Printed in the U.S.A. 0210 317913-000 A TECHNICAL GUIDE TO DESIGNI NG ENERGY-EFFICIENT COMMERCIAL WATER HEATER SYSTEMS.
2 l . Introduction T o Commercial W ater Heating Pages Parameters .................................................................................................................................... 2- 3 What is Hot Water? ............................
3 What is Hot Water? Hot water is water to which heat energy has been added . . .as more heat is added the water becomes hotter . This water temperature guide shows typical water heating system design temperatures.
4 Evaluating Water The coldest water inlet temperature experienced during the year should be the base from which the maximum system temperature rise is established. Y our water supplier can provide this information. Surface water sources such as lakes and rivers tend to fluctuate as the seasons change.
5 Hot Water Demand The major determination in sizing and the basis of all computations is establishing the probable demand for hot water . In addition, any unusual conditions which might relate to hot water consumption must also be recognized and planned for .
6 • This example could represent an industrial process which is operated for two continuous shifts a day . • Hot water is used at a maximum rate of 3.3 gpm or 198 gph. (It is important to establish maximum flow rate and water temperature rise in order to select a heater model.
7 When used at altitudes of 2000’ or more above sea level, gas-fired heater recovery capacities must be derated 4% for each 1000’ above sea level in order to reflect actual recovery . Recovery Capacity means hot water at the heater recovery rate minute after minute, hour after hour .
8 State commercial tank type water heaters, hot water storage tanks and water heating systems using tanks have assigned tank efficiencies as follows: Gas and Oil-Fired T ank T ype Heaters • Use 70% tank draw efficiency for all one and two temperature applications.
9 Eight hour demand period, per hour capacity . 171 gph recovery Storage: + 8 gal storage 179 gal/8 hour 100 gallon tank Recovery provides 96% x 70% tank efficiency of demand.
10 When Using Electricity T o Heat Water The system designer may want to modify the preceding heater recovery and storage tank capacity information when using electricity to heat water . This is because electricity for commercial use, including water heating, is often sold on a demand rate basis.
11 IV . Sy st em T ypes and Application Design Objective The objectives in the design of commercial water heating systems are numerous and varied. The major considerations which the system designer should include in the planning stages are: 1.
12 2. T wo T emperature provides two temperature hot water service by means of a water mixing valve or through a pre-heater/booster heater combination. In the first concept the heater storage tank is maintained at the highest system temperature required (usually at 180°F) and the mixing valve externally produces the 140°F hot water requirement.
13 Creating the Successful System Creating the successful commercial water heating system is a joint venture involving many persons and skills. In order to select the right system using either tank type or copper type heaters, one should understand the role that each of the persons concerned with the installation plays.
14 2. Select a trial size heater 2 / . 3. Subtract the hourly heater recovery from the demand. 4. The difference in gallons between demand and recovery must come from the tank. 5. Multiply the difference by the number of demand hours. The result is the “usable” number of gallons which must come from the tank.
15 T wo temperature example 1. A one hour demand of 75 gallons of 180°F water and 110 gallons of 140°F water has been established. The lowest incoming water temperature is 40°F . The shortest time in any day in which the demand will be repeated is 3 hours.
16 ST A TE W A TER HEA TERS ASHLAND CITY , TENN. © 200 4 TECHNICAL INFORMA TION 800-365-0577.
Een belangrijk punt na aankoop van elk apparaat State Industries 317913-000 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen State Industries 317913-000 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens State Industries 317913-000 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding State Industries 317913-000 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over State Industries 317913-000 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van State Industries 317913-000 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de State Industries 317913-000 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met State Industries 317913-000 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.