9200 Power Supply

This document discusses the installation and specifications for the following 9200 meter power supply options:

! Standard AC/DC power supply

! Low voltage DC power supply

! 480V power supply

In This Document

! Installing the Power Supply 2

! Wiring the Power Supply 3

Wiring the Standard AC/DC or Low Voltage DC Power Supply 3 Wiring the 480V Power Supply 4 Powering Up the Meter 4

! Specifications 5

! 9200 Installation and Operation Guide

© 2003 Siemens Energy & Automation. All rights reserved. The information in this document is believed to be accurate at the time of publication, however, Siemens Energy & Automation assumes no responsibility for errors which may appear here and reserves the right to make changes without notice. ION is a registered trademark of Power Measurement Ltd. All other trademarks are property of their respective owners. Revision Date: June 3, 2003

Additional Information

Page 2 of the Siemens Uninterruptible Power Supply (9200) user manual — Plugging in the Power Supply
Pagina 2 · klik om te vergroten
Pagina 2

Replacing the Power Supply 9200 Power Supply Retrofit Instructions

Replacing the Power Supply

D ANGER

Installation and maintenance of ACCESS meters and meter options should only be performed by qualified personnel that have appropriate training and experience with high voltage/current devices. Refer to Installation Considerations, and the Danger, Warning, and Limitation of Liability notices in the 9200 Installation and Operation Guide.

1. Turn off all power to the meter.
2. Ensure that all cables still connected to the meter are not live.
3. Ensure that the Line and Neutral (or DC power) wires to the power supply inputs of the meter are not live (if you are replacing an existing power supply).
4. Fit the power supply plug-in connector to the meter plug-in port.

N OTE

All 9200 power supply models are installed the same way; the diagram for the 480V power supply is included to show the greater depth dimension of that model.

5. Tighten the two (captive) screws until the power supply fits snugly against the meter. Do not overtighten the screws.

Plugging in the Power Supply

Siemens Uninterruptible Power Supply (9200) — Plugging in the Power Supply diagram (page 2)
Afb. 2 · Plugging in the Power Supply
Page 3 of the Siemens Uninterruptible Power Supply (9200) user manual — G L+ N -
Pagina 3 · klik om te vergroten
Pagina 3

9200 Power Supply Retrofit Instructions Wiring the Power Supply

Wiring the Power Supply

The meter requires a constant power supply to maintain monitoring, analysis, control, and communications operations. Powering the device from the voltage source it is monitoring is not suitable for applications where these operations must be maintained in the event of a power outage.

Wiring the Standard AC/DC or Low Voltage DC Power Supply

Use 18 to 14 AWG (0.8mm2 to 2.1mm2) wire

2A fuse on L+ and N-. DO NOT install the N- fuse in a grounded neutral power system

G L+ N -

Standard AC/DC Power Supply

Connect the line supply wire to the L+ terminal and the neutral supply wire to the N- terminal.

Low Voltage DC Power Supply

Connect the positive supply wire to the L+ terminal and the negative supply wire to the N- terminal.

The power supply G (ground) terminal must be connected to the same point as the meter terminal.

If a Standard AC/DC or a Low Voltage DC power supply is being used, install a Type T (slow blow) 2A fuse on the L+ conductor. If the meter is powered by a grounded neutral power system, a fuse must NOT be installed on the neutral wire. If the line connected to the N/- terminal is not grounded in the breaker panel, then install a Type T (slow blow) 2A fuse on the N- terminal.

Protective Fuses

Page 4 of the Siemens Uninterruptible Power Supply (9200) user manual — Powering Up the Meter
Pagina 4 · klik om te vergroten
Pagina 4

Wiring the 480V Power Supply 9200 Power Supply Retrofit Instructions

Wiring the 480V Power Supply

Siemens Uninterruptible Power Supply (9200) — Wiring the 480V Power Supply diagram (page 4)
Afb. 3 · Wiring the 480V Power Supply

Use18 to 14 AWG (0.8mm2 to 2.1mm2) wires

Use18 to 14 AWG (0.8mm2 to 2.1mm2) wire

Connections to the L1 and L2 terminals can come from V1 and V2

Connect one phase to the L1 terminal and the other phase to the L2 terminal. You can use the same wires from the grid that the voltage inputs use (see diagram above).

The power supply G (ground) terminal must be connected to the same point as the meter terminal.

The 480V power supply requires 100 mA fuses on the L1 and L2 terminals. These should be IEC type T slow blow fuses.

N OTE

100 mA fuses can be shared with the voltage inputs.

Powering Up the Meter

After the power supply is attached to the meter, and its wiring is connected:

1. Reconnect and energize all wiring that was disconnected when the meter was prepared for power supply installation.
2. Power up the meter and verify correct operation.

480V Power Supply · Protective Fuses

Page 5 of the Siemens Uninterruptible Power Supply (9200) user manual — Specifications
Pagina 5 · klik om te vergroten
Pagina 5

9200 Power Supply Retrofit Instructions Specifications

Specifications

Power SupplyRated InputsMeterMaximumSteady StateDielectric Withstand VAWVAW Standard AC / DC Power SupplyAC: 100 – 240 VAC, 50 – 60 Hz DC: 110 – 300 VDC Installation category II (Local). Pollution degree 2.Integrated138852000 VAC RMS, 60 Hz for 1 minute TRAN / RMD13895 TRAN5353 Low Voltage DC Power Supply20 – 60 VDCIntegrated64 TRAN / RMD75 TRAN33 480V Power Supply480 VAC, 60 Hz Installation category III (Distribution). Pollution degree 2.Integrated151212103250 VAC RMS, 60 Hz for 1 minute TRAN / RMD15121310 TRAN119119

Vraag stellen over de Siemens Uninterruptible Power Supply (9200)

Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nog geen vragen over de Siemens Uninterruptible Power Supply (9200)

Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.

Origineel document

Siemens Uninterruptible Power Supply (9200) handleiding-pdf

5 pagina's·210 KB·Voeding·PDF
Klik op een bovenstaande pagina om deze hier te openen
Pagina 1 / …
100%
Pagina's laden…