $ 2-"
(&).- +0"# " ('-+(%,(-" + (&).- +,' /# ,'' #' .,-+#%)+( ,,0#-"' -0(+$#'!-" "(,- (&).- +,) # # ,-" .++ '-+ *.#+ & '-, (+-" () +-#('( + &(- '( ,' #,-" ,-#'-#(' (+,.&&+2 -+ )(+-, (.--" ) + (+&' ( -" )+( ,,
'- +'-#('%% -+# % (&&#,,#('
IEEE
',-#-.- ( % -+# %' % -+('# ,'!#' +,
ISO
'- +'-#('%-' + ,+!'#3-#('
92 Glossary 890 USE 103 00

" %'*"% ! !'%"!!' "!") & !* ' & '%!&%%* ' "('' (&"#( " (! ' "!&&%) & "(& (& &!+ # " "%"!'%" !! "! '"% ! !(&'% #%"&&&
!' " #"%' "!"' &'%('(%") * #%") & !&%) &"%' '%!&%% !" !"% ' "! !
" ! "!'%" #%'"' ) ' '#%"% &' #%"'"" &"% !' , !(&%&"' !'*"% !"%#%") ! % % )%, ! &' % !! ! " &&&
( "% && "!'%" #%'"' ) ' ' #%"% &' #%"'"" &"%& % !' !'*"% * ' "' %) & ! &' $(( !!'%!& && "!""('" ! ) &&&%&&%"! ' "!"% !" ! &&&! %&" (' "!"&&"!'!' "!&
!('(% ! ('" ' "!%"'"" !'*"% #%"'"" ' ' "*&) &"% &* ' !! !(&'% !) %"! !''" " (! '* ' "' %
!'*"% ) * "!'%" &"' %) &'"* ' "!!'& ' ! ' '&'%!&' "!&!& ( &!'%!& '& '& &'"& ))
!' % &,&' ' !'*"% '#&"!!'"%&! '% !'"%&
Modbus
! !(&'% !'*"% !&,&' ' '(&&&% &'%-& )" (! ' "!&'''%!&%%'&"(#'" (
! !(&'% !'*"% !&,&' ' '(&&'" !-#&& ! #%-'"-#%" (! ' "!&'''%!&%%'&""! '& #%&"! !'*"% ( && '* &'-# %

$"#! #& ! "("# ##$""# * "" !*# * ! $ # "###! "!!#" % #" !" #& ! $ " '
$# ! $# !%## # "## ! #! " "" " # ! # " $# " "!%! # # !$""##
#! # %""! # # ! # ! $ # $"$"#%""! # "" # ! # " $ #"" ! " """
!&! $##" $ #!! ! #! ! $ # # #! ! %!# $ #"# # $"$" #& ! ! %"# #! # ! $ # #& # #! !" # ! ! # %" # #& !
%##"!# # ""# $ # " #& ! $"$" (%##" ("( #& !
("# " #! # !! "# ! "! #! $! ! ! %" !# $ # ! $(# #! # # !" ! )#
# !*# * ! $ # #& #& ! %" "#! "!!" !# # "" # " #& " """## # #& !" !""" $ $!# #! " ### " # !## """ $!# '#!##! # "!"#$ !! #! "!"" !# #! # $!# # $ $" ! " "#(!#% # #& ! $! " ! $ # #! "#$! # """

#!!)" ( #"(+""(+#& * ' "+ "-* " " ( (((&"'& !( #)'-* '#"#&! " (#( # '#( !( #)'#"#)' )'
"( !# ( -&( ($* '( $ -' #""( #" "' " " !"'(+""#'#"(+#& "-( '("&
,(&" #""(#&#"* (+ ( "(+#& ' ((
protocol
'(#&) ')'!)() --(+##&!#&* '(# #!!)" (
Repeater
# #"* ( ( "(&#""('(+#'( #"'##)' )' "(+#&
routing path
"#)' )'( '%)"#* "#&'''( ) + !'' + )((# (' " '( "( #"
"#)' )'!'' &! )$# *-('( ('$ - ( &'''#( * ' "( !'' )( " $(
" '("&( ( "'' " &%) &!"('" #""( #"'#&'& (#!!)" ( #"' &(& .-' " + &'#&(&"'! ((("& *(
" '("&( ( "'' " &%) &!"('" #""( #"'#&'& (#!!)" ( #"' &(& .- "$ + &'#( (&"'! (("& *(
#"( )#)' )$ " # ' !"('(# ( &+ ( ( &"# * '#""( &( -(##&!' " $( ( (#'"#($'' ( ) "-$(& ! " !)! " ( #'( #"" /(/!( '!'#"' !"( !, !)! " ( " ( !"'( #"')$$#&(')$(#"#'

#! "( #"# #"( ")#)' " ( #(&)" #""( " $ ($' ( (+#($' "( $ '(+"( (+# ($'"( &"#* '"#&!#&' !"('#&!'( #" #( "(+#& "
"#!!)" ( #"$#&((+ ( '(&"'&&#" (( ( !
slave
"(+#& * + '#"( -"#( &* * * '#"#( " ( (((&"'( #"' -&'$#"(# #!!"'#&&%)'(' " ( (-!'(&*
!#)"(#( !&$&'"( " ( +#&'('( !"-'(( #" #"( "(+#& !)'(+ (#&&'$#"'!"#( &'(( #"( ' ')$#"( &'$#"'( !#( "(+#& '' #+'('(( #"" ( )'$$ ( #" -
(-$#( "$)(& *-"#)' " $( (&"'&'#')' " $"#" )&(#& *)$(# / (+#&'#$ "$)((! #)$(# '#)& "#')$(#!, !)!(#( # +#&'#'" #" )&(#$(#& "#& "#! " (!'$ '#)& "#'
(-$#(#)($)('"(-"#)' " $((&"'&' #')' " $"#" )&(#'")$(# / ( +#&'#$ )($)(((# #)$(# '( "( #""#' )$(#!, !)!(#( # +#&'
$'' ** ( ( #+' (#)( "(#!) ( $ $( ' + ( ''"( -%) ' " !$ () " $( #()'+ ( #)' )'
( ( "'( '(&(#&!#)&& " (&( ' " '"(("'-" " .-( & * " "#

!
!
! !



),.3* * , ' . , ') & 0 0$ , --* , ' . , *,)", '' & ') &- )(!$"/, .$)()0 ,0$ 1 ') , +/$, +/$*' (.
B
!),) /-*),.') &- !),*,)", '' & ') &-
0 $& & ') &- $(.,) / .$)( ) /-*),.') &- *,)", '' & ') &- -* $!$ .$)(-
, %')/(. ') &- -# &!* ( &') &- )1(&) $("
,,), ) - (),' &$( $ .$)(- *, * ,$(".#
!),- ,$ &*),.- ( .1),% )(( .$)(- *)1 , )(( .$)(- - ,$ &*),. )(( .$)(- 1$,$(" $ ", '- )(!$"/, .$)(
)(!$"/, .$)()0 ,0$ 1 0 &)*' (.-)!.1 ,
0 $& $&$.3 - ,$*.$)( $(-. &&$(" * ,.(/' ,- !$& )1(&) $(".) ) /-*),.') &-
I $( $ .),-
)'' ( - )''/($ .$)(-* , ' . ,- )(!$"/, .$)()0 ,0$ 1 ! /&.- ..$("- 0$ - ( & - $(%$' )/.* , ' . , ) /- , -- * ) '))-. ,* , ' . , *),.* , ' . ,- ),.,$),$.3* , ' . ,
) /- ( ,$ &),.-. ./- ) /-&/-( .1),%-. ./- )1 , ( 3-. ./-
Index 890 USE 103 00 99

R ( ('% #,! - $&
& +)'&(*$& #) '(& ($$# $& #)
S )( %)& +)'&(*$& #)
+)*&$ ( (,! $&+%*!% $ * & )
&(!/&%#$&+%*!% &, (,! - ("$&+%* $& #) ) # '% #$& #) , (*!#$&+%*!%
)( % )( % )( % ) (!#'&(*# )&%% *!% ) (!#'&(*)
,! )% # ) & +)'!%&+* '!%&+* )!# %*$)* ('&(* )' ! !*!&%)
O &' (*!% '&- (
&%% *!&%) &%% *!% &%% *&(#.&+*)
& +)'&(*$& #) '(& ($$# $& #)
&%% *!&%) &, (,! - &, (,! - $& #)
T *&' (&%*,! - ("$&+%*$& #) ) # '% #$&+%*$& #)
890 USE 103 00 Index 100
Wat de op het display getoonde foutcodes betekenen en hoe u ze wist.
| Code | Betekenis | Oplossing | |
|---|---|---|---|
| 11 | PROM checksum error | p.64 | |
| 12 | RAM data test error | p.64 | |
| 13 | RAM address test error | p.64 | |
| 14 | Normal power down event | p.64 | |
| 17 | Bad or unexpected interrupt | p.64 | |
| 18 | EEPROM checksum error | p.64 | |
| 19 | Modbus port loopback error | p.64 | |
| 24 | Modbus transmit state error | p.64 | |
| 25 | Modbus receive state error | p.64 | |
| 26 | ASCII transmit communications state error | p.64 | |
| 27 | Transmit underflow error | p.64 | |
| 28 | RTU transmit communications state error | p.64 | |
| 29 | ASCII receive communications state error | p.64 | |
| 2A | RTU receive communications state error | p.64 | |
| 2B | Transmit communications state error | p.64 | |
| 2C | Receive communications state error | p.64 | |
| F1 | BM85 kernel is reloading | p.77 | |
| F4 | Program or task returned to BM85 bootstrap | p.77 | |
| F8 | Program or task called abort() | p.77 |
Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.
Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.