MICROMASTER 410 Operatin g I nstructions Issue A1 User Documentation Order number: 6SE6 400-5EA0 0-0BP0.
MICROMA STER 410 Documentat ion Getting Star te d Guide Is for quick commiss ioning. Operating Instru ctions Gives inf orm ation about f eatures of the MM410, Installat ion, Comm iss ioning, Contr ol m odes, System Param eter str ucture, T roublesh ooting , Specif ications and availab le opt ions of the MM410.
MICROMASTER 410 Operating Instructions User Docum entation Valid for Issue 10/0 1 Converter Ty pe MICROMAST ER 410 Issue A 1 Overv iew 1 Installation 2 Commissioning 3 Using the MICROMA STER 410 4 Sys.
MICROMASTER 410 Operating Instructions 4 6SE6400-5EA 00-0BP0 Further information can be obtained from Internet website: ht tp :/ /ww w.s i em ens . de/m ic r omas t er Approved Siemens Qualit y for S oft ware and Training is to DIN ISO 9001, Reg.
Issue A1 Foreword MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 5 Forew ord User Documentation WARNING Before i nstalli ng and com mis sioning the inver ter, you must read a ll saf ety instruc tions an d warn ings c arefull y inclu ding al l the warn ing l abels att ached to t he equipm ent.
Definitions and W arnings Issue A1 MICROMASTER 410 Operating Instructions 6 6SE6400-5EA 00-0BP0 Definitions and Warnings DA NGE R indicates an imm ientl y hazardo us situa tion wh ich, if not avoid ed, will r esult in deat h or serious injur y.
Issue A1 Safety Ins tructions MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 7 Safety Instructions The f ollowing W arnings , Cautio ns and Not es are provided f or your safet y and as a means of preventi ng dam age to the product or com ponents in th e m achines connecte d.
Safety Ins tructions Issue A1 MICROMASTER 410 Operating Instructions 8 6SE6400-5EA 00-0BP0 Transport & Storage WARNING ♦ Correct tr ansport, s torage, er ection an d m ounting, as well as car eful operatio n and m aintenanc e are es sentia l for pr oper and safe oper ation of the equipm ent.
Issue A1 Safety Ins tructions MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 9 Opera tion WARNING ♦ MICROMAST ERS op erate at high voltag es. ♦ W hen operating electric al devic es, it is im possible to avoid appl ying hazardo us volta ges to c ertain p arts of the equipm ent.
Safety Ins tructions Issue A1 MICROMASTER 410 Operating Instructions 10 6SE6400-5EA 00-0BP0.
Issue A1 Table of C ontents MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 11 Table of Contents 1 Overv iew ................................................................................................................ 15 1.1 The MICROM ASTER 4 10 .
Table of C ontents Iss ue A1 MICROMASTER 410 Operating Instructions 12 6SE6400-5EA 00-0BP0 8 Options ................................................................................................................... 67 8.1 Variant Inde pendent O ptions .
Issue A1 Table of C ontents MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 13 List of Ill ustrati ons Figure 2-1 Forming.............................................................................................................. ........
Table of C ontents Iss ue A1 MICROMASTER 410 Operating Instructions 14 6SE6400-5EA 00-0BP0.
Issue A1 1 Overv iew MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 15 1 Over view 1.1 The MICROM A STER 410 The MICROM ASTER 4 10s are a range of f requency inv erters f or control ling the speed of three phas e AC m otors. T he various models availa ble rang e from 120 W to 750 W single-phas e input.
1 Overv iew Issue A1 MICROMASTER 410 Operating Instructions 16 6SE6400-5EA 00-0BP0 Performance Characteristics Ø F lux Current Control (F CC) for im prove d d ynamic res ponse and m otor c ontrol Ø .
Issue A1 2 Installati on MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 17 2 Inst allation WARNING ♦ ♦ ♦ ♦ W ork on the devic e/s ystem b y unqualif ied pers onnel or failur e to com ply wit h warnings c an resu lt in se vere per sonal injur y or serious dam age to m aterial.
2 Installati on Issue A1 MICROMASTER 410 Operating Instructions 18 6SE6400-5EA 00-0BP0 2.1 General Insta lla tion afte r a P erio d o f S torag e Follo wing a pro longed per iod of storage, you m ust ref orm the c apacitors in the inverter .
Issue A1 2 Installati on MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 19 2.2 Power Losses Figure 2- 2 sho ws the power l oss f or the MICROMAST ER 410 Inverter . The graph c an be us ed to rea d the loss at f ull load of a part icular v ariant.
2 Installati on Issue A1 MICROMASTER 410 Operating Instructions 20 6SE6400-5EA 00-0BP0 Shock Do not drop the inv erter or exp ose to sudden shoc k. Do no t instal l the in verter in an area where it is lik el y to be exposed to cons t ant vi brat ion.
Issue A1 2 Installati on MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 21 2.4 Harmonic Current s Harm onic curr ents with 1% m ains im pedance.
2 Installati on Issue A1 MICROMASTER 410 Operating Instructions 22 6SE6400-5EA 00-0BP0 2.6 Overv olt age and T rip Levels The inv erter wil l protec t itself f rom both suppl y overvolta ge and undervolt age.
Issue A1 2 Installati on MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 23 30 mm 100 mm 100 mm 30 mm Figure 2-5 Clearance distances for mou nting the inverter For side m ounting and UL com plia nce the am bient tem peratur e shoul d be no greater t han 40 ºC.
2 Installati on Issue A1 MICROMASTER 410 Operating Instructions 24 6SE6400-5EA 00-0BP0 2.7.1 Mounting Brackets The MICROM ASTER 4 10 ca n be m ounted using m ount ing brac kets, wh ich are slotted i nto the heats ink at the rear of the in verter f or norm al m ounting pos ition (see Figure 2- 6 A.
Issue A1 2 Installati on MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 25 A B C D E 2.7.2 DIN Rail Mounting The DIN Rai l Mounti ng Kit c onsists of the fol lowing i tems : Ø 1 x plastic moulded base Ø 1 x plastic moulded reta ining c lip Ø 1 x Metal sprin g The DIN Rai l Mounti ng Kit is suppl ied as an option f or the in verter.
2 Installati on Issue A1 MICROMASTER 410 Operating Instructions 26 6SE6400-5EA 00-0BP0 2.8 Electrical Inst allation WARNING THIS EQUIPM ENT MUST BE GROUNDED.
Issue A1 2 Installati on MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 27 Operation with Residual Current Device If an RCD (also ref erred to as E LCB or RCC B) is fitted, t he MICROMAST ER inverter s will operate without nuisance trip ping, pro vided th at: þ A t ype B RCD is used.
2 Installati on Issue A1 MICROMASTER 410 Operating Instructions 28 6SE6400-5EA 00-0BP0 Removal of ‘Y’ Capacitor Link To use the i nverter o n unground ed suppl ies the ‘ Y’ capacitor ( cap) link m ust be rem oved as f ollows: 1. Ensure the inver ter has been disc onnecte d from all power suppl ies.
Issue A1 2 Installati on MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 29 Figure 2-9 Motor and Pow er Connections 2.8.3 A voiding Electro-Magnetic Interfer ence (EMI) The inv erters are d esigned to operat e in a n industr ial en vironm ent where a high level of EMI c an be exp ected.
2 Installati on Issue A1 MICROMASTER 410 Operating Instructions 30 6SE6400-5EA 00-0BP0 The inv erter can be screene d using the m ethodolog y shown in Figure 2- 10.
Issue A1 3 Commis sioning MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 31 3 Commissioni ng WARNING ♦ ♦ ♦ ♦ MICROMAST ERS op erate at high voltag es. ♦ ♦ ♦ ♦ W hen operating electric al devic es, it is im possible to avoid appl ying hazardo us volta ges to c ertain p arts of the equipm ent.
3 Commis sioning Issue A1 MICROMASTER 410 Operating Instructions 32 6SE6400-5EA 00-0BP0 3.1 Block Diagram Figure 3-1 Inverter bloc k diagram.
Issue A1 3 Commis sioning MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 33 3.2 Commission Modes The MICRO MAST ER 410 is suppli ed with def ault p aram eter settings c over t he follo win.
3 Commis sioning Issue A1 MICROMASTER 410 Operating Instructions 34 6SE6400-5EA 00-0BP0 3.2.1 Commissioning without an Operator Panel The inv erter is s upplie d with an L ED to i ndicate t he opera tion stat e of the unit. The inv erter can be used with its d efault s ettings , for a num ber of applic ations .
Issue A1 3 Commis sioning MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 35 3.2.3 Changing the Line Supply Frequenc y The s upply frequenc y of the inverter can be ch anged us ing either t.
3 Commis sioning Issue A1 MICROMASTER 410 Operating Instructions 36 6SE6400-5EA 00-0BP0 3.2.4.1 Commissioning with the Operator Panel The O perator Pane l (OP) provid es acc ess to the inverter param eters and e nables the user t o custom ize the settings of your MICRO MAST ER 41 0.
Issue A1 3 Commis sioning MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 37 Buttons on the Operator Panel Panel/Button Function Effects Indicates Status T he LCD displa ys the sett ings curr entl y used b y the convert er. Start motor Pressing the button st arts the c onver ter.
3 Commis sioning Issue A1 MICROMASTER 410 Operating Instructions 38 6SE6400-5EA 00-0BP0 Changing parameters with the Operator Panel The proc edure for changi ng the va lue of param eter P0004 is desc ribed b elow. Modif ying the value of an indexe d param eter is illustr ated us ing the ex ample of P2011.
Issue A1 3 Commis sioning MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 39 NOTE In som e cases - when chang ing param eter values - t he dis pla y on the Operat or Pane l shows . This means the i nverter is bus y with task s of higher pr iorit y.
3 Commis sioning Issue A1 MICROMASTER 410 Operating Instructions 40 6SE6400-5EA 00-0BP0 Flo w char t Quick Comm issionin g (L ev el 1 Only ) 1) Motor related paramet ers – please refer to motor rating plate. 2) Denotes parameters that c ontain m ore detail e d lists of possible setti ngs f or use in specific applicat i ons.
Issue A1 3 Commis sioning MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 41 Motor d ata for pa rameter i zation Figure 3-7 T ypical M otor Rating Plate Ex ample NOTE Ø P03 08 & P 0309 are onl y visible if P0003 = 3. On ly one of the param eters is shown depe nding on the set tings of P0100 .
3 Commis sioning Issue A1 MICROMASTER 410 Operating Instructions 42 6SE6400-5EA 00-0BP0 3.3 General operation For a f ull desc ription of Level 1 to Le vel 3 par ameter s, pleas e refer to the Parameter List. NOTICE 1. The inv erter does not have a m ain po wer switch an d is li ve when th e m ains suppl y is connect ed.
Issue A1 3 Commis sioning MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 43 External motor thermal ov erl oad protection When oper ated bel ow rated s peed, the cooling effec t of fans f itted to the m otor shaft is reduced. Consequ entiall y, mos t motor s require de- rating for c ontinuous operatio n at lo w frequenci es.
3 Commis sioning Issue A1 MICROMASTER 410 Operating Instructions 44 6SE6400-5EA 00-0BP0.
Issue A1 4 Using th e MICRO MASTE R 41 0 MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 45 4 Using the MICROM A ST ER 410 WARNING ♦ ♦ ♦ ♦ W hen operating electric al devic es, it is im possible to avoid appl ying hazardo us volta ges to c ertain p arts of the equipm ent.
4 Using th e MICRO MASTER 4 10 Iss ue A1 MICROMASTER 410 Operating Instructions 46 6SE6400-5EA 00-0BP0 4.2 Command Sources (P0700) NOTICE The ram p tim es and ram p-sm oothing func tions also aff ect how the m otor star ts and stops.
Issue A1 4 Using th e MICRO MASTE R 41 0 MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 47 4.3.2 OFF2 This comm and causes the m otor to c oast to a s tandsti ll (pu lses disa bled). NOTICE The OF F2 comm and can ha ve one or mor e sources .
4 Using th e MICRO MASTER 4 10 Iss ue A1 MICROMASTER 410 Operating Instructions 48 6SE6400-5EA 00-0BP0 4.4 Control Modes (P1300) The vario us m odes of oper ation of the MICROM ASTER 4 10 contr ol the rel ation- ship bet ween the s peed of the m otor and the voltage s upp lied b y the inver ter.
Issue A1 5 Syste m Parame ters MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 49 5 System Parameter s 5.1 Introduction to MICROM ASTER Sy stem Par ameter s The parameters can only be changed by using the Opera tor Panel (OP) or the Serial Inte rface.
5 Syste m Parameters Issue A1 MICROMASTER 410 Operating Instructions 50 6SE6400-5EA 00-0BP0 5.2 Parameter Overv iew P0004 = 2 Inve rter Un it P0004 = 3 Mo tor Da ta P0004 = 7 Commands and Digtal I /O .
Issue A1 5 Syste m Parame ters MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 51 5.3 Parameter List (short form) Explanat ory inf orm ation on f ollowin g table: Ø Default: Factor y setti.
5 Syste m Parameters Issue A1 MICROMASTER 410 Operating Instructions 52 6SE6400-5EA 00-0BP0 Motor Data (P0004 = 3) ParNr Par Text Default Acc DS QC r0034 CO: Motor temperature (i 2 t) - 3 - - P0300 Select motor type 1 3 C Q P0304 Rated m otor voltage 230 1 C Q P0305 Rated m otor current 3.
Issue A1 5 Syste m Parame ters MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 53 A nalogue I/O (P0004 = 8) ParNr Par Text Default Acc DS QC r0752 Act.
5 Syste m Parameters Issue A1 MICROMASTER 410 Operating Instructions 54 6SE6400-5EA 00-0BP0 Drive Features (P0004 = 12) ParNr Par Text Default Acc DS QC P0005 Displ ay select ion 21 2 CUT N P1200 Flyi.
Issue A1 5 Syste m Parame ters MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 55 Communication (P0004 = 20) ParNr Par Text Default Acc DS QC P0927 Paramet er changeable vi a 15 3 CUT N r0964[5] Firmware version data - 3 - - P0971 Transfer data from RAM to EEPROM 0 3 CUT N P2000 Reference f requenc y 50.
5 Syste m Parameters Issue A1 MICROMASTER 410 Operating Instructions 56 6SE6400-5EA 00-0BP0.
Issue A1 6 Troub leshoot ing MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 57 6 T rouble shooting WARNING ♦ ♦ ♦ ♦ Repairs on equipm ent m ay onl y be carried o ut b y Siemens Serv.
6 Troub leshoot ing Issue A1 MICROMASTER 410 Operating Instructions 58 6SE6400-5EA 00-0BP0 6.3 Fault messages Fault Possibl e Causes Diagnose & R emedy Reac- tion F0001 OverCurrent Ø Motor power (P0307) does not correspond t o the inverter power (r0206) Ø Motor lead short circ uit Ø Earth faults Check t he following: 1.
Issue A1 6 Troub leshoot ing MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 59 Fault Possibl e Causes Diagnose & R emedy Reac- tion F0060 A s ic Timeout Internal c ommunications failur.
6 Troub leshoot ing Issue A1 MICROMASTER 410 Operating Instructions 60 6SE6400-5EA 00-0BP0 6.4 A l arms Alarm Possible C auses Diagnose & Remedy Reac- tion A 0501 Current Limit Ø Motor power does not correspond t o the inverter power Ø Motor leads are too long Ø Earth faults Check t he following: 1.
Issue A1 6 Troub leshoot ing MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 61 Alarm Possible C auses Diagnose & Remedy Reac- tion A 0920 AD C parameters not set properly. ADC parameters should not be set to identic al values, si nce t his would produce illogical results.
6 Troub leshoot ing Issue A1 MICROMASTER 410 Operating Instructions 62 6SE6400-5EA 00-0BP0.
Issue A1 7 MICRO MAST ER 410 Spe ci ficatio ns MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 63 7 MICROM ASTER 410 S p ecifications Table 7-1 MICROMAST E R 410 Performan ce Ratings Feature Specification Mains Operating Volt age & Power Ranges 100 to 120 V ± 10% 1AC 0.
7 MICRO MAST ER 410 Spec ificat ions Issue A1 MICROMASTER 410 Operating Instructions 64 6SE6400-5EA 00-0BP0 Table 7-2 Terminal Torques – Field W irin g Connectors Motorside PE terminal Al l other t erminal s [Nm] 0.8 1 .1 Tightening Torque [lbf.in] 7.
Issue A1 7 MICRO MAST ER 410 Spe ci ficatio ns MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 65 Input voltage range 1 AC 200 V – 240 V, ± 10 % (Unfiltered) Order No. 6SE6410- 2UB11 -2AA0 2UB12 -5AA0 2UB13 -7AA0 2UB15 -5BA0 2UB17 -5BA0 [kW] 0.
7 MICRO MAST ER 410 Spec ificat ions Issue A1 MICROMASTER 410 Operating Instructions 66 6SE6400-5EA 00-0BP0.
Issue A1 8 Options MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 67 8 Options The f ollowing access ories are a vailab le as opt ions for your MICRO MAST ER MM410 I nverter. For mor e details p lease r efer to t he catalo gue or c ontact your loca l Siemens sale s office if you require assi stance.
8 Options Issue A1 MICROMASTER 410 Operating Instructions 68 6SE6400-5EA 00-0BP0.
Issue A1 9 Electro- Magnetic Comp atib ility MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 69 9 Electro-Magnetic Comp atibility (EMC) 9.1 Electro- M agnetic Comp atibilit y (EM C) All m a.
9 Electro- Magnetic Comp atibility Issue A1 MICROMASTER 410 Operating Instructions 70 6SE6400-5EA 00-0BP0 9.1.3 EM C Directiv e Compliance with Harmonics R egulations From 1s t Januar y 2001 all e lec.
Issue A1 9 Electro- Magnetic Comp atib ility MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 71 9.1.4 Genera l cases of EMC performan ce Three G eneral ca ses of EMC perf orm ance are avail.
9 Electro- Magnetic Comp atibility Issue A1 MICROMASTER 410 Operating Instructions 72 6SE6400-5EA 00-0BP0 Case 3: Filtered - for residential, commerc i al and li ght industry This level of perf ormanc.
Issue A1 Fitting the O perator Panel MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 73 A p pendice s A Fitting the Operator Panel.
Applica ble St andards Issue A1 MICROMASTER 410 Operating Instructions 74 6SE6400-5EA 00-0BP0 B A p plicable Standard s European Low Voltage Dir ective The MICROM ASTER pr oduct r ange com plies with the r equirem ents of the Low Voltage D irecti ve 73/23/EEC as am ended b y Directiv e 98/68/E EC.
Issue A1 List of Ab brevia tions MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 75 C List of A bbr eviations AC Alternat ing Curr ent AI N Anal og Inpu t CT Constant T orque DC Direct Curr.
Index Issue A1 MICROMASTER 410 Operating Instructions 76 6SE6400-5EA 00-0BP0 Index A Access Levels .......................................... 49 Altitude ..................................................... 19 Ambient o perating conditi ons .........
Issue A1 Index MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 77 MICROMAST ER 410 available o ptions .................................. 67 general ................................................. 15 main c haracteristics .................
Index Issue A1 MICROMASTER 410 Operating Instructions 78 6SE6400-5EA 00-0BP0.
MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 79 Suggestions and/or Co rrections Suggestions Correctio ns To: Siemens AG Automation & Driv es Group SD VM 4 P.O. Box 3269 D-91050 Erlangen Federal Republic of Germany For Pub licati on/Manual : MICROMAST ER 410 Em ail: Tec hnical.
MICROMASTER 410 Operating Instructions 80 6SE6400-5EA 00-0BP0.
Issue A1 View of Units MICROMASTER 410 Operating Instructions 6SE6400-5EA 00-0BP0 81 Vie w of Un it Standard Inv ert er Inverter with Optional Operato r Panel Fitted Key: 1. Line T erminals 2. Status L ED 3. Operator Panel Con nec tor 4. Control T erm inals 5.
Siemen s AG Bereich Automat i on and Drives (A&D) Geschäftsgebi et Standard Drives (SD) Postfach 3269, D-91050 E rl angen Federal Republic of Germany © Siem ens AG, 2001 Subject to chan ge wi tho ut pri or notice Siemens Aktieng esells chaf t Ord er No.
Een belangrijk punt na aankoop van elk apparaat Siemens 410 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Siemens 410 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Siemens 410 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Siemens 410 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Siemens 410 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Siemens 410 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Siemens 410 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Siemens 410 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.