INSTALLATION INSTRUCTIONSp.1WALL MOUNTED PACKAGE AIR CONDITIONERSp.1MODELS WA381 WA423 WA484 WA491 WA602p.1GETTING OTHER INFORMATION AND PUBLICATIONSp.3FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:p.3WALL MOUNT GENERAL INFORMATIONp.4HEAT PUMP WALL MOUNT MODEL NOMENCLATUREp.4WA 42 3 – A 10 X N X X X Ap.4REVISIONSp.4KWp.4TABLE 1 ELECTRIC HEAT TABLEp.4UNIT DIMENSIONSp.5FIGURE 1p.5) H (p.58 3 A Wp.52 4 A Wp.58 4 A Wp.59 4 A Wp.50 6 A Wp.5TABLE 2 ELECTRICAL SPECIFICATIONSp.6SHIPPING DAMAGEp.7GENERALp.7FILTERSp.8DUCT WORKp.8FRESH AIR INTAKEp.8CONDENSATE DRAINp.8FIGURE 2 FRESH AIR DAMPERp.8WALL MOUNTING INFORMATIONp.9WARNINGp.9MOUNTING THE UNITp.9MOUNTING INSTRUCTIONSp.10FIGURE 3p.10FIGURE 4 ELECTRIC HEAT CLEARANCEp.11FIGURE 5 WALL MOUNTING INSTRUCTIONSp.12FIGURE 6 WALL MOUNTING INSTRUCTIONSp.12SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONSp.12FIGURE 7 COMMON WALL MOUNTING INSTALLATIONSp.13WIRING – MAIN POWERp.14WIRING – LOW VOLTAGE WIRINGp.14TABLE 3 THERMOSTAT WIRE SIZEp.14TABLE 4 WALL THERMOSTAT AND SUBBASE COMBINATIONSp.14FIGURE 8 UNIT 24V TERMINAL BOARDp.15START UPp.16IMPORTANT INSTALLER NOTEp.16PHASE MONITORp.16HIGH PRESSURE SWITCHp.16THREE PHASE SCROLL COMPRESSOR START UP INFORMATIONp.16CONDENSER FAN OPERATIONp.16SERVICE HINTSp.16SEQUENCE OF OPERATIONp.17Alarm Relay Outputp.17COMPRESSOR CONTROL MODULEp.17Adjustable Delay On Make And Break Timerp.17ADJUSTMENTSp.17Adjustable Delay on Make and Delay on Break Timerp.17High Pressure Switch and Lockout Sequencep.17Typical Settings for Dual Unit Installation:p.17PRESSURE SERVICE PORTSp.17Low Pressure Switch, Bypass, and Lockout Sequencep.17TROUBLESHOOTINGp.18FAN BLADE SETTING DIMENSIONSp.18REFRIGERANT CHARGEp.18FIGURE 9 FAN BLADE SETTINGp.18TABLE 5 FAN BLADE DIMENSIONp.18TABLE 6 REFRIGERANT CHARGEp.181 8 3 A Wp.183 2 4 A Wp.184 8 4 A Wp.181 9 4 A Wp.182 0 6 A Wp.18REMOVAL OF FAN SHROUDp.18TABLE 7 INDOOR BLOWER PERFORMANCEp.18CFM @ 230Vp.18. P . S . Ep.18Table 7A on Page 18 for models WA381 and WA491p.18TABLE 7A INDOOR BLOWER PERFORMANCEp.19CFM @ 230V / 460Vp.19TABLE 8 RECOMMENDED AIRFLOWp.19* M F Cp.19* P S Ep.19
Page 1 of the Bard WA381 user manual — INSTALLATION INSTRUCTIONS
Pagina 1 · klik om te vergroten
Pagina 1

INSTALLATION INSTRUCTIONS

WALL MOUNTED PACKAGE AIR CONDITIONERS

MODELS WA381 WA423 WA484 WA491 WA602

Bard WA381 — INSTALLATION INSTRUCTIONS diagram (page 1)
Afb. 1

Bard Manufacturing Company Bryan, Ohio 43506

Manual2100-398A Supersedes: 2100-398 File: Volume III Tab 16 Date: 05-28-02

Since 1914...Moving ahead just as planned.

© Copyright 2002

Page 2 of the Bard WA381 user manual — INSTALLATION INSTRUCTIONS
Pagina 2 · klik om te vergroten
Pagina 2
Page 2 of the Bard WA381 user manual — INSTALLATION INSTRUCTIONS
Page 3 of the Bard WA381 user manual — FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
Pagina 3 · klik om te vergroten
Pagina 3

GETTING OTHER INFORMATION AND PUBLICATIONS

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:

ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721

National Electrical Code ANSI/NFPA 70

Standard for the Installation ANSI/NFPA 90A of Air Conditioning and Ventilating Systems

ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286

Standard for Warm Air ANSI/NFPA 90B Heating and Air Conditioning Systems

ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478

Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning

Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection

NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057

Manufactured under the following

U.S. Patent numbers5,485,878; 5,301,777; 5,002,116; 4,924,934; 4,875,520; 4,825,936
Page 4 of the Bard WA381 user manual — TABLE 1 ELECTRIC HEAT TABLE
Pagina 4 · klik om te vergroten
Pagina 4

WALL MOUNT GENERAL INFORMATION

HEAT PUMP WALL MOUNT MODEL NOMENCLATURE

MODEL NUMBER CONTROL MODULES (See Chart Below)

WA 42 3 – A 10 X N X X X A

CAPACITY 38 - 3 Ton 42 - 3 1/2 Ton 48 - 4 Ton 60 - 5 Ton

COIL OPTIONS X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser

REVISIONS

COLOR OPTIONS X - Beige (Standard) 1 - White 2 - Mesa Tan 4 - Buckeye Gray 5 - Desert Brown 6 - Dark Bronze

KW

VOLTS & PHASE A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3

VENTILATION OPTIONS X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate M - Motorized Fresh Air Damper V - Commercial Ventilator -

OUTLET OPTIONS X - Front (Standard)

Motorized with Exhaust E - Economizer (Internal) - Fully

FILTER OPTIONS X - One Inch Throwaway (Standard) W - One Inch Washable P - Two Inch Pleated

Modulating with Exhaust R - Energy Recovery Ventilator -

TABLE 1 ELECTRIC HEAT TABLE

ModelsWA381-A WA423-A WA484-A WA491-A WA602-AWA381-B WA423-B WA484-B WA491-B WA602-BWA381-C WA423-C WA484-C WA491-C WA602-C 230-1208-1230-3208-3460-3 KWABTUABTUABTUABTUABTU 520.81705018.112800------------------ 6------------14.42050012.5153607.220480 833.32728028.820450------------------ 9------------21.73060018.72303010.830700 1041.63413036.225600------------------ 1562.55120054.03840036.25120031.23840017.347000 18------------43.36143037.546100------ 2083.26826072.151200------------------

Motorized with Exhaust

Page 5 of the Bard WA381 user manual — 8 3 A W
Pagina 5 · klik om te vergroten
Pagina 5
ModelWidth (W)Depth (D)Height (H)Supply ReturnEFGIJKLM NO PQRST A B CB WA38 WA42 WA48 WA49 WA6042.07522.43284.875 9.88 29.88 15.88 29.8843.8819.1031.66 30.0032.6826.9434.6932.43 3.37 42.88 23.88 10.001.4416.001.88
Bard WA381 — UNIT DIMENSIONS diagram (page 5)
Afb. 2

UNIT DIMENSIONS

FIGURE 1

y l p p u S n r u t e R

) D ( t h g i e H

) H (

) W ( h t p e D

l e d o M h t d i W

8 3 A W

2 4 A W

8 4 A W

9 4 A W

0 6 A W

Page 6 of the Bard WA381 user manual — TABLE 2 ELECTRICAL SPECIFICATIONS
Pagina 6 · klik om te vergroten
Pagina 6

TABLE 2 ELECTRICAL SPECIFICATIONS

ModelSINGLECIRCUITDUALCIRCUIT Rated Volts& PhaseNo. Field Power Circuits3 Minimum Circuit Ampacity1 Maximum External Fuseor Circuit Breaker2 Field Power Wire Size2 Ground Wire Size3 Minimum Circuit Ampacity1 Maximum ExternalFuse or Circuit Breaker2 FieldPower WireSize2 Ground WireSize CKTACKTBCKTACKTBCKTACKTBCKTACKTB WA381-A00,A0Z A05 A08 A10230/208-1125 32 47 5835 35 50 608 8 8 610N/AN/AN/AN/AN/AN/AN/AN/A WA381-B00,B0Z B06 B09230/208-31 1 120 24 3330 30 3510 10 810 10 10N/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/A WA381-C00,C0Z C06 C09460-31 1 111 13 1715 15 2014 14 1214 14 12N/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/A WA423-A00,A0Z A05 A10 A15 A20230/208-11or2 1or235 35 59 85 11050 50 60 90 1108 8 6 4 210 10 10 8 6N/A N/A N/A 56 56N/A N/A N/A 26 52N/A N/A N/A 60 60N/A N/A N/A 30 60N/A N/A N/A 6 6N/A N/A N/A 10 6N/A N/A N/A 10 10N/A N/A N/A 10 10 WA423-B00,B0Z B09 B15 B18230/208-3124 34 52 6035 35 50 608 8 6 610N/AN/AN/AN/AN/AN/AN/AN/A WA423-C00,C0Z C09 C15460-31 1 113 17 2615 20 3014 12 1014 12 10N/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/A WA484-A00,A0Z A05 A10 A15 A20230/208-11or2 1or236 36 59 85 11050 50 60 90 1108 8 6 4 210 10 10 8 6N/A N/A N/A 59 59N/A N/A N/A 26 52N/A N/A N/A 60 60N/A N/A N/A 30 60N/A N/A N/A 6 6N/A N/A N/A 10 6N/A N/A N/A 10 10N/A N/A N/A 10 10 WA484-B00,B0Z B09 B15 B18230/208-3125 34 52 6035 35 60 608 8 6 610N/AN/AN/AN/AN/AN/AN/AN/A WA484-C00,C0Z C09 C15460-31 1 113 17 2615 20 3014 12 1014 12 10N/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/A WA491-A00,A0Z A05 A08 A10230/208-1133 33 47 5850 50 50 608 8 8 610N/AN/AN/AN/AN/AN/AN/AN/A WA491-B00,B0Z B06 B09230/208-31 1 127 27 3340 40 408 8 810 10 10N/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/A WA491-C00,C0Z C06 C10460-31 1 113 13 1715 15 2014 14 1214 14 12N/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/A TABLECONTINUEDONPAGE5

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All wiring must conform to NEC and all local codes. These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the

National Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.

Page 7 of the Bard WA381 user manual — GENERAL
Pagina 7 · klik om te vergroten
Pagina 7
TABLECONTINUEDFROMPAGE4 ModelSINGLECIRCUITDUALCIRCUIT Rated Volts& PhaseNo. Field Power Circuits3 Minimum Circuit Ampacity1 Maximum External Fuseor Circuit Breaker2 Field Power Wire Size2 Ground Wire Size3 Minimum Circuit Ampacity1 Maximum ExternalFuse or Circuit Breaker2 FieldPower WireSize2 Ground WireSize CKTACKTBCKTACKTBCKTACKTBCKTACKTB WA602-A00,A0Z A05 A10 A15 A20230/208-11or2 1or244 44 55 85 11060 60 60 90 1108 8 6 4 210 10 10 8 6N/A N/A N/A 59 59N/A N/A N/A 26 52N/A N/A N/A 60 60N/A N/A N/A 30 60N/A N/A N/A 6 6N/A N/A N/A 10 6N/A N/A N/A 10 10N/A N/A N/A 10 10 WA602-B00,B0Z B09 B15 B18230/208-3132 34 52 6045 45 60 608 8 6 610N/AN/AN/AN/AN/AN/AN/AN/A WA602-C00,C0Z C09 C15460-31 1 116 17 2620 20 3012 12 1012 12 10N/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/AN/A N/A N/A

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All wiring must conform to NEC and all local codes. These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the

National Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.

SHIPPING DAMAGE

These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 1 for information on codes and standards.

GENERAL

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.

The refrigerant system is completely assembled and charged. All internal wiring is complete.

Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.

The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.

These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.

Page 8 of the Bard WA381 user manual — FIGURE 2 FRESH AIR DAMPER
Pagina 8 · klik om te vergroten
Pagina 8

FILTERS

DUCT WORK

A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A one inch washable filter and two inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the two inch filter by loosening two (2) screws on each bracket assembly and sliding the brackets apart to the required width and retightening the four (4) screws.

All duct work, supply and return, must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.

Refer to Table 10 for maximum static pressure available for duct design.

Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in the service panel.

If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.

A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.

All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.

Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.

Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.

The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.

Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.

installation codes may limit this cabinet to installation only in a single story structure.

FIGURE 2 FRESH AIR DAMPER

BLADE IS LOCKED CLOSED FOR SHIPPING.

Page 9 of the Bard WA381 user manual — MOUNTING THE UNIT
Pagina 9 · klik om te vergroten
Pagina 9

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

WARNING

1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death.

3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation, but is not required.
6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag bolts.

2. The unit itself is suitable for 0 inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. If a combustible wall use a minimum of 30-1/2” x 10-1/2” dimensions for sizing. However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material. The supply air opening would then be 32” x 12”. See Figures 3 and 4 for details.

7. Secure rain flashing to wall and caulk across entire length of top. See Figure 3.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side by side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.
Page 10 of the Bard WA381 user manual — MOUNTING INSTRUCTIONS
Pagina 10 · klik om te vergroten
Pagina 10
Bard WA381 — MOUNTING INSTRUCTIONS diagram (page 10)
Afb. 3

MOUNTING INSTRUCTIONS

FIGURE 3

Page 11 of the Bard WA381 user manual — FIGURE 4 ELECTRIC HEAT CLEARANCE
Pagina 11 · klik om te vergroten
Pagina 11

FIGURE 4 ELECTRIC HEAT CLEARANCE

Bard WA381 — FIGURE 4 ELECTRIC HEAT CLEARANCE diagram (page 11)
Afb. 4

SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES.

Bard WA381 — FIGURE 4 ELECTRIC HEAT CLEARANCE diagram (page 11)
Afb. 5

A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.

It is important to insure that the 1/4 inch minimum spacing is maintained at all points.

Failure to do this could result in overheating the combustible material and may result in a fire causing damage, injury or death.

Page 12 of the Bard WA381 user manual — FIGURE 6 WALL MOUNTING INSTRUCTIONS
Pagina 12 · klik om te vergroten
Pagina 12

FIGURE 5 WALL MOUNTING INSTRUCTIONS

Bard WA381 — FIGURE 5 WALL MOUNTING INSTRUCTIONS diagram (page 12)
Afb. 6

FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION

BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT.

FIGURE 6 WALL MOUNTING INSTRUCTIONS

SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONS

Bard WA381 — FIGURE 6 WALL MOUNTING INSTRUCTIONS diagram (page 12)
Afb. 7

ATTACH TO BOTTOM PLATE OF WALL FRAMING MATERIAL 2 X 4’S, 2 X 6’S AND/OR STRUCTURAL STEEL

THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.

Page 13 of the Bard WA381 user manual — FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS
Pagina 13 · klik om te vergroten
Pagina 13

FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS

Bard WA381 — FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS diagram (page 13)
Afb. 8
Bard WA381 — FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS diagram (page 13)
Afb. 9

FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT

Bard WA381 — FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS diagram (page 13)
Afb. 10
Page 14 of the Bard WA381 user manual — TABLE 4 WALL THERMOSTAT AND SUBBASE COMBINATIONS
Pagina 14 · klik om te vergroten
Pagina 14

WIRING – MAIN POWER

WIRING – LOW VOLTAGE WIRING

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring muse conform to NEC and all local codes.

230 / 208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP RANGE 240 253 – 216 208 220 – 187

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8:

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

TABLE 3 THERMOSTAT WIRE SIZE

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

m u m i x a M

r e m r o f s n a r T

e c n a t s i D

A V A L F e g u a G e ri W

t e e F n I

e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g a u g 4 1 e g a u g 2 1

5 4 0 6 0 0 1 0 6 1 0 5 2

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut a padlock may be placed through the hole in the tab preventing entry.

5 5 3 . 2

See “Start Up” section for important information on three phase scroll compressor start ups.

TABLE 4 WALL THERMOSTAT AND SUBBASE COMBINATIONS

t a t s o m r e h T e s a b b u S s e r u t a e F e t a n i m o d e r P

2 0 0 - 3 0 4 8 1 1 1 3 F 7 8 T

3 0 0 - 4 0 4 8 0 2 2 1 A 9 3 5 Q

lo o c e g a ts 1 ,t a e h e g a ts 1 lo o c -ff o -t a e h : m e ts y S n o - o tu a :n a F

1 4 0 - 3 0 4 8 C 4 3 0 8 T

--- lo o c e g a ts 1 ,t a e h e g a ts 1 lo o c -ff o -t a e h : m e ts y S n o - o tu a :n a F

9 1 0 - 3 0 4 8 0 6 7 1 C 4 7 8 T

2 1 0 - 4 0 4 8 1 0 0 1 A 4 7 6 Q

t a e h e g a ts 2 ,lo o c e g a ts 1 lo o c - o tu a -t a e h : m e ts y S n o - o tu a :n a F

1 2 0 - 3 0 4 8 4 3 9 1 D 4 7 8 T

2 1 0 - 4 0 4 8 1 0 0 1 A 4 7 6 Q

t a e h e g a ts 2 ,lo o c e g a ts 2 lo o c - o tu a -t a e h : m e ts y S n o - o tu a :n a F

9 4 0 - 3 0 4 8 0 8 3 - 3 9 F 1 --- t a e h e g a ts 2 ,lo o c e g a ts 2 cin o rtc el E g n i m m a r g o r p y a d 7

3 4 0 - 3 0 4 8 0 0 2 - M C --- lo o c e g a ts 1 ,t a e h e g a ts 1 lo o c -ff o -t a e h : m e ts y S n o - o tu a :n a F

8 4 0 - 3 0 4 8 3 1 3 1 0 0 4 8 T --- lo o c e g a ts 1 ,t a e h e g a ts 1 cin o rtc el E

Page 15 of the Bard WA381 user manual — FIGURE 8 UNIT 24V TERMINAL BOARD
Pagina 15 · klik om te vergroten
Pagina 15

FIGURE 8 UNIT 24V TERMINAL BOARD

Bard WA381 — FIGURE 8 UNIT 24V TERMINAL BOARD diagram (page 15)
Afb. 11
Page 16 of the Bard WA381 user manual — SERVICE HINTS
Pagina 16 · klik om te vergroten
Pagina 16

START UP

IMPORTANT INSTALLER NOTE

PHASE MONITOR

For improved start up performance wash the indoor coil with a dish washing detergent.

All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

HIGH PRESSURE SWITCH

The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.

The WA381, WA484, WA491 and WA602 models are supplied with a remote reset high pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.

If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

THREE PHASE SCROLL COMPRESSOR START UP INFORMATION

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

CONDENSER FAN OPERATION

The condenser fan motor on 230/208 volt, one and three phase, 60 HZ units is a two speed motor that comes factory wired on high speed for peak performance. If ambient conditions permit, it can be reconnected to low speed (red wire) for lower sound level. See wiring diagram.

However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.

50 HZ models must have fan wired on low speed. These models are factory wired on low speed.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs.

Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.

2. Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the remote reset high pressure switch. Turn thermostat off then on to reset the high pressure switch.
3. Check all power fuses or circuit breakers to be sure they are the correct rating.

All three phase ZR compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction.

4. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

The direction of rotation of the compressor may be changed by reversing any two line connections to the unit.

Page 17 of the Bard WA381 user manual — Low Pressure Switch, Bypass, and Lockout Sequence
Pagina 17 · klik om te vergroten
Pagina 17

SEQUENCE OF OPERATION

pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase of constant air circulation. On all 230 volt units there is a one minute off delay on the blower motor. 460 volt models do not have an off delay. On a call for heating, circuit R-W1 make at the thermostat pulling in heat contact for the strip heat and blower operation. On a call for second stage heat, R-W2 makes bringing on second heat contactor, if so equipped.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

COMPRESSOR CONTROL MODULE

inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

The compressor control module is standard on the WA391, WA484, WA491and WA602 models covered by this manual and is optional on the WA423 model. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

ADJUSTMENTS

On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10% of the delay on break setting. When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired.

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute (30 seconds) DOB = 123 second DOM 1.0 minute (60 seconds) DOB = 126 second DOM 2.0 minute (120 seconds) DOB = 132 second DOM 3.0 minute (180 seconds) DOB = 138 second DOM 4.0 minute (240 seconds) DOB = 144 second DOM 5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1DOB set at 2 minutes, and DOM is 132 seconds
Unit 2DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

Low Pressure Switch, Bypass, and Lockout Sequence

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low

Page 18 of the Bard WA381 user manual — Table 7A on Page 18 for models WA381 and WA491
Pagina 18 · klik om te vergroten
Pagina 18

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

4. Unwire condenser fan motor.

Shown in Figure 10 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.

5. Slide complete motor, fan blade, and shroud assembly out the left side of the unit.
6. Service motor/fan as needed.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

7. Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 6.

FIGURE 9 FAN BLADE SETTING

Bard WA381 — FIGURE 9 FAN BLADE SETTING diagram (page 18)
Afb. 12

TABLE 5 FAN BLADE DIMENSION

TABLE 6 REFRIGERANT CHARGE

n o i s n e m i D

l e d o M

A

d e t a R

D O 5 9 e r u t a r e p m e T

D O 2 8 e r u t a r e p m e T

l e d o M

w o lfri A

1 8 3 A W

3 2 4 A W

1 8 3 A W 0 0 1 1 8 4 - 0 5 6 4 - 8 4

4 8 4 A W

5 7 . 1

1 9 4 A W

3 2 4 A W 0 0 4 1 4 5 - 2 5 6 6 - 4 6

2 0 6 A W

4 8 4 A W 0 5 5 1 6 5 - 4 5 7 6 - 5 6

1 9 4 A W 0 5 2 1 6 4 - 8 4 5 4 - 7 4

REMOVAL OF FAN SHROUD

2 0 6 A W 0 0 7 1 5 5 - 3 5 2 6 - 0 6

1. Disconnect all power to the unit.

The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.

2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.

TABLE 7 INDOOR BLOWER PERFORMANCE

CFM @ 230V

4 8 4 A W , 3 2 4 A W 2 0 6 A W

V 0 3 2 w o L V 0 3 2 h g i H V 0 3 2 w o L V 0 3 2 h g i H

. P . S . E

li o C y r D t e W

li o C li o C y r D t e W

li o C li o C y r D t e W

li o C li o C y r D t e W

H n I 20

0 5 6 1 0 5 5 1 0 5 4 1 0 5 3 1 0 0 3 1 - - -

0 0 6 1 0 0 5 1 0 0 4 1 0 0 3 1 5 7 1 1 - - -

5 8 8 1 0 7 7 1 5 3 6 1 0 0 5 1 0 7 3 1 0 5 2 1

0 0 8 1 5 6 6 1 0 4 5 1 0 0 4 1 5 8 2 1 0 5 1 1

0 0 6 1 5 2 5 1 - - -

0 5 4 1 5 7 3 1 - - -

0 0 2 2 0 0 1 2 0 0 0 2 5 7 8 1 5 7 7 1 0 5 6 1

0 0 0 2 0 0 9 1 0 0 8 1 0 0 7 1 0 0 6 1 5 7 4 1

Table 7A on Page 18 for models WA381 and WA491

li o C

Page 19 of the Bard WA381 user manual — 5 1 C -
Pagina 19 · klik om te vergroten
Pagina 19

TABLE 7A INDOOR BLOWER PERFORMANCE

CFM @ 230V / 460V

1 8 3 A W 1 9 4 A W

d e e p S h g i H d e e p S m u i d e M d e e p S w o L d e e p S h g i H d e e p S m u i d e M

. P . S . E

n I H2O

5 2 6 1 5 7 4 1 0 5 3 1 0 5 1 1

5 7 4 1 0 5 3 1 0 5 1 1 5 2 8

5 2 4 1 5 2 3 1 0 0 2 1 - - -

5 2 3 1 0 0 2 1 5 2 1 5 7 8

5 2 1 1 0 0 1 1 0 0 0 1 - - -

0 0 1 1 0 0 0 1 0 5 8 - - -

0 0 7 1 0 5 5 1 0 0 4 1 0 5 2 1

0 5 5 1 0 0 4 1 0 5 2 1 0 0 1 1

5 7 4 1 5 7 3 1 0 5 2 1 0 0 1 1

5 7 3 1 0 5 2 1 0 0 1 1 - - -

TABLE 8 RECOMMENDED AIRFLOW

d e t a R

d e t a R

d e d n e m m o c e R

d e e p S y r o t c a F

l e d o M

* M F C

* P S E

e g n a R w o lfri A

n o it c e n n o C

1 8 3 A W 0 0 1 1 5 1 . 0 5 8 - 0 5 2 1 m u id e M

3 2 4 A W 0 0 4 1 0 3 . 0 5 1 1 - 0 0 6 1 h g i H

4 8 4 A W 0 5 5 1 0 2 . 5 8 2 1 - 0 5 7 1 h g i H

1 9 4 A W 0 5 2 1 0 2 . 0 0 1 1 - 5 7 4 1 h g i H

2 0 6 A W 0 0 7 1 0 3 . 5 7 3 1 - 0 5 9 1 h g i H

TABLE 9 MAXIMUM ESP OF OPERATION

TABLE 9A MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

ELECTRIC HEAT ONLY

l e d o M 3 2 4 A W 4 8 4 A W 2 0 6 A W

l e d o M 1 8 3 A W 1 9 4 A W

h g i H

h g i H

h g i H

h g i H

h g i H

W K

d e e p S

d e e p S

d e e p S

d e e p S

d e e p S

d e e p S

W K

d e e p S

d e e p S

d e e p S

d e e p S

d e e p S

5 0 A -

5 0 A -

8 0 A -

0 1 A -

5 1 A -

0 1 A -

0 2 A -

6 0 B -

0 0 B -

9 0 B -

9 0 B -

6 0 C -

5 1 B -

9 0 C -

8 1 B -

9 0 C -

Values shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter. Derate ESP by .15 for 2 inch pleated filters.

5 1 C -

Values shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter. Derate ESP by .15 for 2 inch pleated filters.

Show 26 more labels / short text on this page
y r D · t e W · y r D · t e W · y r D · t e W · y r D · t e W · y r D · t e W · li o C · li o C · li o C · li o C · li o C · li o C · li o C · li o C · li o C · li o C · w o L · w o L · w o L · d e M · w o L · d e M
Page 20 of the Bard WA381 user manual — 2 0 6 A W
Pagina 20 · klik om te vergroten
Pagina 20

TABLE 10 PRESSURE TABLE

COOLING

Air Temperature Entering Outdoor Coil °F

ri A n r u t e R

l e d o M

e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1

B D . g e d 5 7 B W . g e d 2 6 e d i S w o L

4 7 5 7 1 4 7 7 8 1 5 7 2 0 2 6 7 6 1 2 8 7 2 3 2 9 7 9 4 2 9 7 5 6 2 0 8 4 8 2 1 8 2 0 3

e d i S h g i H

B D . g e d 0 8 B W . g e d 7 6 e d i S w o L

9 7 9 7 1 9 7 2 9 1 0 8 7 0 2 1 8 2 2 2 3 8 8 3 2 4 8 5 5 2 5 8 2 7 2 6 8 1 9 2 7 8 0 1 3

1 8 3 A W

e d i S h g i H

B D . g e d 5 8 B W . g e d 2 7 e d i S w o L

2 8 5 8 1 2 8 9 9 1 3 8 4 1 2 4 8 0 3 2 6 8 6 4 2 7 8 4 6 2 8 8 2 5 2 9 8 1 0 3 0 9 1 2 3

e d i S h g i H

B D . g e d 5 7 B W . g e d 2 6 e d i S w o L

0 7 7 0 2 2 7 0 2 2 3 7 5 3 2 5 7 1 5 2 6 7 6 6 2 7 7 3 8 2 8 7 0 0 3 9 7 8 1 3 9 7 7 3 3

e d i S h g i H

3 2 4 A W

B D . g e d 0 8 B W . g e d 7 6 e d i S w o L

5 7 2 1 2 7 7 6 2 2 8 7 1 4 2 0 8 7 5 2 1 8 3 7 2 2 8 0 9 2 3 8 8 0 3 4 8 6 2 3 5 8 6 4 3

e d i S h g i H

B D . g e d 5 8 B W . g e d 2 7 e d i S w o L

8 7 9 1 2 0 8 4 3 2 1 8 9 4 2 3 8 6 6 2 4 8 3 8 2 5 8 0 0 3 6 8 9 1 3 7 8 7 3 3 8 8 8 5 3

e d i S h g i H

B D . g e d 5 7 B W . g e d 2 6 e d i S w o L

3 7 4 0 2 4 7 7 1 2 6 7 2 3 2 8 7 8 4 2 9 7 5 6 2 0 8 4 8 2 2 8 4 0 3 3 8 5 2 3 4 8 8 4 3

e d i S h g i H

B D . g e d 0 8 B W . g e d 7 6 e d i S w o L

8 7 0 1 2 9 7 3 2 2 1 8 8 3 2 2 8 4 5 2 4 8 2 7 2 6 8 1 9 2 7 8 2 1 3 9 8 4 3 3 0 9 7 5 3

4 8 4 A W

e d i S h g i H

B D . g e d 5 8 B W . g e d 2 7 e d i S w o L

4 8 7 1 2 5 8 1 3 2 7 8 7 4 2 8 8 4 6 2 0 9 2 8 2 2 9 2 0 3 3 9 3 2 3 5 9 5 4 3 7 9 9 6 3

e d i S h g i H

B D . g e d 5 7 B W . g e d 2 6 e d i S w o L

0 7 9 9 1 1 7 3 1 2 1 7 7 2 2 2 7 4 4 2 3 7 0 6 2 5 7 9 7 2 6 7 8 9 2 7 7 0 2 3 9 7 1 4 3

e d i S h g i H

B D . g e d 0 8 B W . g e d 7 6 e d i S w o L

5 7 4 0 2 6 7 8 1 2 6 7 3 3 2 7 7 0 5 2 8 7 7 6 2 0 8 6 8 2 1 8 6 0 3 2 8 8 2 3 4 8 0 5 3

1 9 4 A W

e d i S h g i H

B D . g e d 5 8 B W . g e d 2 7 e d i S w o L

8 7 1 1 2 9 7 6 2 2 9 7 1 4 2 0 8 9 5 2 1 8 6 7 2 3 8 6 9 2 4 8 7 1 3 5 8 9 3 3 7 8 2 6 3

e d i S h g i H

B D . g e d 5 7 B W . g e d 2 6 e d i S w o L

1 7 3 3 2 2 7 7 4 2 4 7 2 6 2 5 7 8 7 2 6 7 5 9 2 7 7 3 1 3 8 7 1 3 3 8 7 1 5 3 9 7 1 7 3

e d i S h g i H

B D . g e d 0 8 B W . g e d 7 6 e d i S w o L

6 7 7 3 2 8 7 3 5 2 9 7 9 6 2 0 8 5 8 2 1 8 3 0 3 2 8 1 2 3 3 8 0 4 3 4 8 0 9 3 5 8 1 8 3

2 0 6 A W

e d i S h g i H

B D . g e d 5 8 B W . g e d 2 7 e d i S w o L

4 8 5 4 2 5 8 1 6 2 5 8 8 7 2 6 8 6 9 2 7 8 4 1 3 8 8 3 3 3 9 8 3 5 3 0 9 3 7 3 1 9 4 9 3

e d i S h g i H

Low side pressure ± 2 PSIG High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.

Page 21 of the Bard WA381 user manual — B 6 0 - B C M W
Pagina 21 · klik om te vergroten
Pagina 21

TABLE 11 OPTIONAL ACCESSORIES

WA381-A

WA381-B

WA381-C

WA423-A

WA423-B

WA423-C

WA484-A

WA484-B

WA484-C

WA491-A

WA491-B

WA491-C

WA602-A

WA602-B

WA602-C

tr a P

r e b m u N n o it p ir c s e D

5 0 A - 5 0 A W H E

s e g a k c a P r e t a e H

X

X X X X

X X X X

8 0 A - 5 0 A W H E

s e g a k c a P r e t a e H

0 1 A - 5 0 A W H E

s e g a k c a P r e t a e H

5 1 A - 5 0 A W H E

s e g a k c a P r e t a e H

5 0 A - 8 3 A W H E

s e g a k c a P r e t a e H

8 0 A - 8 3 A W H E

s e g a k c a P r e t a e H

0 1 A - 8 3 A W H E

s e g a k c a P r e t a e H

5 0 A - 9 4 A W H E

s e g a k c a P r e t a e H

9 0 B - 5 0 A W H E

s e g a k c a P r e t a e H

5 1 B - 5 0 A W H E

s e g a k c a P r e t a e H

8 1 B - 5 0 A W H E

s e g a k c a P r e t a e H

6 0 B - 8 3 A W H E

s e g a k c a P r e t a e H

9 0 B - 8 3 A W H E

s e g a k c a P r e t a e H

6 0 B - 9 4 A W H E

s e g a k c a P r e t a e H

A 9 0 C - 5 0 A W H E

s e g a k c a P r e t a e H

5 1 C - 5 0 A W H E

s e g a k c a P r e t a e H

6 0 C - 8 3 A W H E s e g a k c a P r e t a e H X X

5 - P O B

e t al P ff O k n al B

5 - D A F B

r e p m a D ri A h s e r F cirt e m o r a B

5 - D A F M

r e p m a D ri A h s e r F d e zir o t o M

5 - V R C

ts u a h x E h ti w r o t alitn e V la ic r e m m o C

5 - M F I E

ts u a h x E h ti w r e zi m o n o c E

B 5 A - V R E W

r o t alitn e V y r e v o c e R y g r e n E

B 5 C - V R E W

r o t alitn e V y r e v o c e R y g r e n E

6 - A M C

) C A L ( lo rtn o C tn e ib m A w o L

X

X X X X X X X X

0 1 - A M C

R D T + C P H + C P L

3 1 - A M C

C A L + R D T + C P H + C P L

5 1 - C M C

ti K tr a t S

6 1 - A M C

lo rtn o C e u s s e r P w o L

8 1 - A M C

C A L + C P L

B 5 0 - B C M W

ti K r e k a e r B tiu c ri C

C 1 0 - D C M W

ti K tc e n n o c si D llu P

A 8 0 - B C M W

r e k a e r B tiu c ri C

A 9 0 - B C M W

r e k a e r B tiu c ri C

B 7 0 - B C M W

r e k a e r B tiu c ri C

A 5 0 - B C M W

r e k a e r B tiu c ri C

B 4 0 - B C M W

r e k a e r B tiu c ri C

B 6 0 - B C M W

r e k a e r B tiu c ri C

Vraag stellen over de Bard WA381

Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nog geen vragen over de Bard WA381

Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.

Origineel document

Bard WA381 handleiding-pdf

21 pagina's·328 KB·Airconditioner·PDF
Klik op een bovenstaande pagina om deze hier te openen
Pagina 1 / …
100%
Pagina's laden…