Automation– and Driv e Technology - SCE Training document for the company -w ide automation solution Totally Integrated Automation (T I A) MODULE B4 Data blocks T I A Training doc ument Page 1 of 18.
Automation– and Driv e Technology - SCE This docum ent was provided by Siemens A&D SC E (autom ation and drive technology, Siemens A&D Cooperates with Education) f or training purposes . Siem ens does not m ake any ty pe of guarantee regar ding its contents.
Automation– and Driv e Technology - SCE PA GE: 1. Forward ................................................................................................................. 4 2. Notes for Dat a Blocks .................................................
Automation– and Driv e Technology - SCE 1. FORWA RD The m odule B4 is as signed content wise to A dditional functions of S TEP 7- Progra mming . Basics of STEP 7- Programmin g 2 - 3 da y s A m odule.
Automation– and Driv e Technology - SCE Required har dware and software 1 PC, Operating system W indows 95/98/2000/ME/NT 4.0 with - Minimal: 133MHz and 64MB RAM, approx. 65 MB f ree hard dis k spac e - Optim al: 500MHz and 128MB RAM, approx. 65 MB free hard dis k s pace 2 Software ST EP 7 V 5.
Automation– and Driv e Technology - SCE 2. NOTES FOR DATA BLOCKS Data Block s (DBs) can be used by y our program to save data in the CPU. Your hard disk contains up to 8 KBy tes ( 8192 Bytes ) space.
Automation– and Driv e Technology - SCE 3. GENERA TING DA TA BLOCKS Data block s are generated and opened lik e program block s in the tool LAD,S TL,FBD: Program blocks .
Automation– and Driv e Technology - SCE In order to generate this program exam ple, the following steps m ust be f ollowed (Ther eby the program is dispens ed with the creation of the hardware c onfiguration): 1. Call SI MA TI C Ma n a g e r with a double click ( ® SIMATIC Manager) 2.
Automation– and Driv e Technology - SCE 3. In the name path, c reate the projec t with the name T estproject_DB . ( ® ’Tes tproject_DB’ ® OK) 4.
Automation– and Driv e Technology - SCE 5. Highlight the f older Blocks . ( ® Block s) 6. Insert Data Block ( ® Insert ® S7 Block ® Data Block ).
Automation– and Driv e Technology - SCE 7. Enter the num ber DB10 f or the data block and accept with OK ( ® DB10 ® OK). 8. Open the data bloc k DB10 with a double click ( ® DB10).
Automation– and Driv e Technology - SCE 9. Ack nowledge the ty pe of data block . ( ® Data Block ® OK ) Note: Data block s with an assigned FB are autom atically display ed by the call of your associated FB. It m ak es no sens e to create this alone.
Automation– and Driv e Technology - SCE 10. The Data Bloc k is gener ated with a sy mbol Name . T he Ty pe , an Initial value as well as a Comment (optional) are enter ed. The addres s is autom atically generated and cannot be altered. The data bloc k can be s aved and downloaded into the PLC .
Automation– and Driv e Technology - SCE Data in a data block mus t be determ ined through data ty pes. The f ollowing standard- data types are defined in the S7 below : Type and description Size in .
Automation– and Driv e Technology - SCE 11. Values should be m odified in a data bloc k. It is not adequate to modif y them in the field Initial valu e . This is only possible, when one switches to the Data View under View ( ® View ® Data View). 12.
Automation– and Driv e Technology - SCE 13. In order to generate the progr am with the acc essible data elem ents, the OB1 mus t be opened through a double click in SI MA TIC Ma n a ge r ( ® SIMATIC Manager ® OB1). 14. Then ac cept the setting with OK ( ® OK ).
Automation– and Driv e Technology - SCE There are t hree possibilities to access th e data: 1. Direct address access: One can acc ess one data elem ent in a data block with the following instructions : Exam ple: L DB 20. DBB2 Load data byte 2 from DB20 into ACCU 1 L DB 22.
Automation– and Driv e Technology - SCE 15. W ith LA D, STL, FBD: Progra m blocks , y ou now have an editor that give y ou the possibility to generate your STEP 7-Program . The s chem a for the selec tion of the data elem ent through the button is s hown for the firs t three inputs as s pecified below.
Een belangrijk punt na aankoop van elk apparaat Siemens B4 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Siemens B4 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Siemens B4 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Siemens B4 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Siemens B4 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Siemens B4 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Siemens B4 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Siemens B4 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.