D400-13-00 1 I56-555-09R DH400ACDCP Air Duct Smoke Detector INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
[3] Contents Of The Duct Detector Kit 1. Complete housing base and cov er assembly 2. T wo #1 0 sheet metal mounting scre ws 3. T wo sampling tube filter s 4. One test magnet 5. Drilling template 6. T wo 5/16 O-rings 7. T wo rubber tube bushing seals 8.
feet per minute . Be sur e to check engineering specifications to ensure that the air velocity in the duct falls within these parameter s . If necessary , use a velocity meter to check the air velocity in the duct. [5.2] Drill The Mounting Holes R emo ve the paper backing from the mounting template supplied.
[5.4.1] Installation For Ducts Less Than 8 Feet Wide 1. If the tube is longer than the width of the air duct, drill a 3/4-inch hole in the duct directly opposite the hole already cut for the inlet tube. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4.
Install the inlet tube as follow s: 1. Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube . 2. Slide the inlet tube with the flange into the centermost housing bushing. Position the tube so that the arr ow s point into the air flow .
24V 120 VAC 220/240 VAC 1 2 1 2 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
24V 120 VAC 220/240 VAC 1 2 12 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
[5.6] Install The Filters T o install the sampling tube filters , simply push the filter adapter into the exhaust tube, and push the filter onto the adapter tube on the left, as shown in Figure 9. Install the other filter ov er the end of the inlet sampling tube .
[6.1] Smoke Entr y T ests [6.1.1] Air Flow T o verify sufficient sampling of ducted air , use a manometer to measure the differ ential pressure created from air flow across the sampling tubes . The pr essure should measure no less than 0.0 1 inches of water and no greater than 1.
the R T S45 1/R T S45 1KEY manual. The DH400A CDCP duct detector can be reset by the R T S45 1/R T S45 1KEY . If a sys- tem control panel is used, the panel itself may also requir e resetting. T o install the R T S45 1/R T S45 1KEY , connect the device as shown in Figur e 8; wir e runs must be limited to 25 ohms or less per interconnecting wire .
3. V acuum the photo chamber . Use clean compr essed air to blow it clean. 4. R eplace the screen by aligning the arro w on top with the field test port on the detector . Press the screen into place . It should fit tightly on the chamber . 5. R eplace the detector co v er and rotate it clockwise to lock it in place .
[8] Model DH400ACDCP Air Duct Smoke Detector Specifications Description HV A C air duct mounted ionization or photoelectronic smoke detector for separately power ed sy stems or stand alone sys- tems. A uxiliary alarm relay contacts pr ovide fan contactor shutdo wn to pr e vent HV A C circulation of smoke .
Electrical Specifications P o wer supply v oltage: 20-29 VDC 24 V A C 5 0-60-Hz 120 V A C 50-60 Hz 220/240 V A C 50-60 Hz Input capacitance: 27 0 µ F max. 27 0 µ F max. N/A N/A R eset v oltage: 3.0 VDC min. 2.0 V A C min. 1 0 V A C min. 20 V A C min.
NOTES D400-13-00 14 I56-555-09R.
NOTES D400-13-00 15 I56-555-09R.
D400-13-00 16 I56-555-09R © Sy stem Sensor 1997 DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model: ______________________ Number: ___________________.
Een belangrijk punt na aankoop van elk apparaat System Sensor DH400ACDCP (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen System Sensor DH400ACDCP heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens System Sensor DH400ACDCP vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding System Sensor DH400ACDCP leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over System Sensor DH400ACDCP krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van System Sensor DH400ACDCP bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de System Sensor DH400ACDCP kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met System Sensor DH400ACDCP . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.