This document discusses the installation and specifications for the following 9200 meter power supply options:
! Standard AC/DC power supply
! Low voltage DC power supply
! 480V power supply
! Installing the Power Supply 2
! Wiring the Power Supply 3
Wiring the Standard AC/DC or Low Voltage DC Power Supply 3 Wiring the 480V Power Supply 4 Powering Up the Meter 4
! Specifications 5
! 9200 Installation and Operation Guide
© 2003 Siemens Energy & Automation. All rights reserved. The information in this document is believed to be accurate at the time of publication, however, Siemens Energy & Automation assumes no responsibility for errors which may appear here and reserves the right to make changes without notice. ION is a registered trademark of Power Measurement Ltd. All other trademarks are property of their respective owners. Revision Date: June 3, 2003
Additional Information

Replacing the Power Supply 9200 Power Supply Retrofit Instructions
Installation and maintenance of ACCESS meters and meter options should only be performed by qualified personnel that have appropriate training and experience with high voltage/current devices. Refer to Installation Considerations, and the Danger, Warning, and Limitation of Liability notices in the 9200 Installation and Operation Guide.
All 9200 power supply models are installed the same way; the diagram for the 480V power supply is included to show the greater depth dimension of that model.


9200 Power Supply Retrofit Instructions Wiring the Power Supply
The meter requires a constant power supply to maintain monitoring, analysis, control, and communications operations. Powering the device from the voltage source it is monitoring is not suitable for applications where these operations must be maintained in the event of a power outage.
Use 18 to 14 AWG (0.8mm2 to 2.1mm2) wire
2A fuse on L+ and N-. DO NOT install the N- fuse in a grounded neutral power system
Standard AC/DC Power Supply
Connect the line supply wire to the L+ terminal and the neutral supply wire to the N- terminal.
Low Voltage DC Power Supply
Connect the positive supply wire to the L+ terminal and the negative supply wire to the N- terminal.
The power supply G (ground) terminal must be connected to the same point as the meter terminal.
If a Standard AC/DC or a Low Voltage DC power supply is being used, install a Type T (slow blow) 2A fuse on the L+ conductor. If the meter is powered by a grounded neutral power system, a fuse must NOT be installed on the neutral wire. If the line connected to the N/- terminal is not grounded in the breaker panel, then install a Type T (slow blow) 2A fuse on the N- terminal.
Protective Fuses

Wiring the 480V Power Supply 9200 Power Supply Retrofit Instructions

Use18 to 14 AWG (0.8mm2 to 2.1mm2) wires
Use18 to 14 AWG (0.8mm2 to 2.1mm2) wire
Connections to the L1 and L2 terminals can come from V1 and V2
Connect one phase to the L1 terminal and the other phase to the L2 terminal. You can use the same wires from the grid that the voltage inputs use (see diagram above).
The power supply G (ground) terminal must be connected to the same point as the meter terminal.
The 480V power supply requires 100 mA fuses on the L1 and L2 terminals. These should be IEC type T slow blow fuses.
100 mA fuses can be shared with the voltage inputs.
After the power supply is attached to the meter, and its wiring is connected:
480V Power Supply · Protective Fuses

9200 Power Supply Retrofit Instructions Specifications