CC1A7865.1en 31.10.2002 Sie mens Bu ildi ng Tech nolo gies HVAC Product s 7 865.1 Interface RS-485 RWF40... The RS-485 interface is used f or integrati ng RW F40… controllers into data networks via MOD bus protocol.
2/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Transmission mode (RT U) The transmission mode used is the RTU (re mote terminal unit) mode. Data are trans- mitted in binary format (hexadecimal) with 8 bits. The LSB (least significant bit) is transmitted first.
3/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Communication se quence Both the start and end of a data block are c haracterized by transmiss ion pauses. The maximum period of tim e that m ay elapse between 2 successi ve characters is 3 times the period of time required for the transmis sion of one character.
4/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Data query sequence The time sequence of a data query looks as follows: Master Sl ave Data qu er y Rep ly Data qu ery t 0 t 1 t 0 t 2 7865z12e/1102 t0 Identification of end = 3 characters (time is dependent on the Baud rate) t1 This time is dependent on internal handling.
5/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Structure of the data blocks All data blocks use the same structure: Slave address Function c ode Data field Checksum CRC16 .
6/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Checksum (CRC16) The che cksum ( CRC1 6) is used to det ect tra nsmissio n err ors.
7/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Reading n words This function is used to read n words from a certain address.
8/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Writing n w ords Slave address Function 0x10 Address of first word Number of words Number of by t es (max.
9/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Address tables Address Data typ e Access Parameter Value range Default valu e 0x0000 f loat R / O Actual value E1 0x0002 f loat R / O Actual value E2 0x0004 f loat R / O Actual value E3 0x0006 f loat R / W Current setpoint 0x0008 f loat R / W SP1 First setpoint SPL.
10/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Address Data typ e Access Parameter Value range Default valu e 0x0300 word [13] R / O Device data 0x0300 char SW Version [1.
11/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Address Data type Access Parameter 0x0200 word R / O Outputs and states B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 .
12/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Description of operati ng modes Parameter «RemoteStatus» is used to switch between the operating modes «LOCAL», «REMOTE SETPOINT» and «FULLY REMOTE». The change is always accomplished via the MOD bus.
13/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 The previous functions of the RW F40... are maintained (apart from mem ory usage). The R W F40... can be parameterized and uploaded via the MOD bus, whereby the out- puts cannot be changed.
14/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Modulating controller: The management system predefines the va lue (degree of modulat ion) for the analog output via «RY». Setting the «RK2» and «RK3» by the management system has no impact.
Een belangrijk punt na aankoop van elk apparaat Siemens RS-485 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Siemens RS-485 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Siemens RS-485 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Siemens RS-485 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Siemens RS-485 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Siemens RS-485 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Siemens RS-485 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Siemens RS-485 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.