INSTALLATION INSTRUCTIONSp.1SPLIT AIR CONDITIONER OUTDOOR SECTIONp.1SPLIT AIR CONDITIONER MODEL NOMENCLATUREp.3HAC 36 1 – A DXXXp.3FIGURE 1 UNIT DIMENSIONAL DRAWINGp.3ALTERNATE ELECTRICAL ENTRANCESp.3ON BACKp.3HIGH VOLTAGEp.3ENTRANCEp.3LOW VOLTAGEp.3REFRIGERANTp.3SHUTOFFp.3VALVESp.3MIS-1789p.3TABLE 1 UNIT DIMENSIONSp.3TABLE 2 RATED CFM AND AIR FLOW DATAp.4(WET COIL – COOLING)p.4APPLICATION and LOCATIONp.6GENERALp.6LOCATIONp.6MOUNTING UNIT OUTSIDE ON SLABp.6SHIPPING DAMAGEp.6APPLICATIONp.6IMPORTANT INSTALLER NOTEp.6INSTALLATION REFRIGERANT TUBINGp.6FIGURE 2 INSTALLATION CLEARANCEp.6MIS-589p.6FIGURE 3 INSTALLING REFRIGERANT TUBINGp.7CAUTIONp.7SWEAT STYLE TUBING CONNECTIONS: SWEAT INDOOR UNIT and SWEAT OUTDOOR UNITp.7FIGURE 4 FLOW CONTROL ASSEMBLY FIELD ORIFICE REPLACEMENT INSTRUCTIONSp.7WARNINGp.8TABLE 4 TUBING CHARTp.8TABLE 5 COUPLINGSp.10WIRING INSTRUCTIONSp.11TABLE 7 CONTROL DIAGRAMSp.11CONTROL CIRCUIT WIRINGp.11WALL THERMOSTATSp.11TABLE 8 WALL THERMOSTAT and SUBBASEp.11TABLE 6 CONTROL CIRCUIT WIRINGp.11COMBINATIONSp.11OPTIONAL CONTROLSp.14INSTALLATION INSTRUCTIONS — CMA-6p.14FIGURE 5 COMPONENT MOUNTING LOCATIONp.14SK109 LOW VOLTAGE START KITp.14CMA-10A & CMA-13A COMPRESSOR CONTROLp.14MIS-1302p.14INSTALLATION INSTRUCTIONS — CMA-5p.14FIGURE 7 INSTALLATION INSTRUCTIONS FOR CMA-6 LOW AMBIENT FAN CYCLING CONTROLp.14FIGURE 6 INSTALLATION INSTRUCTIONS FOR CMA-5 COMPRESSOR TIME DELAY RELAYp.14MIS-594p.14MIS-598p.14INSTALLATION INSTRUCTIONS – CMA-10Ap.15FIGURE 8 INSTALLATION INSTRUCTIONS FOR CMA-10A DUAL PRESSURE CONTROL andp.15COMPRESSOR TIME DELAY RELAYp.15MIS-1303p.15INSTALLATION INSTRUCTIONS – CMA-13Ap.16and COMPRESSOR TIME DELAY RELAYp.16MIS-1304p.16CHARGING INSTRUCTIONSp.17PRESSURE SERVICE PORTSp.17TABLE 9 SYSTEM SUPERHEATp.17SYSTEM START-UP (INDOOR UNITS WITHOUT EXPANSION VALVES)p.17TABLE 10 SATURATED SUCTION TEMPERATURE R-22p.17________ ºFp.17= ________ ºFp.17SCHEDULE FOR TABLE 11p.18A - S A 0 3 Ap.18A - 1 8 1 C A Hp.18A - S A 4 2 Sp.18B 4 2 C Bp.18A - 1 4 2 C A Hp.18B 6 3 C Bp.18A - S A 2 4 Ap.18A - S A 8 4 Ap.18A - 1 2 4 C A Hp.18B 0 6 C Bp.18SERVICEp.19SERVICE HINTSp.19FIGURE 10 FAN BLADEp.19
Page 1 of the Bard HAC601-BD040 user manual — INSTALLATION INSTRUCTIONS
Pagina 1 · klik om te vergroten
Pagina 1

INSTALLATION INSTRUCTIONS

SPLIT AIR CONDITIONER OUTDOOR SECTION

Models: HAC181-AD040 HAC241-AD040 HAC301-AD040 HAC361-AD040 HAC421-AD040 HAC481-AD040 HAC481-BD040 HAC601-AD040 HAC601-BD040 FOR USE WITH: MATCHING INDOOR BLOWER COIL UNITS AND MATCHING ADD ON COIL UNITS ONLY

Bard HAC601-BD040 — INSTALLATION INSTRUCTIONS diagram (page 1)
Afb. 1

Bard Manufacturing Company Bryan, Ohio 43506

Manual No.: 2100-346C Supersedes: 2100-346B File: Volume 1, Tab 4 Date: 09-04-02

Since 1914 . . . Moving ahead just as planned.

© Copyright 2002

Page 2 of the Bard HAC601-BD040 user manual — INSTALLATION INSTRUCTIONS
Pagina 2 · klik om te vergroten
Pagina 2
Page 2 of the Bard HAC601-BD040 user manual — INSTALLATION INSTRUCTIONS
Page 3 of the Bard HAC601-BD040 user manual — FIGURE 1 UNIT DIMENSIONAL DRAWING
Pagina 3 · klik om te vergroten
Pagina 3

SPLIT AIR CONDITIONER MODEL NOMENCLATURE

HAC 36 1 – A DXXX

Electrical Characteristics A – 230/208-60-1 B – 230/208-60-3

Capacity – 3 Ton or approx. 36,000 BTU

FIGURE 1 UNIT DIMENSIONAL DRAWING

W

ALTERNATE ELECTRICAL ENTRANCES

ON BACK

H

HIGH VOLTAGE

ENTRANCE

LOW VOLTAGE

ENTRANCE

REFRIGERANT

SHUTOFF

VALVES

B

F

D

A

E

MIS-1789

TABLE 1 UNIT DIMENSIONS

ModelNo."W" Width"D" Depth"H" HeightABCEF HAC181 HAC24140.0015.0026.005.12520.1884.007.12524.188 HAC301 HAC36145.0015.0026.005.12525.1884.007.12529.188 HAC421 HAC481 HAC60150.0015.0032.006.62528.6884.008.62532.688

Customized Unit Code · Modification Code · Basic Model Number

Page 4 of the Bard HAC601-BD040 user manual — TABLE 2 RATED CFM AND AIR FLOW DATA
Pagina 4 · klik om te vergroten
Pagina 4

TABLE 2 RATED CFM AND AIR FLOW DATA

(WET COIL – COOLING)

RatedAirflow Condensing Unit ModelNo.Evaporator Coil ModelNo.CFMPressure DropHO 2Rated E.S.P.Motor Speed TapRecommended AirFlowRangeSystem Orifice Required HAC181-AA30AS-A S24AS-A BC24B650 650 650.15 .24.35Med550-715 550-715 550-715.052 * .052 * .052 * HAC241AA30AS-A S24AS-A BC24B800 780 750.18 .30.20High700-910 680-890 700-910.055 * .055 .055 * HAC301-AA36AS-A BC36B1,000 1,000.20.30Low850-1,175 850-1,175.063 * .063 * HAC361-AA37AS-A BC36B1,100 1,100.18.27High920-1,220 920-1,220.069 * .069 * HAC421-AA42AS-A A48AS-A BC36B BC60B1,400 1,500 1,200 1,500.30 .26.15 .38High Low1,270-1,550 1,250-1,625 1,020-1,320 1,250-1,625.078 .078 * .078 * .078 * HAC481-A,-BA61AS-B BC60B1,700 1,700.28.25Low1,450-1,875 1,450-1,875.081 * .081 * HAC601-A,-BA61AS-B BC60B1,760 1,800.30.28High1,500-1,950 1,525-1,975.092 .092

Measured across the evaporator coil assembly, including drain pan. External static pressure available for the duct system -- supply and return. All blower coils have multispeed motors, and value shown is at the recommended rated speed. Consult specification air flow charts with the blower coil units for complete information at other speeds.

* IMPORTANT INFORMATION Proper sized orifice is not factory installed in indoor section. Proper orifice size is shipped with outdoor unit packaged with its installation instructions for indoor sections listed on this page. The orifice must be replaced with the proper system orifice shown above in Table 2.

For other evaporator coil models not listed, see indoor coil installation instructions for proper orifice information.

Page 5 of the Bard HAC601-BD040 user manual — TABLE 2 RATED CFM AND AIR FLOW DATA
Pagina 5 · klik om te vergroten
Pagina 5
MODELSHAC181-AHAC241-AHAC301-AHAC361-AHAC421-AHAC481-AHAC481-BHAC601-AHAC601-B ElectricalRating(60HZ/V/PH)230/208-1230/208-1230/208-1230/208-1230/208-1230/208-1230/208-3230/208-1230/208-3 OperatingVoltageRange197-253197-253197-253197-253197-253197-253187-253197-253187-253 MinimumCircuitAmpacity151519202526173521 ¬ FieldWireSize14141212101012810 ! DelayFuseMaximumorCircuitBreaker202030304045256035 TotalUnitAmps 230/2087.9/8.610.2/11.413.4/14.014.5/15.819.1/19.619.4/21.012.8/13.422.7/26.715.3/17.2 COMPRESSOR Volts 230/208230/208230/208230/208230/208230/208230/208230/208230/208230/208 RatedLoadAmps6.8/7.59.1/10.312.3/12.913.4/14.717.6/18.117.9/19.511.3/11.921.2/25.213.8/15.7 BranchCircuitSelectionCurrent8.610.313.714.718.119.512.626.315.7 LockRotorAmps 230/20849/4956/5675/7582/82105/105102/10291/91135/135150/150 CrankcaseHeatNoneNoneNoneNoneImmersion TypeImmersion TypeImmersion TypeNoneNone FANMOTORandCONDENSER FanMotor–HP/RPM1/6–8251/6–8251/6–8251/6–8251/4–8251/4–8251/4–8251/4–8251/4–825 FanMotor–Amps1.11.11.11.11.51.51.51.51.5 Fan–Diameter20"–2,00020"–2,00020"–2,00020"–2,00024"–2,60024"–2,60024"–2,60024"–2,60024"–2,600 SWEATCONNECTSYSTEM SuctionLineSizeID5/8"3/4"3/4"3/4"7/8"7/8"7/8"7/8"7/8" LiquidLineSizeID1/4"3/8"3/8"3/8"3/8"3/8"3/8"3/8"3/8" FactoryChangeR-22Oz.73oz.79oz.84oz.96oz.102oz.155oz.155oz.153oz.153oz. SHIPPINGWEIGHT–LBS.155155180180250250250255255

R E S N E D N O C d n a R O T O M N A F

M E T S Y S T C E N N O C T A E W S

R O S S E R P M O C

Page 6 of the Bard HAC601-BD040 user manual — MIS-589
Pagina 6 · klik om te vergroten
Pagina 6

APPLICATION and LOCATION

GENERAL

LOCATION

The condensing unit is designed to be located outside with free and unobstructed condenser air inlet and discharge. It must also permit access for service and installation. Condenser air enters the coil from the rear of the unit as shown in Figure 2 with electrical service access.

These instructions explain the recommended method to install the air cooled remote type condensing unit, the interconnecting refrigerant tubing and the electrical wiring connections to the unit.

The condensing units are to be used in conjunction with the matching evaporator coils or evaporator blower units for comfort cooling applications as shown in the specification sheet.

MOUNTING UNIT OUTSIDE ON SLAB

A solid level base or platform, capable to support the unit’s weight, must be set at the outdoor unit predetermined location. The base should be at least two inches larger than the base dimensions of the unit and at least two inches higher than surrounding grade level. The required unit minimum installed clearances must be maintained as called out in Figure 2 when locating and setting the base.

These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.

Remove the unit from its shipping carton and position the unit on the prepared base or platform.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving part must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

Consideration should be given to the electrical and tubing connections when placing the unit to avoid unnecessary bends or length of material.

APPLICATION

Size of unit for a proposed installation should be based on heat loss calculation and air duct sizing made according to methods of Air Conditioning Contractors of America. The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor coil with a dishwashing detergent.

INSTALLATION REFRIGERANT TUBING

The information that follows on installing refrigerant tubing and for changing the system orifice (if required) covers applications listed in the front of this installation instruction only. Although other indoor units may be of similar construction, the installation instructions for these units should be consulted for proper installation of those units prior to installation.

FIGURE 2 INSTALLATION CLEARANCE

This information is provided for the field service personnel to install refrigerant tubing in compliance with Section 608 of Title VI National Recycling and Emission Reduction Program for the U.S. Clean Air Act effective July 1, 1992.

Consult manual 2100-002 on procedure for leak test – evacuation – charging before installation refrigerant tubing that requires any refrigerant recovery or system evacuation. Manual 2100-002 is included with the unit installation instruction package when shipped from the factory.

MIS-589

Page 7 of the Bard HAC601-BD040 user manual — CAUTION
Pagina 7 · klik om te vergroten
Pagina 7

FIGURE 3 INSTALLING REFRIGERANT TUBING

If the orifice does not have to be changed, skip the instructions outlined further in Step 3 and proceed to Step 8.

Bard HAC601-BD040 — FIGURE 3 INSTALLING REFRIGERANT TUBING diagram (page 7)
Afb. 2
3. Disassemble Flow Control Assembly by turning body hex.
4. If existing orifice has not dropped out of the body when disassembled, remove by using a pin or paper clip. Discard this original orifice.
5. Insert proper sized orifice fully into the flow control body with rounded “bullet” nose towards the unit as shown in Figure 4. Insure the orifice stays inserted in body before connecting mating half. See chart in the outdoor unit installation instructions for proper size.

CAUTION

SWEAT STYLE TUBING CONNECTIONS: SWEAT INDOOR UNIT and SWEAT OUTDOOR UNIT

Be sure there is no dirt introduced into the flow control - orifice assembly. Be sure to install the orifice with the bullet nose pointing in the proper direction as shown in Figure 4. Failure to do so will result in improper operation.

Use only refrigeration grade (dehydrated and sealed) copper tubing. Care must be taken to insure that the tubing is kept clean and dry before and during installation. Do not remove the plugs from the tubing ends, coil connections or base valves until the connection is ready to be brazed.

FIGURE 4 FLOW CONTROL ASSEMBLY FIELD ORIFICE REPLACEMENT INSTRUCTIONS

The suction line must be insulated with a minimum of 3/8” Armaflex or equivalent before cutting and making connections.

1. Being careful not to kink, route both the suction line and liquid line between the indoor unit and outdoor unit. Use a tubing bender to make any necessary bends in tubing. When necessary to bend the insulated tube suction line, cut the insulation around its circumference at a distance far enough beyond the point of the bend so as to clear the tubing bender. Slip the insulation back together and vapor seal the joint with tape. Coil any excess tubing in a horizontal place with the slope of the tubing toward the condensing unit. See Figure 3.

Bard HAC601-BD040 — FIGURE 4 FLOW CONTROL ASSEMBLY FIELD ORIFICE REPLACEMENT INSTRUCTIONS diagram (page 7)
Afb. 3
6. Thread assembly halves together by hand to insure proper mating of threads and tighten until bodies “bottom” or a definite resistance is felt.

CAUTION

7. Using a marker pen or ink pen, mark a line lengthwise from the union nut to the bulkhead. Then tighten an additional 1/6 turn (or 1 hex flat). The misalignment of the line will show the amount the assembly has been tightened. This final 1/6 turn is necessary to insure the formation of the leakproof joint.
1. Be careful not to tear the insulation when pushing it through hole in masonry or frame walls. 2. When sealing the tube opening in house wall, use a soft material to prevent tube damage and vibration transmission. 3. Avoid excessive bending in any one place to avoid kinking.
8. Wrap a wet rag around the copper stub before brazing.
9. Flux the copper tube and insert into the stub. Braze the joint using an alloy of silver or copper and phosphorus with a melting temperature above 1,100° F for copper to copper joints. The phosphorus will act as a flux, therefore, no flux will be required.
2. The tubing ends should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contaminants from entering the system.

pp5 · pp5

Page 8 of the Bard HAC601-BD040 user manual — TABLE 4 TUBING CHART
Pagina 8 · klik om te vergroten
Pagina 8

A copper-silver alloy with a high silver content should be used when iron or steel material is involved in the joint. These alloys require the use of silver solder flux. Alloys containing phosphorus should not be used with iron or steel. Phosphorus reacts with the iron forming iron phosphate which is extremely brittle.

FIELD FABRICATED TUBING CONNECTIONSQUICK CONNECT INDOOR UNIT and SWEAT OUTDOOR UNIT USING CTO KIT

Use only refrigeration grade (dehydrated and sealed) copper tubing. Care must be taken to insure that the tubing is kept clean and dry before and during installation. Do not remove the plugs from the tubing ends, coil connections or base valves until the connection is ready to be brazed.

CAUTION

The suction line must be insulated with a minimum of 3/8” Armaflex or equivalent before cutting and making connections.

1. Brazing alloys with a melting temperature below 700° F should not be used. 2. Leadtin or tin-antimony solders should not be used due to their low melting point and necessity for corrosive fluxes.

1. Being careful not to kink, route both the suction line and liquid line between the indoor unit and outdoor unit. Use a tubing bender to make any necessary bends in tubing. When necessary to bend the insulated tube suction line, cut the insulation around its circumference at a distance far enough beyond the point of the bend so as to clear the tubing bender. Slip the insulation back together and vapor seal the joint with tape. Coil any excess tubing in a horizontal place with the slope of the tubing toward the condensing unit. See Figure 3.

To further prevent the formation of copper oxide inside the tubing, dry nitrogen may be purged through the refrigerant system during brazing.

WARNING

CAUTION

Never purge or pressurize a system with oxygen. An explosion and fire will result.

1. Be careful not to tear the insulation when pushing it through hole in masonry or frame walls. 2. When sealing the tube opening in house wall, use a soft material to prevent tube damage and vibration transmission. 3. Avoid excessive bending in any one place to avoid kinking.
10. After brazing, quench with wet rag to cool the joint and remove any flux residue.
11. Leak test all connections using an electronic leak detector or a halide torch.
12. Evacuate suction line, liquid line and indoor unit through outdoor unit base valves.
13. Open both the suction and liquid base valves to the fully open position. Refer to section later in installation instructions for details on setting proper system charge.

TABLE 4 TUBING CHART

Basic Condensing UnitModelRefrigerantLineLength (Ft.) 0-2021-6061-100 LiquidSuctionLiquidSuctionLiquidSuction HAC1811/4"5/8"1/4"5/8"3/8"3/4" HAC2413/8"5/8"3/8"3/4"3/8"3/4" HAC3013/8"5/8"3/8"3/4"3/8"3/4" HAC3613/8"5/8"3/8"3/4"1/27/8" HAC4213/8"3/4"3/8"7/8"1/27/8" HAC4813/8"7/8"3/8"7/8"1/21-1/8" HAC6013/8"7/8"3/8"7/8"1/21-1/8"
Page 9 of the Bard HAC601-BD040 user manual — WARNING
Pagina 9 · klik om te vergroten
Pagina 9
2. The tubing ends should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contaminants from entering the system.
8. Recover charge from the indoor unit.

A. Connect the suction line only to the indoor unit as

outlined in Steps 15, 16, and 17.

B. Recover indoor unit and suction line unit charge

through service port located on outdoor unit base valve.

3. Wrap a wet rag around the copper stub before brazing.
9. Disassemble Flow Control Assembly by turning body hex.
4. Flux the copper tube and insert into the stub. Braze the joint using an alloy of silver or copper and phosphorus with a melting temperature above 1,100° F for copper to copper joints. The phosphorus will act as a flux, therefore, no flux will be required.
10. If existing orifice has not dropped out of the body when disassembled, remove by using a pin or paper clip. Discard this original orifice.
11. Insert proper sized orifice fully into the flow control body with rounded “bullet” nose towards the unit as shown in Figure 4. Insure the orifice stays inserted in body before connecting mating half. See chart in the outdoor unit installation instructions for proper size.

A copper-silver alloy with a high silver content should be used when iron or steel material is involved in the joint. These alloys require the use of silver solder flux. Alloys containing phosphorus should not be used with iron or steel. Phosphorus reacts with the iron forming iron phosphate which is extremely brittle.

CAUTION

To further prevent the formation of copper oxide inside the tubing, dry nitrogen may be purged through the refrigerant system during brazing.

Be sure there is no dirt introduced into the flow control – orifice assembly. Be sure to install the orifice with the bullet nose pointing in the proper direction as shown in Figure 4. Failure to do so will result in improper operation.

CAUTION

1. Brazing alloys with a melting temperature below 700° F should not be used. 2. Lead-tin or tin-antimony solders should not be used due to their low melting point and necessity for corrosive fluxes.
12. Thread assembly halves together by hand to insure proper mating of threads and tighten until bodies “bottom” or a definite resistance is felt.
13. Using a marker pen or ink pen, mark a line lengthwise from the union nut to the bulkhead. Then tighten an additional 1/6 turn (or 1 hex flat). The misalignment of the line will show the amount the assembly has been tightened. This final 1/6 turn is necessary to insure the formation of the leakproof joint.

WARNING

Never purge or pressurize a system with oxygen. An explosion and fire will result.

14. Evacuate the suction line and indoor unit through the outdoor unit base valve before connecting all other tubing. Refer to section later in installation instructions for details on setting the proper refrigerant charge.
5. After brazing, quench with wet rag to cool the joint and remove any flux residue.
15. Remove (remaining) protector caps and plugs (if orifice was changed). Inspect fittings and if necessary carefully wipe coupling seats and threaded surfaces with a clean cloth to prevent the inclusion of dirt or any foreign material in the system.
6. Leak test all connections using an electronic leak detector or a halide torch.
7. Evacuate suction line and liquid line through outdoor unit base valves.

If orifice does not have to be changed, skip the instructions outlined further in Step 8 and proceed to Step 15.

Page 10 of the Bard HAC601-BD040 user manual — CAUTION
Pagina 10 · klik om te vergroten
Pagina 10
16. Lubricate male half diaphragm and synthetic rubber seal with refrigerant oil. Thread coupling halves together by hand to insure proper mating of threads. Be sure to hold the coupling firmly to prevent movement of the coupling and tubing. Failure to do so could tear out the diaphragm causing a blockage of the system. Use proper size wrenches (on coupling body hex and on union nut) and tighten until coupling bodies ”bottom” or a definite resistance is felt.

TABLE 5 COUPLINGS

CouplingSizeFeetPounds -610-12 -1035-45 -1135-45 -1250-65

CAUTION

18. Leak test all connections using an electronic leak detector or a halide torch.

19. When tubing is installed in attics or drop ceilings, insulate the couplings on the larger tube thoroughly with 3/8” wall thickness, closed cell sponge tube insulation or equivalent. Failure to insulate will result in water damage to ceiling since the fitting will “sweat” and drop water on the ceiling. 17. Using a marker or ink pen, mark a line lengthwise from the coupling union nut to the bulkhead. Then tighten an additional 1/4 turn. The misalignment of the line will show the amount the coupling has been tightened. This final 1/4 turn is necessary to insure the formation of leakproof joint. If a torque wrench is used, the torque values shown in Table 5 are recommended.

After starting to tighten up the fitting, never try to back it off or take it apart.

Page 11 of the Bard HAC601-BD040 user manual — TABLE 8 WALL THERMOSTAT and SUBBASE
Pagina 11 · klik om te vergroten
Pagina 11

WIRING INSTRUCTIONS

GENERAL

Example: 1. Control circuit transformer rated at 40 VA 2. Maximum total distance of control circuit wiring 85 feet. From Table 6, minimum of 18 gauge wire should be used in the control circuit wiring.

All wiring must be installed in accordance with the National Electrical Code and local codes. In Canada, all wiring must be installed in accordance with the Canadian Electrical Code and in accordance with the regulations of the authorities having jurisdiction. Power supply voltage must conform to the voltage shown on the unit serial plate. A wiring diagram of the unit is attached to the inside of the electrical cover. The power supply shall be sized and fused according to the specification supplied. A ground lug is supplied in the control compartment for equipment ground.

For control circuit transformers rated other than those listed, use the next lower rated transformer listed. Example: 1. Control circuit transformer rated at 55 VA From table use 50VA transformer.

There are two (2) separate control diagrams for fossil fuel furnaces with air conditioners.

The unit rating plate lists a “Maximum Time Delay Fuse” or HACR type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

Control diagrams for the various circuit which could be encountered with blower coils can be found in the installation instructions of the blower coil.

TABLE 7 CONTROL DIAGRAMS

CONTROL CIRCUIT WIRING

For split systems, the minimum control circuit wiring gauge needed to insure proper operation of all controls in both indoor and outdoor units will depend on two factors:

SystemGasFurnace ControlDiagramOilFurnace ControlDiagram AllModels4091-1004091-101
1. The rated VA of the control circuit transformer.
2. The maximum total distance of the control circuit wiring. (This is the distance between the wall thermostat to the indoor unit plus the distance between the indoor unit to the outdoor unit.)

WALL THERMOSTATS

The following wall thermostats and subbases should be used as indicated, depending on the application.

The following table should be used to determine proper gauge of control circuit wiring required.

TABLE 8 WALL THERMOSTAT and SUBBASE

TABLE 6 CONTROL CIRCUIT WIRING

COMBINATIONS

ThermostatSubbasePredominateFeatures 8403-002 T87F3118404-003 Q529A12201stageheat,1stagecool; Mercury System: heat-off-cool Fan: on-auto 8403-041 T8034-C---1stageheat, 1stagecool; Mercury System: heat-off-cool Fan: on-auto 8403-035 1F95-80---2stageheat,2stagecool Programmable Electronic 8403-042 T8511G---2stageheat, 1stagecool System: heat-off-auto-cool Fan: on-auto Electronic 8403-043 CM200---1stageheat, 1stagecool System: heat-off-cool Fan: on-auto SnapAction 8403-027 1F92-71---3stageheat, 2stagecool Programmable Electronic
RatedVAof ControlCircuit TransformerTransformer Secondary FLA@24VMximumTotal Distanceof ControlCircuit WiringinFeet 401.620gauge 65 18gauge 90 16gauge 145 14gauge 230 502.120gauge 45 18gauge 60 16gauge 100 14gauge 160 12gauge 250 652.720gauge 40 18gauge 55 16gauge 85 14gauge 135 12gauge 210
Page 12 of the Bard HAC601-BD040 user manual — WIRING INSTRUCTIONS
Pagina 12 · klik om te vergroten
Pagina 12
Page 12 of the Bard HAC601-BD040 user manual — WIRING INSTRUCTIONS
Page 13 of the Bard HAC601-BD040 user manual — WIRING INSTRUCTIONS
Pagina 13 · klik om te vergroten
Pagina 13
Page 13 of the Bard HAC601-BD040 user manual — WIRING INSTRUCTIONS
Page 14 of the Bard HAC601-BD040 user manual — FIGURE 6 INSTALLATION INSTRUCTIONS FOR CMA-5 COMPRESSOR TIME DELAY RELAY
Pagina 14 · klik om te vergroten
Pagina 14

OPTIONAL CONTROLS

INSTALLATION INSTRUCTIONS — CMA-6

FIGURE 5 COMPONENT MOUNTING LOCATION

Disconnect all power to unit. Remove control panel inner and outer cover.

1. Mount terminal block in position shown in Figure 5.

CMA-5 & CMA-13A LOW AMBIENT FAN CYCLING CONTROL TERMINAL BLOCK CMA-5 COMPRESSOR TIME DELAY RELAY

2. Disconnect black high voltage outdoor motor lead from compressor contactor and reconnect to terminal block.
Bard HAC601-BD040 — OPTIONAL CONTROLS diagram (page 14)
Afb. 4
3. Route low ambient control wires up through the bushing in the bottom of the control panel. Connect the low ambient control wires between the terminal block and T2 of the compressor contactor.
4. Remove service port cap on discharge line. Install the low ambient control on the discharge line with the flare tee adapter that is brazed to the low ambient control. Check for pressure at the flare tee dill valve after installation to insure that the dill valve in the unit service port was depressed by the flare tee connector. Check for leaks at the flare tee connectors. Replace service port cap on the flare tee service port and tighten.

SK109 LOW VOLTAGE START KIT

CMA-10A & CMA-13A COMPRESSOR CONTROL

MIS-1302

5. Recheck wiring. See Figure 10. Check for proper operation of the unit by energizing in cooling mode. The condenser fan motor should not run until the discharge pressure has exceeded 300 PSI. Should the discharge pressure fall below 200 PSI while running, the condenser fan motor will de-energize until the head pressure builds to 300 PSI.

INSTALLATION INSTRUCTIONS — CMA-5

Disconnect all power to the unit. Remove control panel cover.

1. Mount compressor TDR in position shown in Figure 5 with screw provided.
6. Apply “This unit equipped with CMA-6 control module” label to the inside of the control panel cover above the wiring diagrams.
2. Disconnect yellow low voltage (Y) wire at the compressor contactor coil and reconnect to the Y1 or #3 terminal of the TDR.
7. Replace all panels and covers. This completes installation.
3. Connect yellow wire from terminal (Y) of the TDR to the (Y) terminal of the compressor contactor coil. This is the terminal that the wire was removed from in Step 2.

FIGURE 7 INSTALLATION INSTRUCTIONS FOR CMA-6 LOW AMBIENT FAN CYCLING CONTROL

4. Recheck wiring. Refer to Figure 9. Energize unit. Compressor should start. Remove power and reapply. Compressor should not start until the 5 minute time delay has expired.
Bard HAC601-BD040 — FIGURE 7 INSTALLATION INSTRUCTIONS FOR CMA-6 LOW AMBIENT FAN CYCLING CONTROL diagram (page 14)
Afb. 5
5. Apply “This unit equipped with CMA-5 control module” label to inside of the inner control panel cover above wiring diagram.
6. Replace all panels and covers. This completes installation.

FIGURE 6 INSTALLATION INSTRUCTIONS FOR CMA-5 COMPRESSOR TIME DELAY RELAY

MIS-594

MIS-598

Page 15 of the Bard HAC601-BD040 user manual — MIS-1303
Pagina 15 · klik om te vergroten
Pagina 15

INSTALLATION INSTRUCTIONS – CMA-10A

7.Remove service port caps on both the suction and

discharge lines. Install the high pressure switch on the discharge line to the flare tee adapter that is brazed to the controls. Install the low pressure switch on the suction line. Check for pressure at the flare tee dill valves after installation to insure that the dill valve in the unit service port was depressed by the flare tee connector. Check for leaks at the flare tee connectors. Replace service port caps on the flare tee service ports and tighten.

Disconnect all power to unit. Remove control panel cover.

1. Screw compressor control module and terminal block into control panel as shown in Figure 5.
2. Disconnect yellow low voltage wire form compressor contactor and reconnect to terminal “Y” of the compressor control module.
3. Connect the yellow wire from the compressor control module to “Y” side of the compressors contactor coil. This is the same terminal from which the wire was removed in Step 2.
8. Adjust the compressor time delay relay to the desired delay on break. Two minutes are recommended. This TDR is variable form 30 seconds to 5 minutes.
4. Connect the black wire form the compressor control module to common “C” side of the compressor contactor coil.
9. Recheck wiring. Energize unit is first stage cooling. Compressor should not start until the time delay has expired. This will be 10% of the delay on break period. Run the unit for at least 5 minutes. The unit should not go into lockout.
5. Connect a field supplied wire from “R” of the indoor unit to “R” on the compressor control module.
10. Apply “ This unit equipped with CMA-10A control module. ” label to the inside of the inner control panel cover above the wiring diagram.
6. Route the high (red) and low (blue) pressure switch wires through the bushing in the bottom of the control panel. Connect the low pressure switch wire to terminals LPC of the compressor control module.
11. Replace all panels and covers. This completes installation.

FIGURE 8 INSTALLATION INSTRUCTIONS FOR CMA-10A DUAL PRESSURE CONTROL and

COMPRESSOR TIME DELAY RELAY

Bard HAC601-BD040 — FIGURE 8 INSTALLATION INSTRUCTIONS FOR CMA-10A DUAL PRESSURE CONTROL and diagram (page 15)
Afb. 6 · FIGURE 8 INSTALLATION INSTRUCTIONS FOR CMA-10A DUAL…

MIS-1303

Page 16 of the Bard HAC601-BD040 user manual — MIS-1304
Pagina 16 · klik om te vergroten
Pagina 16

INSTALLATION INSTRUCTIONS – CMA-13A

the high voltage outdoor motor lead was removed in Step 7.

Disconnect all power to unit. Remove control panel cover.

9. Remove service port caps on both the suction and discharge lines. Install the high pressure switch and the low ambient control on the discharge line with the flare tee adapter that is brazed to the controls. Install the low pressure switch on the suction line. Check for pressure at the flare tee dill valves after installation to insure that the dill valve in the unit service port was depressed by the flare tee connector. Check for leaks at the flare tee connectors. Replace service port caps on the flare tee service ports and tighten.

1. Screw compressor control module and terminal block into control panel as shown in Figure 5.
2. Disconnect yellow low voltage wire from compressor contactor and reconnect to terminal “Y” of the compressor control module.
3. Connect the yellow wire from the compressor control module to “Y” side of the compressor’s contactor coil. This is the same terminal from which the wire was removed in Step 2.
10. Adjust the compressor time delay relay to the desired delay on break. Two minutes are recommended. This TDR is variable from 30 seconds to 5 minutes.
4. Connect the black wire from the compressor control module to common “C” side of the compressor contactor coil.

11. Recheck wiring. Energize unit in first stage cooling. Compressor should not start until the time delay has expired. This will be 10% of the delay on break period. Run the unit for at least 5 minutes. The unit should not go into lockout. The condenser fan motor should not run until the discharge pressure has exceeded 300 PSI. Should the discharge pressure fall below 200 PSI while running the condenser fan motor will de-energize until the head pressure builds to 300 PSI.

5. Connect a field supplied wire from “R” of the indoor unit to “R” on the compressor control module.
6. Route the high (red) and low (blue) pressure switch wires through the bushing in the bottom of the control panel. Connect the low pressure switch wire to terminals LPC of the compressor control module. Connect the high pressure switch wires to terminals HPC of the compressor control module.
7. Disconnect the high voltage outdoor motor lead and reconnect to the terminal block installed in Step 1.
12. Apply “ This unit equipped with CMA-13A control module. ” label to the inside of the inner control panel cover above the wiring diagram.
8. Route the LAC (black) wires up through the busing in the bottom of the control panel. Connect one wire to the terminal block and the other to “T2” of the contactor. This will be the same terminal from which
13. Replace all panels and covers. This completes installation.

FIGURE 9 INSTALLATION INSTRUCTIONS FOR CMA-13A DUAL PRESSURE CONTROL, LOW AMBIENT FAN CYCLING CONTROL

and COMPRESSOR TIME DELAY RELAY

Bard HAC601-BD040 — and COMPRESSOR TIME DELAY RELAY diagram (page 16)
Afb. 7 · and COMPRESSOR TIME DELAY RELAY

MIS-1304

Page 17 of the Bard HAC601-BD040 user manual — = ________ ºF
Pagina 17 · klik om te vergroten
Pagina 17

CHARGING INSTRUCTIONS

PRESSURE SERVICE PORTS

TABLE 9 SYSTEM SUPERHEAT

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

t n e i b m A r o o d t u O

e r u t a r e p m e T ri A n r u t e R

b l u B t e W F

F ( e r u t a r e p m e T

) b l u B y r D

9 5 3 6 7 6 1 7

5 0 1 5 9 0 9 5 8 0 8 5 7

1 1 1 3 8 0 1

1 3 7 9 4 1 0 2

5. 8 (

0 2 6 2 3 3 9 3 2 4

SYSTEM START-UP (INDOOR UNITS WITHOUT EXPANSION VALVES)

4 1 9 1 5 2 0 3

1. Close disconnect switch(es) and set the thermostat to cool and the temperature to the highest setting.
2. Check for proper airflow across the indoor coil by referring to indoor unit installation.

TABLE 10 SATURATED SUCTION TEMPERATURE R-22

3. Connect the service gauges and allow the unit to run for at least 10 minutes or until pressures are stable. Check pressures to the system pressure table attached to the outdoor unit service panel. For optimum system performance, go to Step 4.

n o it c u S d e t a r u t a S

G I S P e r u s s e r P n o it c u S

) F ( e r u t a r e p m e T

0 5 3 5 5 5

6 2 8 2 0 3

4. Install a thermometer on the suction line approximately 6" to 10" from the compressor. Optimum system performance will occur with a refrigerant charge resulting in a suction line superheat as determined from the following calculations.

8 5 1 6 3 6

2 3 4 3 6 3

A. Measure outdoor air dry bulb temperature

5 6 7 6 0 7

8 3 9 3 1 4

ºF

B. Measure indoor air wet bulb temperature

ºF

3 7 6 7 9 7

3 4 5 4 7 4

C. Measure suction pressure PSIG

D. Measure suction line temperature ºF

2 8 6 8 9 4 1 5

E. Determine optimum system superheat

from Table 9 using outdoor air dry bulb (Step B) and indoor air wet bulb (Step A)

ºF

F. Determine saturated suction temperature

from suction pressure using Table 10 ºF

G. Determine system superheat:

Suction line temperature (Step D) ºF - Saturated suction temperature (Step F)

- ºF = System superheat

= ºF

H. Adjust the system superheat (Step G) to the

optimum system superheat (Step E) by adding charge to lower the superheat or removing charge to raise the superheat.

I. Check final system operating pressures to the system pressure tables as was done in Step 3.

Page 18 of the Bard HAC601-BD040 user manual — B 0 6 C B
Pagina 18 · klik om te vergroten
Pagina 18

TABLE 11 TOTAL SYSTEM OPERATING CHARGE (Includes charge for the basic outdoor unit, indoor coil and 25’ of interconnecting tubing.)

SCHEDULE FOR TABLE 11

r e t e m a i D e n i L d i u q i L .t F r e P 2 2 - R .z O

" 4 / 1 " 8 / 3 " 2 / 1

5 2 . 0 0 6 . 0 0 2 . 1

2 2 - R l a t o T

n o it c e S r o o d t u O n o it c e S r o o d n I

).z O ( e g r a h C

Installer Note: Stamp or mark the final system charge determined above on the outdoor unit serial plate.

A - S A 0 3 A

.z o 3 7 .z o 3 7 .z o 8 7

A - 1 8 1 C A H

A - S A 4 2 S

B 4 2 C B

A - S A 0 3 A

.z o 0 8 .z o 0 8 .z o 9 7

A - 1 4 2 C A H

A - S A 4 2 S

B 4 2 C B

A - 1 0 3 C A H A - S A 6 3 A

.z o 4 8 .z o 5 9

B 6 3 C B

A - 1 6 3 C A H A - S A 7 3 A

.z o 8 9 .z o 6 9

B 6 3 C B

A - S A 2 4 A

.z o 2 0 1 .z o 7 1 1 .z o 5 0 1 .z o 2 4 1

A - S A 8 4 A

A - 1 2 4 C A H

B 6 3 C B

B 0 6 C B

B - , A - 1 8 4 C A H A - S A 1 6 A

.z o 5 5 1 .z o 5 7 1

B 0 6 C B

B - , A - 1 0 6 C A H A - S A 1 6 A

.z o 3 5 1 .z o 5 6 1

B 0 6 C B

Includes 25’ of 1/4” diameter liquid line. For other than 25’ and other tube sizes, adjust the total charge according to the following schedule.

Includes 25’ of 3/8” diameter liquid line. For other than 25’ and other tube sizes, adjust the total charge according to the following schedule.

Show 9 more labels / short text on this page
· · · · · · · ·
Page 19 of the Bard HAC601-BD040 user manual — 1 8 1 C A H
Pagina 19 · klik om te vergroten
Pagina 19

SERVICE

SERVICE HINTS

FIGURE 10 FAN BLADE

1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life, as well as, increasing operating costs.
Bard HAC601-BD040 — SERVICE HINTS diagram (page 19)
Afb. 8
2. Check all power fuses or circuit breakers to be sure that they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and unrestricted air flow circulation is essential.

FAN BLADE SETTING DIMENSIONS

B

Shown in Figure 10 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

A

TABLE 12 FAN BLADE SETTING

l e d o M A n o i s n e m i D s n o it a c o L b u H n a F

1 8 1 C A H

1 4 2 C A H

" 5 B

1 0 3 C A H

1 6 3 C A H

1 2 4 C A H

1 8 4 C A H

" 4 / 3 - 4 C

1 0 6 C A H

7960-337

Page 20 of the Bard HAC601-BD040 user manual — SERVICE
Pagina 20 · klik om te vergroten
Pagina 20
Bard HAC601-BD040 — SERVICE diagram (page 20)
Afb. 9
Page 21 of the Bard HAC601-BD040 user manual — SERVICE
Pagina 21 · klik om te vergroten
Pagina 21
Bard HAC601-BD040 — SERVICE diagram (page 21)
Afb. 10
Page 22 of the Bard HAC601-BD040 user manual — B 4 2 C B
Pagina 22 · klik om te vergroten
Pagina 22

TABLE 13 PRESSURE TABLE

HAC181-A

li o C r o o d t u O g n ir e t n E e r u t a r e p m e T ri A

r o o d n I

ri A n r u t e R

n o it c e S

. p m e T e r u s s e r P

5 6 0 7 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

B D 5 7 B W 2 6 e di S w o L

8 6 0 5 1 0 7 0 7 1 2 7 7 8 1 4 7 3 0 2 6 7 6 2 2 8 7 4 4 2 0 8 4 5 2 2 8 8 5 2 4 8 5 5 2 5 8 6 4 2 7 8 0 2 3

e di S h gi H

A - S A 0 3 S A

B D 0 8 B W 7 6 e di S w o L

0 7 9 6 1 3 7 3 8 1 6 7 8 9 1 9 7 3 1 2 1 8 8 2 2 4 8 4 4 2 6 8 0 6 2 8 8 6 7 2 0 9 3 9 2 2 9 0 1 3 3 9 8 2 3

A - S A 4 2 S

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

6 7 7 7 1 9 7 1 9 1 2 8 6 0 2 5 8 1 2 2 7 8 6 3 2 0 9 2 5 2 2 9 9 6 2 4 9 6 8 2 6 9 4 0 3 8 9 2 2 3 9 9 0 4 3

e di S h gi H

B D 5 7 B W 2 6 e di S w o L

5 5 2 6 1 2 6 8 7 1 8 6 3 9 1 3 7 9 0 2 8 7 4 2 2 1 8 0 4 2 4 8 6 5 2 6 8 2 7 2 7 8 8 8 2 7 8 4 0 3 7 8 0 2 3

e di S h gi H

B 4 2 C B

B D 0 8 B W 7 6 e di S w o L

7 7 4 6 1 8 7 0 8 1 8 7 8 9 1 0 8 3 1 2 1 8 0 3 2 2 8 6 4 2 4 8 3 6 2 6 8 0 8 2 8 8 6 9 2 0 9 3 1 3 3 9 9 2 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

6 7 7 7 1 9 7 1 9 1 2 8 6 0 2 5 8 1 2 2 7 8 6 3 2 0 9 2 5 2 2 9 9 6 2 4 9 6 8 2 6 9 4 0 3 8 9 2 2 3 9 9 0 4 3

e di S h gi H

Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

TABLE 14 PRESSURE TABLE

HAC241-A

li o C r o o d t u O g n ir e t n E e r u t a r e p m e T ri A

r o o d n I

ri A n r u t e R

n o it c e S

. p m e T e r u s s e r P

5 6 0 7 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

B D 5 7 B W 2 6 e di S w o L

0 6 2 7 1 4 6 0 9 1 8 6 7 0 2 1 7 4 2 2 4 7 1 4 2 6 7 8 5 2 8 7 5 7 2 0 8 2 9 2 1 8 8 0 3 2 8 5 2 3 2 8 1 4 3

e di S h gi H

A - S A 0 3 S A

B D 0 8 B W 7 6 e di S w o L

6 6 7 7 1 0 7 5 9 1 3 7 3 1 2 6 7 0 3 2 9 7 7 4 2 1 8 5 6 2 3 8 2 8 2 5 8 9 9 2 6 8 6 1 3 7 8 3 3 3 8 8 0 5 3

A - S A 4 2 S

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

3 7 5 8 1 6 7 3 0 2 9 7 0 2 2 2 8 8 3 2 5 8 7 5 2 7 8 3 7 2 9 8 1 9 2 1 9 9 0 3 2 9 6 2 3 4 9 4 4 3 5 9 2 6 3

e di S h gi H

B D 5 7 B W 2 6 e di S w o L

5 6 9 7 1 9 6 4 9 1 3 7 9 0 2 7 7 5 2 2 0 8 1 4 2 2 8 7 5 2 3 8 3 7 2 4 8 0 9 2 5 8 6 0 3 6 8 4 2 3 7 8 1 4 3

e di S h gi H

B D 0 8 B W 7 6 e di S w o L

0 7 4 0 1 3 7 2 5 1 5 7 2 9 1 7 7 5 2 2 9 7 1 5 2 1 8 9 6 2 3 8 0 8 2 5 8 4 8 2 6 8 1 8 2 8 8 0 7 2 9 8 2 5 2

B 4 2 C B

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

3 7 5 8 1 6 7 3 0 2 9 7 0 2 2 2 8 8 3 2 5 8 6 5 2 7 8 3 7 2 9 8 1 9 2 1 9 9 0 3 2 9 6 2 3 4 9 4 4 3 5 9 2 6 3

e di S h gi H

Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

values listed) · values listed)

Page 23 of the Bard HAC601-BD040 user manual — B 6 3 C B
Pagina 23 · klik om te vergroten
Pagina 23

TABLE 15 PRESSURE TABLE

HAC301-A

li o C r o o d t u O g n ir e t n E e r u t a r e p m e T ri A

r o o d n I

ri A n r u t e R

n o it c e S

. p m e T e r u s s e r P

5 6 0 7 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

B D 5 7 B W 2 6 e di S w o L

2 6 2 6 1 5 6 3 8 1 7 6 4 0 2 9 6 4 2 2 1 7 4 4 2 3 7 2 6 2 5 7 0 8 2 7 7 7 9 2 8 7 3 1 3 0 8 9 2 3 1 8 4 4 3

e di S h gi H

A - S A 6 3 A

B D 0 8 B W 7 6 e di S w o L

8 6 7 6 1 0 7 8 8 1 2 7 0 1 2 4 7 0 3 2 6 7 0 5 2 8 7 9 6 2 0 8 7 8 2 2 8 5 0 3 4 8 1 2 3 5 8 8 3 3 7 8 3 5 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

5 7 1 7 1 7 7 4 9 1 8 7 6 1 2 0 8 8 3 2 2 8 8 5 2 4 8 8 7 2 6 8 7 9 2 8 8 5 1 3 0 9 3 3 3 2 9 9 4 3 4 9 5 6 3

e di S h gi H

B D 5 7 B W 2 6 e di S w o L

1 6 5 8 1 5 6 1 0 2 9 6 7 1 2 2 7 4 3 2 5 7 0 5 2 7 7 6 6 2 9 7 2 8 2 1 8 8 9 2 2 8 4 1 3 3 8 1 3 3 4 8 7 4 3

e di S h gi H

B D 0 8 B W 7 6 e di S w o L

7 6 0 9 1 1 7 7 0 2 4 7 3 2 2 7 7 9 3 2 0 8 6 5 2 2 8 2 7 2 4 8 9 8 2 6 8 6 0 3 7 8 2 2 3 8 8 9 3 3 9 8 6 5 3

B 6 3 C B

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

4 7 8 9 1 7 7 5 1 2 0 8 2 3 2 3 8 8 4 2 6 8 5 6 2 8 8 2 8 2 0 9 9 9 2 2 9 6 1 3 3 9 3 3 3 5 9 1 5 3 6 9 8 6 3

e di S h gi H

Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

TABLE 16 PRESSURE TABLE

HAC361-A

li o C r o o d t u O g n ir e t n E e r u t a r e p m e T ri A

r o o d n I

ri A n r u t e R

n o it c e S

. p m e T e r u s s e r P

5 6 0 7 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

B D 5 7 B W 2 6 e di S w o L

6 6 1 8 1 8 6 7 9 1 0 7 3 1 2 2 7 0 3 2 4 7 6 4 2 6 7 2 6 2 8 7 8 7 2 0 8 4 9 2 2 8 0 1 3 4 8 6 2 3 6 8 3 4 3

e di S h gi H

A - S A 7 3 A

B D 0 8 B W 7 6 e di S w o L

1 7 6 8 1 3 7 2 0 2 5 7 9 1 2 7 7 5 3 2 9 7 2 5 2 1 8 8 6 2 3 8 5 8 2 5 8 2 0 3 7 8 8 1 3 9 8 5 3 3 1 9 1 5 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

7 7 1 9 1 9 7 8 0 2 1 8 6 2 2 3 8 3 4 2 5 8 0 6 2 7 8 8 7 2 9 8 5 9 2 1 9 2 1 3 3 9 0 3 3 5 9 7 4 3 7 9 4 6 3

e di S h gi H

B D 5 7 B W 2 6 e di S w o L

3 6 8 7 1 6 6 5 9 1 8 6 2 1 2 0 7 8 2 2 2 7 5 4 2 4 7 2 6 2 6 7 9 7 2 8 7 6 9 2 9 7 3 1 3 1 8 1 3 3 2 8 8 4 3

e di S h gi H

B D 0 8 B W 7 6 e di S w o L

6 6 4 8 1 9 6 0 0 2 2 7 7 1 2 5 7 4 3 2 8 7 1 5 2 0 8 9 6 2 2 8 6 8 2 4 8 4 0 3 5 8 1 2 3 7 8 9 3 3 8 8 7 5 3

B 6 3 C B

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

2 7 8 8 1 5 7 6 0 2 8 7 4 2 2 1 8 2 4 2 3 8 0 6 2 6 8 8 7 2 8 8 6 9 2 0 9 4 1 3 2 9 2 3 3 4 9 1 5 3 5 9 9 6 3

e di S h gi H

Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

values listed) · values listed)

Page 24 of the Bard HAC601-BD040 user manual — B 0 6 C B
Pagina 24 · klik om te vergroten
Pagina 24

TABLE 17 PRESSURE TABLE

HAC 421-A

li o C r o o d t u O g n ir e t n E e r u t a r e p m e T ri A

r o o d n I

ri A n r u t e R

5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

n o it c e S

. p m e T e r u s s e r P

B D 5 7 B W 2 6 e di S w o L

4 6 3 0 2 7 6 8 1 2 0 7 3 3 2 2 7 0 5 2 4 7 6 6 2 6 7 3 8 2 7 7 0 0 3 8 7 8 1 3 9 7 6 3 3

e di S h gi H

A - S A 2 4 A

B 6 3 C B

B D 0 8 B W 7 6 e di S w o L

9 6 8 0 2 2 7 4 2 2 5 7 0 4 2 7 7 6 5 2 9 7 3 7 2 2 8 0 9 2 2 8 8 0 3 4 8 6 2 3 5 8 5 4 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

3 7 6 1 2 7 7 2 3 2 0 8 8 4 2 3 8 5 6 2 5 8 2 8 2 7 8 0 0 3 9 8 8 1 3 0 9 7 3 3 1 9 9 5 3

e di S h gi H

B D 5 7 B W 2 6 e di S w o L

3 7 2 1 2 4 7 8 2 2 6 7 4 4 2 7 7 0 6 2 9 7 7 7 2 1 8 4 9 2 2 8 2 1 3 4 8 0 3 3 6 8 9 4 3

e di S h gi H

A - S A 8 4 A

B D 0 8 B W 7 6 e di S w o L

7 7 8 1 2 9 7 4 3 2 1 8 0 5 2 3 8 7 6 2 5 8 4 8 2 7 8 2 0 3 9 8 0 2 3 0 9 9 3 3 2 9 8 5 3

B 0 6 C B

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

3 8 4 2 2 5 8 1 4 2 7 8 8 5 2 9 8 6 7 2 1 9 4 9 2 3 9 4 9 2 5 9 1 3 3 7 9 0 5 3 9 9 0 7 3

e di S h gi H

Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

TABLE 18 PRESSURE TABLE HAC481-A, HAC481-B

li o C r o o d t u O g n ir e t n E e r u t a r e p m e T ri A

r o o d n I

ri A n r u t e R

n o it c e S

. p m e T e r u s s e r P

5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

B D 5 7 B W 2 6 e di S w o L

4 7 8 0 2 5 7 3 2 2 7 7 8 3 2 8 7 4 5 2 0 8 1 7 2 2 8 8 8 2 3 8 6 0 3 5 8 4 2 3 7 8 3 4 3

e di S h gi H

- S A 1 6 A B

B D 0 8 B W 7 6 e di S w o L

8 7 4 1 2 0 8 9 2 2 2 8 5 4 2 4 8 1 6 2 6 8 8 7 2 8 8 6 9 2 0 9 4 1 3 1 9 3 9 2 5 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

4 8 0 2 2 6 8 6 3 2 8 8 3 5 2 0 9 0 7 2 2 9 8 8 2 4 9 6 0 3 6 9 5 2 3 7 9 4 4 3 9 9 4 6 3

e di S h gi H

B D 5 7 B W 2 6 e di S w o L

8 6 2 4 2 0 7 0 5 2 2 7 0 6 2 4 7 2 7 2 6 7 5 8 2 8 7 0 0 3 9 7 7 1 3 0 8 6 3 3 1 8 6 5 3

e di S h gi H

B 0 6 C B

B D 0 8 B W 7 6 e di S w o L

6 7 8 4 2 7 7 6 5 2 8 7 6 6 2 0 8 8 7 2 1 8 2 9 2 2 8 8 0 3 4 8 5 2 3 5 8 4 4 3 7 8 5 6 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

2 8 7 5 2 3 8 5 6 2 4 8 6 7 2 6 8 8 8 2 7 8 2 0 3 8 8 8 1 3 0 9 6 3 3 1 9 6 5 3 3 9 8 7 3

e di S h gi H

Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

values listed) · values listed)

Page 25 of the Bard HAC601-BD040 user manual — B 0 6 C B
Pagina 25 · klik om te vergroten
Pagina 25

TABLE 19 PRESSURE TABLE HAC601-A, HAC601-B

li o C r o o d t u O g n ir e t n E e r u t a r e p m e T ri A

r o o d n I

ri A n r u t e R

5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

n o it c e S

. p m e T e r u s s e r P

B D 5 7 B W 2 6 e di S w o L

7 6 7 2 2 9 6 3 4 2 1 7 0 6 2 3 7 6 7 2 5 7 3 9 2 6 7 0 1 3 8 7 6 2 3 9 7 3 4 3 9 7 9 5 3

e di S h gi H

- S A 1 6 A B

B D 0 8 B W 7 6 e di S w o L

2 7 2 3 2 4 7 9 4 2 6 7 6 6 2 8 7 4 8 2 0 8 1 0 3 2 8 8 1 3 4 8 6 3 3 6 8 3 5 3 8 8 0 7 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

8 7 0 4 2 0 8 8 5 2 2 8 6 7 2 4 8 3 9 2 6 8 1 1 3 8 8 9 2 3 0 9 6 4 3 2 9 4 6 3 4 9 2 8 3

e di S h gi H

B D 5 7 B W 2 6 e di S w o L

4 6 3 2 2 7 6 9 3 2 0 7 7 5 2 2 7 5 7 2 4 7 5 9 2 6 7 6 1 3 7 7 9 3 3 8 7 3 6 3 8 7 8 8 3

e di S h gi H

B 0 6 C B

B D 0 8 B W 7 6 e di S w o L

9 6 0 3 2 2 7 6 4 2 5 7 4 6 2 7 7 3 8 2 9 7 3 0 3 1 8 5 2 3 2 8 8 4 3 3 8 2 7 3 4 8 8 9 3

e di S h gi H

B D 5 8 B W 2 7 e di S w o L

6 7 7 3 2 8 7 5 5 2 0 8 3 7 2 2 8 3 9 2 5 8 4 1 3 5 8 6 3 3 7 8 0 6 3 9 8 5 8 3 0 9 1 1 4

e di S h gi H

Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

values listed)

Vraag stellen over de Bard HAC601-BD040

Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nog geen vragen over de Bard HAC601-BD040

Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.

Origineel document

Bard HAC601-BD040 handleiding-pdf

25 pagina's·389 KB·Airconditioner·PDF
Klik op een bovenstaande pagina om deze hier te openen
Pagina 1 / …
100%
Pagina's laden…