Operating Instructions Edition: AB simovert A ctive Front End (AFE) A FE Rectifie r / Regenerative Feedback Unit AC-DC Chassis Type G and J 400 V / 210.
The reproduction, transmission or us e of this document or its con- tents is not permitted without ex press written authority . Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
01.2004 Contents Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 1 Content s 1 DEFINITIONS AND WARNINGS ..................................................................... 1-1 2 DESCRIPTION ............................
Contents 01.2004 6SE7087-6CX86-2BA1 Siemens AG 2 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.4 Connecting up cont rol cabl es ......................................................................... 7-12 7.5 Terminal assi gnments .............
01.2004 Contents Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 3 12.11 Diagnostic functions ...................................................................................... 12-31 12.12 Gating uni t ..............
Contents 01.2004 6SE7087-6CX86-2BA1 Siemens AG 4 Operating Instructions SIMOVERT MASTERDRIVES AFE 16 FORMING ....................................................................................................... 16-1 17 TECHNICAL DATA ...............
01.2004 Definitions and Warnings Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 1-1 1 Definitions and W arnings For the purpose of this documentation and the produ ct w.
Definitions and Warnings 01.2004 6SE7087-6CX86-2BA1 Siemens AG 1-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Hazardous voltages are pr esent in this electrical equipment du ring operation. Non-observance of the warning s can thus result in severe personal injury or property damage.
01.2004 Definitions and Warnings Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 1-3 Components which can be destroyed by electrostatic discharge (ESD) The board contains component s which can be destroyed by electrostatic discharge.
Definitions and Warnings 01.2004 6SE7087-6CX86-2BA1 Siemens AG 1-4 Operating Instructions SIMOVERT MASTERDRIVES AFE Safety and Operating Instructions for Drive Converters (in conformity with the lo w-voltage d irective 73/23/EEC) 1.
01.2004 Description Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 2-1 2 Description The AFE (Active Front End) rect ifier/re generativ e feedback units belonging to the SIMOVERT MASTERDRIVES AFE series are power electronics devices that are available a s cabinet units, as chassis units and as compact units.
Description 01.2004 6SE7087-6CX86-2BA1 Siemens AG 2-2 Operating Instructions SIMOVERT MASTERDRIVES AFE On the 3-phase end, a mains angle- oriented high -speed vector control is subordinate to the DC l.
01.2004 Description Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 2-3 Both one and several inverters can be conne cted to the output. The maximum connected power of the inverters may amount to 4 times the rated power of the AFE inverter.
01.2004 Initial Start-Up Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 3-1 3 Initial S t art-Up After remov ing the packaging, check th at the unit is intact and undamaged. Only int act units may be st arted up. Plea se also check t hat all th e necessary option boards ar e present and cor rect.
Initial Start-Up 01.2004 6SE7087-6CX86-2BA1 Siemens AG 3-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Carry out the basic function check See chapter entitled "Basic function check" It must be ensured that no danger for persons and equipment c an occur by energizing the power and the unit.
01.2004 Transport, Storage, Unpacking Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 4-1 4 T ransport, S torage, Unp acking The units and component s are packed in the manufacturing plant corresponding to that specified when ordered.
Transport, Storage, Unpacking 01.2004 6SE7087-6CX86-2BA1 Siemens AG 4-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Line-side components: 1. AFE reactor 6SE7036-0ES87-1FG1 2.
01.2004 Transport, Storage, Unpacking Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 4-3 AFE i nv e r t e r CU SA control /c ontrol sect i on 6 -L2 -C 4 ..C 5 L1 -K 1 -K 4 -R 1..R 3 VSB AF E reactor E box: opti o ns -R 7 .
01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-1 5 Inst allation 5.1 Installing the units Safe converter operation requires that the equipment is mounted and commissioned by qualified personn el taking into account the warning information provided in these Operating Instruction s.
Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 5.2 Mounting dimensions and dimension sheets 5.
01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-3 5.2.2 Mounting dimensi ons of AFE reactor a 2 n 2 b h 2 h 3 h 1 a 1 a 1 n 1 l d 2 d 2 d 1 d 1 Fig.
Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 5.2.3 AFE inverter (construction type G) H h 350 b aa B c Type G a b 119 270 B 508 H 1450 c2 5 h 1375 Mounting surfac e Cutouts fo r M8 scr ew Dimen- sions [mm] Side v iew Front v iew Fig.
01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-5 Partitions should be executed up to the cabinet fram e and should be designed in such a way that the di scharged air flow is taken around the cabinet beams and not pressed into the m.
Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-6 Operating Instructions SIMOVERT MASTERDRIVES AFE The following filter mat is approved for use: FIBROIDELASTOV made by DELBAG-Luftfilter GMBH Tech.
01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-7 The units with water cooling (MLFB Annex: -1AC0 ) are suitable for installing in an enclosed cabinet (IP5 4). The mains filter connection module is identical for water and air cooling.
Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-8 Operating Instructions SIMOVERT MASTERDRIVES AFE 5.2.4 AFE inverter (construction type J) Si de v ie w Front view 550 b 800 213 483 708 h H [mm] .
01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-9 If the units are operated with an arcing s hort-circuit, this will result in the failure of the units or in their destruction! An arcing short-circuit must be pr evented by the prov ision of partitions.
Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-10 Operating Instructions SIMOVERT MASTERDRIVES AFE The following filter mat is approved for use: FIBROIDELASTOV made by DELBAG-Luftfilter GMBH Tec.
01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-11 MLFB 6SE7035-1TJ80 6SE7036-0TJ80 Fan 2 x RH28M Minimum flow rate [m3/s] 0.46 Min. opening cross-section in cabinet doors [m2] Degree of protection IP00 to I P42 0.
Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-12 Operating Instructions SIMOVERT MASTERDRIVES AFE Inverters with water cooling (item number suffix: -1AA0) are suitable for mounting in enclosed cabinets (IP54 ).
01.2004 Installation Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 5-13 5.3 Installing the optional boards The boards may only be replaced by qualified pe rsonnel. It is not permitted to withdraw or insert the boards under voltage.
Installation 01.2004 6SE7087-6CX86-2BA1 Siemens AG 5-14 Operating Instructions SIMOVERT MASTERDRIVES AFE The optional boards contain compone nts which could be damaged by electrostatic discharge. These comp onents can be very easily destroyed if not handled with caut ion.
01.2004 Installation in Conformance with EMC Regulations Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 6-1 6 Inst allation in Conformance with EMC Regulations The following contains a summary of general informat ion and guidelines which will make it easier for you to comply with EMC and CE regulations.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 7-1 7 Connecting-Up and Wiring SIMOVERT MASTERDRIVES converters are operated at high voltages.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.1 Connection overviews 7.1.1 AFE basic mains modul e and CleanPower filter AF E re.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 7-3 7.1.2 AFE Inverter construction type G PE/GND Electro nics box for boards CUSA -X101.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.1.3 AFE Inverter construction type J 3AC connection for AFE reactor Fan connection.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 7-5 7.1.4 Overview of core and system components for AFE functionality with example conf.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-6 Operating Instructions SIMOVERT MASTERDRIVES AFE AFE inverter order number / rating Input current Mains fuse 3AC Utilization category.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-7 -K4 -X2: U2 V2 W2 C/ L+ 3PE AC380-460V 50/60Hz L1 L2 L3 PE1 -Q1 < 8 > -F1...3 6 5 4 3 2 1 < 12 >: Power con nection 3 AC -K1 12 34 56 12 34 56 -R1 -R2 -R3 VSB3 VSB2 VSB1 -U1 < 57 > -L2 D/ L- -U1-X1: -F41.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-8 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.2 Power connections The connection cross-sect ions are determined for copper cable s at 40 °C (104 °F) ambient temperatu re (according to DIN VDE 0298 Part 4 / 02.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-9 7.2.2 Auxiliary powe r supply, precharging The 5-pole terminal strip is used for connectin g up a 24 V voltage supply and for connecting a pre charging contactor.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-10 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.3 Control terminals 7.3.1 Standard connections of the AFE inverter The basic vers.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-11 -X100 -X101 -X102 PMU Fig. 7-8 View of CUSA X1 00 ≥ 1 1 2 3 4 5 6 7 8 9 PM U X3 00 RS485N RS485P 1 2 3 4 5 X1 01 13 14 15 16 17 P24 M M 5V 24V 5V 24V 5V 24V 5V 24V 5V 24V 18 19 20 X1 02 25 33 34 D A AO 0.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-12 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.4 Connecting up control cables Generally, control lines that are co nnected to the AFE inverter must be shielded to achieve maximum possible interferen ce immunity.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-13 The terminals on the control terminal stri p are as follows: Terminal Name Function Range 13 P24 AUX Aux.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-14 Operating Instructions SIMOVERT MASTERDRIVES AFE The terminals on the control terminal stri p are as follows: Terminal Name Function.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-15 A serial connection to an automation uni t or PC can be made via connector X300 on the PMU. The unit can therefore be controlled and operated from the central contro l station or control room.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-16 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.6 Digital inputs/output s Four parameterizable digital inputs (24 V) are avail able on the control terminal strip (-X101) of the CUSA board.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-17 The USS protocol (universal serial interface ) is implemented on the basic converter interface SCom1.
Connecting-Up and Wiring 01.2004 6SE7087-6CX86-2BA1 Siemens AG 7-18 Operating Instructions SIMOVERT MASTERDRIVES AFE 7.7 V oltage Sensing Board (VSB) The supply voltage is sensed usi ng the analog board VSB (Voltage Sensing Board) via the two anal og inputs on control b oard CUSA.
01.2004 Connecting-Up and Wiring Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructi ons 7-19 VSB X3 -15-V output 10 CUSA Do not connect Line voltage component V sa 9 X102:27 Analog input 1 Line voltage component V sb 8 X102:30 Analog input 2 Ex t.
01.2004 Basic Function Check Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 8-1 8 Basic Function Check It imperative to observe the procedure described here for initial commissioning of the equipment.
Basic Function Check 01.2004 6SE7087-6CX86-2BA1 Siemens AG 8-2 Operating Instructions SIMOVERT MASTERDRIVES AFE ♦ Main contactor -K1 and prech arging contactor -K4 must be op en ♦ Main switch must.
01.2004 Basic Function Check Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 8-3 Issue the ON command via PMU (by def ault, ON command P554 already s et on PMU) ♦ Reac.
Basic Function Check 01.2004 6SE7087-6CX86-2BA1 Siemens AG 8-4 Operating Instructions SIMOVERT MASTERDRIVES AFE → After successful precharging and a ctual value check P561 = 1 ♦ Reaction: The AFE inverter pulse is audibly and evenly The DC link voltage (r006) goe s to the value P071 x P125, and is stable with slight fluctuations ± approx.
01.2004 Explanation of Terminology and Functionality of the AFE Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 9-1 9 Explanation of T erminology and Functionality of th.
Explanation of Terminology and Functionality of the AFE 01.2004 6SE7087-6CX86-2BA1 Siemens AG 9-2 Operating Instructions SIMOVERT MASTERDRIVES AFE These parameters are divided into vario us "indices" (i001, i002, etc.). A separate parameter value can be assigned to ea ch index.
01.2004 Function Diagrams Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 10-1 10 Function Diagrams Line synchronization Analog input 1 Vsa Analog input 2 Vsb Line filte.
Function Diagrams 01.2004 6SE7087-6CX86-2BA1 Siemens AG 10-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 0 1 2 3 ... ... ... ... Content of parameter 001 0 CU-AA act.
01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-1 11 Parameterization The functions stored in the converte rs are adjusted to suit specific applications by means of parameters. Every param eter is uniquely identified by its name and number.
Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 11.1 Setting p arameters via the PMU The parameterization unit (PMU) is p rovided for direct parameterization, operation and visuali z ation of the converter/inverter.
01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-3 Since the seven-segment display on t he PMU has onl y four digits, the 3 descriptive elements of a parameter, i.
Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-4 Operating Instructions SIMOVERT MASTERDRIVES AFE The following example shows the sequence of operat or inputs via the PMU required to select operating m ode "Reactive power compensation".
01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-5 11.2 "S tart-up" parameterization P050 = Select language: 0 = Deutsch , 1 = Engli.
Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 11.2.1 Function selection (P052) Start-up functions are selected via parameter P052 . These provide start-up variants specially adapted to start-up mode.
01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-7 11.2.3 Initialization (ML FB input) (P052 = 2) This function is used to alter the order number (device type) of the converter.
Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-8 Operating Instructions SIMOVERT MASTERDRIVES AFE P052 = 0 Select "Return" The operating display appears and, if the MLFB has been .
01.2004 Parameterization Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 11-9 11.2.5 Hardware conf iguration (P052 = 4) The purpose of this function is to define option bo ards (SCB, TSY, CB, TB) installed in the electron ics box of the converter.
Parameterization 01.2004 6SE7087-6CX86-2BA1 Siemens AG 11-10 Operating Instructions SIMOVERT MASTERDRIVES AFE P052 = 5 Select "Closed-loop control settings" (see Sect ion "Closed-loo p control s ettings") P052 = 0 Select "Return" The operating display (r000) appea rs.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-1 12 Parameter List General Visualization Parameters to 49 Analog Input/Output from 650 General.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.1 General visuali zation pa rameters PNU *:conf-P Parameter Name in OP1 Description Range .
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-3 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory .
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.2 General parameters PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Tex.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-5 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P053 * 35Hex Parameter access Release of interfaces for parameterization.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.3 Drive data PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P070 * 46Hex MLFB(6SE70.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-7 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P081 51Hex Line filter L/mH Inductance L of AFE filter reactor in mH.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-8 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.4 Hardware configuration PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-9 12.5 Closed-loop control PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P120 78Hex CosPhi set Power factor cos(PHI) setpoint.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-10 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-11 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P155 9BHex max. t. pow.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-12 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P173 ADHex Imax Maximum current (fundamental r.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-13 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-14 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.6 Functions PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of .
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-15 12.7 Setpoint channel PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P443 * 1BBHex Src.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-16 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P517 205Hex SetActValDev.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-17 12.8 Control and st atus bit connections PNU *:conf-P Parameter Name in OP1 Description Rang.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-18 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-19 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-20 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P578 * 242Hex Src.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-21 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-22 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-23 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P618 * 26AHex DstCurrLimAct.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-24 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-25 12.9 Analog inputs/outputs PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-26 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-27 12.10 Interface configuration PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Va.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-28 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-29 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-30 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-31 12.11 Diagnostic functions PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-32 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r725 2D5Hex CalcTimeHeadroom Available CPU computation time reserve on CUSA as % of total computing power.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-33 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-34 Operating Instructions SIMOVERT MASTERDRIVES AFE 12.12 Gating unit PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r764 2FCHex Modulation Depth Control factor of closed-loop control for gating unit.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-35 12.14 Profile parameters PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value T.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-36 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-37 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ P952 * 3B8Hex # of Faults Number of faults Contains the number of fault events stored in the fault memory (max.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-38 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
01.2004 Parameter List Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 12-39 PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory.
Parameter List 01.2004 6SE7087-6CX86-2BA1 Siemens AG 12-40 Operating Instructions SIMOVERT MASTERDRIVES AFE PNU *:conf-P Parameter Name in OP1 Description Range [Unit] Value Texts # of Indices Factory Settings read: _/_ write: _/_ r986 3DAHex Par # List Pt7 List of available parameter numbers, part 7 See r980.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-1 13 Control and S tatus W ords 13.1 Control word Operating states can be read in vi sualization paramet er r001: e.g. READY FOR ON: r001 = 009 The functional sequence s are described in the order in whi ch they occur.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-2 Operating Instructions SIMOVERT MASTERDRIVES AFE ♦ Multiple connections are permitted! ♦ The control word commands "OFF2 .
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-3 13.1.2 Control word 1 (visualiz ation parameter r550 or r967) The factory setting applies only when P077 = 0. Designation High / Low values Parameter No.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-4 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.1.3 Control word 2 (vis ualization parameter r551) The factory setting applies only when P077 = 0. Designation High / Low values Parameter No.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-5 13.1.4 Sources for control words 1 and 2 Table X (external terminals) 1001 BE1 term.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-6 Operating Instructions SIMOVERT MASTERDRIVES AFE Table A 0000 Constant value 0 1010 PMU o p erator p anel 2001 SCom1 word 1 3001 CB/.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-7 Table E 0000 Constant value 0 0001 Constant value 1 1010 PMU o p erator p anel 2001.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-8 Operating Instructions SIMOVERT MASTERDRIVES AFE Table I 0000 Constant value 0 0001 Constant value 1 2004 SCom1 word 4 3004 CB/TB wo.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-9 13.1.5 Description of t he control word bits Bit 0: ON / OFF1 command ( ↑ "ON") / (L "OFF1") Positive edge change from L to H (L → H) in READY FOR ON (009) state.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-10 Operating Instructions SIMOVERT MASTERDRIVES AFE Bit 7: Acknowledg e command ( ↑ "Ackno wledge") Positive edge change from L to H (L → H) in FAULT (007) stat e. ♦ Reset all current faults after they have been transferred to the diagnostics memory.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-11 Bit 11: Reserv ed Bit 12: Regenerativ e feedback enable command (H "Regenerative feedba ck enable") HIGH signal ♦ Regenerative feedback o peration is enabled.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-12 Operating Instructions SIMOVERT MASTERDRIVES AFE Bit 21: Reserv ed Bit 22: Reserv ed Bit 23: Reserv ed Bit 24: Reserv ed Bit 25: Re.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-13 Bit 30: Select reserve/basic setting (H "R eserv e setting") / (L ".
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-14 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.2 S tatus word Status words are proce ss data as def ined by the explanation in Section "Process data".
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-15 Bit # Value 1 = High Select Value Destin ation 0 = Low destin. Bit 0 1 Ready for ON P600. x 0 Not ready for ON x = 1 0000 No destinati on Bit 1 1 Ready to RUN P601.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-16 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.2.2 Status word 2 (vis ualization parameter r553) PMU display "Status word.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-17 Bit # Value 1 = High Select Value Destination 0 = Low destin. Bit 16 Reserv ed x = 1 0000 No destination Bit 17 Reserved 1001 Assigned Bit 18 2) 1 Current limit ac tive P618.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-18 Operating Instructions SIMOVERT MASTERDRIVES AFE 13.2.3 Description of t he status word bits Bit 0: "Ready for ON" signal (H ) STARTING LOCKOUT (008) or READY FOR ON (009) state ♦ The power supply, open-l oop control and closed -loop control are all operative.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-19 Bit 6: "Starting lockout" signal (H) STARTING LOCKOUT state (008) ♦ The power supply, open-l oop control and closed -loop control are all operative.
Control and Status Words 01.2004 6SE7087-6CX86-2BA1 Siemens AG 13-20 Operating Instructions SIMOVERT MASTERDRIVES AFE Bit 13: Reserv ed Bit 14: "Motor operation" signal (L) AFE operates in r.
01.2004 Control and Status Words Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 13-21 Bit 23: "AFE overtem perature fault" signal (H) "Inverter temperature too high" fault (F023) ♦ The inverter temperature limit value has been exceeded.
01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-1 14 Fault s and Alarms 14.1 Faults General information about faults The available informati.
Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Fault messages No. Descrip tion of fault Remedial measures F006 DC-link overvoltage The drive has been shut down due to an excessive DC- link voltage.
01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-3 Fault messages No. Descrip tion of fault Remedial measures F025 UCE Ph. L1 A UCE shutdown has occurred in phase L1 Check • phase L1 for short circuit or earth fault (-X2:U2 - including motor).
Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-4 Operating Instructions SIMOVERT MASTERDRIVES AFE Fault messages No. Descrip tion of fault Remedial measures F046 Par.con. Switch the device off and on again. Replace the CUSA (-A10) board. F047 Int.
01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-5 Fault messages No. Descrip tion of fault Remedial measures F076 Aninput1 SL2 Amps at analog input 1, sl ave2, have dropped below 4mA Check connection from signal source to SCI1 (slave1) -X428:4, 5.
Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 14.2 Alarms An alarm message is periodically displayed on the PMU by A=alarm and a 3-digit number. An alarm cannot be acknowledged. It is automatically deleted once the ca use has been rem oved.
01.2004 Faults and Alarms Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 14-7 Alarm messages Ala rm No. Param- No. Bit No. Description Remedial measures A039 P955 6 Electrical off The electronics voltage supply is not o.
Faults and Alarms 01.2004 6SE7087-6CX86-2BA1 Siemens AG 14-8 Operating Instructions SIMOVERT MASTERDRIVES AFE Alarm messages Ala rm No. Param- No. Bit No. Description Remedial measures A065 P957 0 WEA active The WEA option (P366) restarts the drive. No time monitor is activated when the DC link is precharging.
01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-1 15 Maintenance SIMOVERT MASTERDRIVES units ar e operated at high voltages. All work carried out on or with the equipment mu st conform to all the national electrical codes (VBG 4 in Germany).
Maintenance 01.2004 6SE7087-6CX86-2BA1 Siemens AG 15-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 15.1 Electrical components 15.1.1 AFE basic mains module Position Equipment designation Brief de.
01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-3 15.2 AFE inverter maintenance 15.2.1 Replacing the fan The fan is designed for an operating time of L 10 ≥ 35 000 ho urs at an ambient temperature of T u = 40 °C.
Maintenance 01.2004 6SE7087-6CX86-2BA1 Siemens AG 15-4 Operating Instructions SIMOVERT MASTERDRIVES AFE ♦ Disconnect the cable conn ections and terminals o n the fan. ♦ Remove the fan support plate from the fan assembly and deta ch the fan from the support plate.
01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-5 15.2.4 Replacing the capacitor battery The unit is an assembly which consists of the DC link capacitors, the capacitor support and the DC link bus module.
Maintenance 01.2004 6SE7087-6CX86-2BA1 Siemens AG 15-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 15.2.5 Replacing the PMU ♦ Remove the grounding cable on the si de. ♦ Press the spring catches o n the adapter section caref ully together, remove the PMU with adapter from the e lectronics box.
01.2004 Maintenance Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 15-7 15.3 Fuses 15.3.1 Fan fuses for AFE inverters Line voltage 3AC 380 V to 460 V Order No. 6SE70.. Fan Fuse (F101 / F102) 35-1TJ80 FNQ-R-5 36-0TJ80 FNQ-R-5 Order No.
01.2004 Forming Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 16-1 16 Forming For units in the 400 V and 690 V voltage classes (cf. 9th digit of the MLFB, letter E or H), the DC link capacitors m ust be formed again after an idle period of more than 2 years.
Forming 01.2004 6SE7087-6CX86-2BA1 Siemens AG 16-2 Operating Instructions SIMOVERT MASTERDRIVES AFE P408 Set forming time ( 60.0 to 600.0 min utes) P052 = 20 Select "Form DC link" P ke y The op erating display appears: The AFE m ust be switched on within 20 s or else a shut down on faults (F091) will occur ( fault value 4) .
01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-1 17 T echnical Dat a CleanPower filter AFE basic mains module Fig. 17-1 AFE basic mains module mounted on CleanPower filter Fig. 17-2 AFE reactor for AFE inverters 510.
Technical Data 01.2004 6SE7087-6CX86-2BA1 Siemens AG 17-2 Operating Instructions SIMOVERT MASTERDRIVES AFE 17.1 AFE basic mains module and CleanPower filter EU low-voltage directive 73/23/EEC and RL93.
01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-3 Supply system type T N-C; 3/PEN Mains voltage 3AC 400 V Mains frequency 50 Hz / 60 Hz Rated operating voltage 3 AC 380 (-20 %) V to 3AC 460 (+5 %) V) Rated current 210 A, 260 A, 315 A, 370 A, 510.
Technical Data 01.2004 6SE7087-6CX86-2BA1 Siemens AG 17-4 Operating Instructions SIMOVERT MASTERDRIVES AFE The electronic and asso ciated electrical comp onents are installed according to the recommendations of the relevant com ponent manufacturers.
01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-5 17.4 AFE inverter EU low-voltage directive 73/23/EEC and RL93/68/EEC EN 50178 EU directive EM.
Technical Data 01.2004 6SE7087-6CX86-2BA1 Siemens AG 17-6 Operating Instructions SIMOVERT MASTERDRIVES AFE 10 30 50 0 25 50 75 100 0 Cooling-medi um tem p. in ° C Permis sible rat ed current in % 20 40 Temp [°C] Derating factor K 2 50 0.76 0.879 45 1.
01.2004 Technical Data Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 17-7 Designation Value Order No. 6SE70... 35-1EJ80 36-0EJ 80 33-7EG80 33-2EG80 32-6EG80 32-1EG8 0 .
01.2004 Environmental Friendliness Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 18-1 18 Environmental Friendliness The number of component s has been significa ntly reduced over earlier converter series by the use of highly integrated com ponents and the modular design of the complete se ries.
01.2004 Certificates Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 19-1 19 Certificates Autom ation an d Dr ives Confir mation Er langen, 01. 05.19 98 This confir ms that Eq uipment AC drive conver ter • Type SI MOVE RT MASTERDRIVES • O rder No.
Certificates 01.2004 6SE7087-6CX86-2BA1 Siemens AG 19-2 Operating Instructions SIMOVERT MASTERDRIVES AFE Te st cer tif ic ate Erlan gen, 01.05. 19 98 Eq uipment • Type • Ord er No. : A C d r iv e c onv ert e r SI MOVERT MASTERDRIV ES 6SE70 ... 1) The r outine test ing accord ing t o thes e test inst ructions 475 1 00.
01.2004 Certificates Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 19-3 This declaration does not guarantee any features.
01.2004 Appendix Siemens AG 6SE7087-6CX86-2BA1 SIMOVERT MASTERDRIVES AFE Operating Instructions 20-1 20 Appendix Order number: 6SE708x-xCX86-2BA1 x-x stands for language code e.
.
.
.
nderung )%')!'%' Datum 1 Name Datum Bearb. Gepr. Norm 16.04. 2 003 Heeg 2 Urspr. SIMOVERT -MASTE RDRIVES A FE Modulare Netza nbindung 3 Ers.f. Ers.d. 4 SIEMENS AG A&D SE W KC Netzbasi smodul (315kW) Stromlau fplan 56 MLFB-Nr.
nderung )%')!'%' Datum 1 Name Datum Bearb. Gepr. Norm 16.04.2003 Heeg 2 Urspr. SIMOVERT -MASTE RDRIVES A FE Modulare Netza nbindung 3 Ers.f. Ers.d. 4 SIEMENS AG A&D SE W KC Clean Po wer Fi lter (315kW) Stromlau fplan 56 MLFB-Nr.
Siemens AG A utomatisierungs- un d Antriebstechnik Motion Control Systems Postfach 3180, D – 9 1050 Erlangen Bundesrepublik D eutschland www.ad.siemens.
Een belangrijk punt na aankoop van elk apparaat Siemens 400 V / 210...590 A (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Siemens 400 V / 210...590 A heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Siemens 400 V / 210...590 A vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Siemens 400 V / 210...590 A leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Siemens 400 V / 210...590 A krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Siemens 400 V / 210...590 A bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Siemens 400 V / 210...590 A kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Siemens 400 V / 210...590 A . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.