1 Instruction Manual PRINTED IN THE U .S .A 0408 1 97 834-000 KEEP THIS MANUAL IN THE POCKET ON HEA TER FOR FUTURE REFERENCE WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
2 SAFE INST ALLA TION, USE AND SERVICE Y our safety and the safety of others is extremely important in the installation, use and servicing of this water heater .
3 GENERAL SAFETY.
4 GENERAL SAFETY.
5 Thank Y ou forpurchasingthis waterheater .Properlyinstalled and maintained,itshouldgiveyouyearsoftroublefreeservice.
6 * CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See “Planning the Vent System,” “Installation of Vent System” and “Condensate” for more information.
7 Rough-In-Dimensions Model Units A B C D E F 100 Inches 68.50 49.25 22.00 15.75 3.00 8.00 cm 174 125.09 55.88 40.00 7.62 20.32 T op/Side Inlet and Outlet: 3/4” NPT Gas Inlet: 1/2” NPT Capacity , Gas and Electrical Characteristics Model ApproximateCapacity Manifold Pressure Electrical Characteristics U.
8 For all sidewall terminated, horizontally vented powervent, direct vent, andpower directvent gas fueled waterheaters installed in ever.
9 FIGURE 2. W A TER PIPING - MIXING V AL VE USAGE This appliance has been design certified as complying with American National Standard/CSA Standard for water heaters and is.
10 F ACTS TO CONSIDER ABOUT THE LOCA TION Car eful ly cho ose an ind oor locat ion for the new wat er hea ter , beca use the placementis a very importantconsideration for the safetyof the occupants in the building and for the most economical use of the appliance.
11 in an alcove or closet, the entire oormust be covered bythe panel. Failuretoheedthiswarningmayresultinarehazard. Minimum clearances between the water heater and combustible con stru ctio n are 0 i nc h at the sides an d rear , 5.
12 a f r ee areaofone squareinchper 1000Btu/hr(22cm 2 /kW) ofthe total inputof all appliances inthe enclosure, but notless than 100 squareinches(645cm 2 ).
13 CLOSED W A TER SYSTEMS W ater supply systems may , because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back ow preventers.
14 Figures2 and 10show the typicalattachment of thewater piping to the water heater . The water heater is equipped with 3/4 inch NPT water connections. NOTE: If using copper tubing, solder tubing to an adapter before attaching the adapter to the water heater connections.
15 The te mper ature - pr essu re reli ef valve must b e manu ally o p e r a t e d a t l e a s t o n c e a y e a r , s e e F i g u r e 2 8 .
16 SEDIMENT TRAPS A sedime nt tra p sha ll be inst alled as close to the ga s inle t of the water heater as practical at the time of water heater installation.
17 FIGURE 15B. U.S. POWER VENT CANADIAN POWER VENT W ARNING VENT HOOD(S) MA Y BE EXTREMEL Y HOT DURING OPERA TION. W ARNING VENT HOOD(S) MA Y BE EXTREMEL Y HOT DURING OPERA TION.
18 FIGURE 15D. U.S. DIRECT VENT CANADIAN DIRECT VENT W ARNING VENT HOOD(S) MA Y BE EXTREMEL Y HOT DURING OPERA TION. W ARNING VENT HOOD(S) MA Y BE EXTREMEL Y HOT DURING OPERA TION.
19 PLANNING THE VENT SYSTEM Plan the route of the vent system from the exhaust elbow to the plannedlocationoftheventterminal. 1. Layout total vent systemtousea minimumofventpipeandelbows.
20 INST ALLA TION OF VENT SYSTEM Beforebeginning installation of pipingsystem thoroughly read the section of this manual VENT PIPE PREP ARA TION.
21 INST ALLA TION SEQUENCE For installations in the City of LosAngeles, California Category IV PVCPipesuch asthatmanufacturedbyBrownline PipeCompany , mustbeusedasventpipematerial.
22 INST ALLA TION OF VENT SYSTEM, SIDEW ALL With the route of the venting system and selection of materials completed, as d isc uss ed in t he se cti on of t his m.
23 Thi s c onc entr icvent ter minat ionkitmay beusedwith 3or 4inchdiamete r pi pe sy st em s. Whe nco nn ect in gt oa4 in .
24 5. Secure assemblyto roofstructure as shownin Figure Eusing fieldsuppliedmetalstrappingorequivalentsupportmaterial. NOTE: Ensure termination height is above the roof surface or anticipated snow level (1 ft.
25 8. Operate heater through 1 heat cycle to ensure combustion-ai r and ventpipesareproperlyconnectedtoconcentricventtermination connections.
26 VENT PIPE PREP ARA TION 1. INITIAL PREP ARA TION. A. ) Make sure the solvent cement you are planning to use isdesignedforthespecicapplicationyouareattempting.
27 B. Deburring Us e ak ni fe, p las ti cp ip ed eb ur ri ng to ol, o rf il et or em ov eb ur rs fr om the end of small diameter pipe. Be sure to remove all burrs from ar ou nd th e ins id e as we ll as th e ou tsi de of th e pi pe .
28 CONTROLS AND SWITCHES This model is provi ded with three pressure switch es. These switche s are essential to the safe and proper operation of the unit. All switches are wired in series.
29 CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERA TION. VERIFY PROPER OPERA TION AFTER SERVICING. POWER VENT WIRING SCHEMA TIC - FIGURE 24. THI S WATER H EATER IS P OL ARIT Y S ENSIT V E.
30 W ARNING: If you do not follow these instructions exactly , a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance does not have a pilot. It is equippe d with an ignition device which automatically lights the burner .
31 The water temperature is controlled using the T emperature Control on the Display at the front of the unit (See Figure 1). Thiscontrol utilizes a temperatureprobe to determine thetank temperature.
32 USING THE ELECTRONIC CONTROLLER 1. Overview Interactionwith thewaterheater controllerisdone throughan up,adown, andthree operationbuttons.
33 3. Adjusting the Operating Set Point The Operating Set Point ofthiswaterheaterdeterminestheregulated temperatureforthewaterinthetank.
34 3. Changing the Display Units The display interface to the heater has the option of selecting between degrees Fahrenheit and degrees Celsius for temperature displays. Thiscan befound inthe “DisplaySettings” menu.
35 ACTION: T ogettothecurrentfaultinformationscreen,press Menu. DISPLA Y : ACTION: Press the DOWN buttontohighlight"currentFault"andpress Select. DISPLA Y : ACTION: Press the DOWN button for more information.
36 FOR YOUR INFORMA TION ST ART UP CONDITIONS SMOKE/ODOR Itis notuncommonto experienceasmall amountofsmoke and odor during the initial start-up. This is due to burning off of oil frommetalparts,andwilldisappearinashortwhile.
37 VENTING SYSTEM INSPECTION At least once a year a visual inspection should be made of the venting system.Y oushouldlookfor: 1.Obst ruc tion s whi ch coul d cau se impr ope r ven ting .
38 INST ALLED IN SUIT ABLE AREA: T o insure sufcient ventilat ion and combu stion air supply , proper clearan ces from the wat er heat er mus t be maintained. See “Facts to Consider About Location” section.
39 LEAKAGE CHECKPOINTS Neveruse thiswater heaterunlessit iscompletelylled withwater . T o prevent damage to the tank, the tank must be lled with water .
40 PROBLEMS NOT ENOUGH HOT W A TER 1.)Blowerwillnotrun. a.“ON/OFF”controlswitchturnedoff. T urnswitchtothe“ON”position. b.Blowerunplugged. Plugblowerbackinto1 15V ACoutlet.
41 NOTES.
42 NOTES.
43 Limited W arranty StateW aterHeaters,thewarrantor,extendsthefollowingLIMITEDW ARRANTYtotheownerofthiswaterheater .
44 500T ennesseeWaltzParkway , AshlandCity ,TN37015 Phone:800-821-2017•Fax:800-644-9306 Website: www .statewaterheaters.
Een belangrijk punt na aankoop van elk apparaat State Industries Power Vent/Power Direct Vent Gas Models (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen State Industries Power Vent/Power Direct Vent Gas Models heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens State Industries Power Vent/Power Direct Vent Gas Models vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding State Industries Power Vent/Power Direct Vent Gas Models leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over State Industries Power Vent/Power Direct Vent Gas Models krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van State Industries Power Vent/Power Direct Vent Gas Models bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de State Industries Power Vent/Power Direct Vent Gas Models kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met State Industries Power Vent/Power Direct Vent Gas Models . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.