/ Mar le y Class F40 0 Cooling T ower / User Manual 93-1288A.
2 Contents These instructions assist in obtaining efficient, long life from Marley counterflow cooling towers. Direct questions concerning cooling tower operation and maintenance to your Marley sales representative. Al- ways include your tower serial number when writing for information or ordering parts.
3 Before Start-up Among other sources, outbreaks of Legionnaires’ disease have re- portedly been traced to cooling towers. Maintenance procedures that prevent amplification and dissemination of Leg.
4 The oil level placard must be adjusted so that its “full” mark is at the same elevation as the “full” mark on the side of the Gear educer case. Check oil lines to be sure there are no leaks. See Geareducer User Manual for oil filling procedur e and list of recommended lubricants.
5 TOWER PERFORMANCE –Keep the cooling tower clean and water dis- tribution uniform to obtain continued maximum cooling capacity . The capacity of a cooling tower to cool water to a given cold water tem- perature varies with the wet-bulb temperature and the heat load applied to the cooling tower .
6 Caution cold weather operation will be enhanced if you read “Operating Cooling T owers in Freezing W eather” Marley T echnical Report #H-003 . Ice forming characteristics on any given cooling tower will vary , depending on velocity and direction of wind, circulating water rate, and heat load.
7 least tower maintenance. See Cooling T ower Inspection Check List in this manual. Keep a continuous lubrication and maintenance r ecord for each cooling tower . HOT W A TER DISTRIBUTION SYSTEM –Keep the circulating water and distribution system (piping and nozzles) clean and free of dirt, algae, and scale.
8 W ater T reatment BLOWDOWN –Blowdown, or bleed-of f, is the continuous r emoval of a portion of the water from the circulating system. Blowdown is used to prevent the dissolved solids from concentrating to the point where they will form scale.
9 compounds which contain copper are not recommended. Chlorine and chlorine containing compounds are effective algaecides and slimicides. If used, chlorine should be added as intermittent (or shock) treatment only as fr equently as needed to control the slime and algae.
.
class F400.
12 Spare Parts SPX Cooling T echnologies manufactur es and maintains a stock of re- placement parts for all cooling tower mechanical equipment. Shipment of these parts ar e normally made within ten days after an order is received. If emer gency service is necessary , contact the local Marley representative for assistance.
13 Geareducer (shutdown for 3 months or mor e). 1. If the motors have space heaters, operate mechanical equipment one hour each month. 2. If the motors do not have space heaters, operate mechanical equipment one hour each week. 3. At startup, operate mechanical equipment one hour or until oil is warm, then shut the equipment down.
14 T r oubleshooting Remedy 1. Check power at starter . Correct any bad connections be- tween the control apparatus and the motor . 2. Check starter contacts and control circuit. Reset overloads, close contacts, reset tripped switches or r eplace failed con- trol switches.
15 Ladders, Stairways, Walkways, Handrails, Covers, Decks and Access Doors Davits, Derricks, and Hoists Inspect for General Condition Semi-annually Semi-annually Inspect and Repair for Safe U.
16 Inspection and Maintenance Schedule General Recommendations —more frequent inspection and mainte- nance may be desirable D–Daily W–W eekly M–Monthly Q–Quarterly S–Semiannually Y–Y early R–as Required 1. Inspect for clogging M M W W 2.
17 Inspection and Maintenance Notes.
18 Date Inspected Inspected By Owner Location Owner’ s T ower Designation T ower Manufacturer Model No. Serial No. Process Served by T ower Operation: Continuous Intermittent Seasonal Design Conditi.
19 Mechanical Equipment Gear Drive Units Manufacturer Model Ratio Oil Level: Full Add Immediately Low , check again soon Oil Condition: Good Contains W ater Contains Metal Contains Sludge Oil Used—t.
7 401 WEST 129 STRE ET | O VE R LAN D P AR K, KANSAS 66213 U N ITE D ST A TES | 913 664 7 4 00 | spxcooling@spx.com | spxcooling.com In the interest of technological progress, all products are subject to design and/or material c hange without notice. ©2009 S PX Cooling T echnologies, Inc.
Een belangrijk punt na aankoop van elk apparaat SPX Cooling Technologies F400 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen SPX Cooling Technologies F400 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens SPX Cooling Technologies F400 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding SPX Cooling Technologies F400 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over SPX Cooling Technologies F400 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van SPX Cooling Technologies F400 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de SPX Cooling Technologies F400 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met SPX Cooling Technologies F400 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.