Gebruiksaanwijzing /service van het product 7600 van de fabrikant Beckett
Ga naar pagina of 36
P ARTS & AC CESSORIES Description / A pplica tions The Beckett AquaSmart™ is an advanced boiler control designed for use on residential and light commercial boiler systems. All models include the option of enabling Beckett HeatManager™ dynamic temperature reset that, when selected, provides up to 20% fuel consumption savings.
2 HeatManager™ dynamic temperature reset for additional energy savings — DOE 2012 Compliant — Meets NR CAN proposed 2012 requir ements Advanced microprocessor-based design Backlit LCD digital di.
3 AquaSmart Boiler Control Manual Figure 1 - Getting to know the AquaSmart 7600 Series Control T emperature Ranges and Differentials High Limit Setting Range: 100 to 240°F (37 to 1 15°C) High Limit .
4 Figure 2 - Basic Dimensions (inches) Mounting OEM Installation: When replacing an OEM-installed AquaSmart, consult the appliance manufacturer ’s wiring diagrams and instructions for additional information. Retro fi t Installation: The AquaSmart can be used to replace most standard boiler temperature controls.
5 AquaSmart Boiler Control Manual AquaSmart Models and Cross-Reference Guide T able 1a - Direct Replacements Honeywell Beckett Replacement Notes L7148F (All) L8148E (All) 7600B Must con fi rm that 7600 V A rating is adequate to meet V A requirements of system.
6 Honeywell Beckett Replacement Notes L4081A/B L6081A/C 7600A or 7600B (Based on System V oltage Requirements) Remove switching relay , if used, from the system when replacing the L4081 or L6081. Make sure 7600 outputs do not exceed 7.4A @ 120 V AC. 7600 outputs are not rated for 240 V AC.
7 AquaSmart Boiler Control Manual Compare the attached wires to available wiring diagrams on the control cover and to the devices to which they can be traced. If wiring diagrams have been lost they are available later in this manual. Label each wire accordingly , to ensure accurate reconnection.
8 Installing the 2-in-1 Sensor For proper operation, there must be a secure electrical bond between the green sensor wire from the sensor and the boiler metal vessel in direct contact with the boiler water . Failure to secure an electrical bond will result in the AquaSmart locking out and displaying, “LOCKOUT - LOW W A TER”.
9 AquaSmart Boiler Control Manual T est the Low W ater Cut-off (L WCO) Safety Function W ARNING! Avoid touching or shorting the live terminals during this test. T urn electric power ON to energize AquaSmart control. Perform the following tests to verify the L WCO function.
10 Immersion Well or 2-in-1 Sensor Mount the control by aligning the 7/8” diameter hole (found on back) around the mating feature of the immersion well or 2-in-1 sensor and press into place. Position the control upright and tighten down the #10 screw located on the left side of the control.
11 AquaSmart Boiler Control Manual Explosion Hazard. Can Cause Severe Injury , Death or Property Damage. Use this product only in systems with a pressure relief valve. Wiring the AquaSmart Control Consult the appliance wiring diagrams to check the manufacturer ’s speci fi cations.
12 SK10030 P1 COLD WATER INLET EXP ANSION TA N K HEA TING ZONE AIR SEP ARA TOR AIR VENT Figure 12 - 7600A/B single-zone connections with or without a tankless coil W ater Flow: Control Wiring: 1. Set “DHWP OFF” (default, see programming section for instructions) 2.
13 AquaSmart Boiler Control Manual Figure 13 - 7600A/B multi-zone connections with or without a tankless coil W ater Flow: Control Wiring (Option 1): Circulator-On and -Off Delays on Zone 1 ONL Y 1. Set “DHWP OFF” (default, see programming section for instructions) 2.
14 TR TW SK10032 6 5 4 3 2/N 1/H T T ZONE RELA Y ZONE 1 LOW VOL T AGE THERMOST A T LOW VOL T AGE THERMOST A T ZONE 2 ZONE RELA Y T T 1/H 2/N 3 4 NEUTRAL HOT 120 V AC BLACK WHITE P1 CIRCULA TOR 120 V A.
15 AquaSmart Boiler Control Manual Figure 14 - 7600A/B alternate multi-zone connections with or without a tankless coil W ater Flow: Control Wiring (Option 1): 7600B only 1. Set “DHWP OFF” (default, see programming section for instructions) 2. Set “C1 on TT” (default, see programming section for instructions) 3.
16 Figure 14 (continued) - 7600A/B alternate multi-zone connections with or without a tankless coil Control Wiring (Option 2): 7600A only 1. Set “DHWP OFF” (default, see programming section for instructions) 2. Set “C1 on TT” (default, see programming section for instructions) 3.
17 AquaSmart Boiler Control Manual SK10034 COLD WATER INLET EXP ANSION TA N K AIR SEP ARA TOR AIR VENT HEA TING ZONE 1 INDIRECT DHW DHW ZONE P2 P1 Figure 15 - 7600A/B single-zone connections with Indirect Domestic Hot Water (DHW) W ater Flow: Control Wiring: 1.
18 SK10035 COLD WATER INLET EXP ANSION TA N K AIR SEP ARA TOR AIR VENT HEA TING ZONE 1 INDIRECT DHW DHW ZONE P1 P2 P3 HEA TING ZONE 2 HEA TING ZONE 3* P4* Figure 16 - 7600A/B multi-zone connections wi.
19 AquaSmart Boiler Control Manual Figure 16 (continued)- 7600A/B multi-zone connections with Indirect Domestic Hot Water (DHW) Control Wiring (Option 1): Circulator-On and -Off Delays on DHW Zone Only 1. Set “DHWP on TT” (see programming section for instructions) 2.
20 L2 L1 C1 C2 ZC ZR B1 B2 TR TW SK10024 6 5 4 3 2/N 1/H T T ZONE RELA Y LOW VOL T AGE THERMOST A T ZONE 1 ZONE RELA Y T T 1/H 2/N 3 4 5 6 NEUTRAL HOT 120 V AC BLACK WHITE P1 CIRCULA TOR 120 V AC P3 C.
21 AquaSmart Boiler Control Manual Figure 16 (continued) - 7600A/B multi-zone connections with Indirect Domestic Hot Water (DHW) ◄ CONTINUED FROM PREVIOUS P AGE Control Wiring (Option 3): Utilizing a Zone Panel 1. Set “DHWP on TT” (see programming section for instructions).
22 Figure 17 - 7600A/B alternate multi-zone connections with Indirect Domestic Hot Water (DHW) W ater Flow: SK10037 COLD WATER INLET EXP ANSION TA N K HEA TING ZONE 1 AIR SEP ARA TOR AIR VENT HEA TING.
23 AquaSmart Boiler Control Manual Figure 17 (continued) - 7600A/B alternate multi-zone connections with Indirect Domestic Hot Water (DHW) Control Wiring (Option 1): 7600B only 1. Set “DHWP on ZR” (see programming section for instructions) 2. Set “C1 on BOTH” (see programming section for instructions) 3.
24 ◄ CONTINUED FROM PREVIOUS P AGE Control Wiring (Option 2): 7600A only 1. Set “DHWP on ZR” (see programming section for instructions) 2. Set “C1 on BOTH” (see programming section for instructions) 3. Circulator-on delay will affect all zones.
25 AquaSmart Boiler Control Manual T o ensure smooth appliance operation, the AquaSmart requires a separation between the High and Low limits no less than the greater differential plus 5°F .
26 Press the “ENTER (RESET)” key . The control will ask you to con fi rm the setting with the following screen: Press “ENTER (RESET)” if the value is correct, or “CANCEL (BACK)” if it is not.
27 AquaSmart Boiler Control Manual Press the “ENTER (RESET)” key . The following screen will be displayed: A B C D T o navigate the history menu, press “ ▲ ” or “ ▼ ” key to view additional data and cycles.
28 T o change the call for heat source that the circulator is activated from (see Figures 8 - 13 for examples), press the “ ▲ ” and “ ▼ ” keys until the following screen is displayed: .
29 AquaSmart Boiler Control Manual Press the “ ▲ ” and “ ▼ ” keys until the following screen is displayed: Press “ENTER (RESET) ” .
30 AquaSmar t Operation T able 4 – Typical operation with default settings (Circulator set “ON TT”) System Action AquaSmart Response T emperature falls below low limit Burner is turned on until the water temperature reaches the low limit plus the low differential.
31 AquaSmart Boiler Control Manual 75 50 100 125 150 175 200 225 250 275 300 75 50 100 125 150 175 200 225 250 275 300 How a Boiler Control Works Figure 19 - Cold Start Operation (Low Limit ► OFF) F.
32 T r oubleshooting Lockout The AquaSmart will lock out if any number of abnormal conditions are detected. Hea tMana ger T ec hnolog y The Beckett AquaSmart comes equipped with the Department of Energy (DOE) 2012 compliant Heat Manager load-matching energy saving algorithm.
33 AquaSmart Boiler Control Manual During Annual Maintenance or More Frequent Service Intervals, V erify the below items. Note: The 7600 control has no serviceable internal parts. DO NOT attempt to repair a malfunctioning control. The control is clean and all vents are free of dust, lint or foreign material.
34 Notes Section.
35 AquaSmart Boiler Control Manual SK10029 Mounting T empla te THIS END UP Use self-drilling screws supplied in the 7600RMU Remote Mount Kit -or- Drill 0.
Form No. 61738 Rev . 6, Printed in USA 6/1 1 CORPORA TION USA: P.O. Box 1289 ● Elyria, OH 44036 Canada: R.W. Beckett Canada, Ltd. ● Unit #3, 430 Laird Road ● Guelph, Ontario N1G 3X7 www.
Een belangrijk punt na aankoop van elk apparaat Beckett 7600 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Beckett 7600 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Beckett 7600 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Beckett 7600 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Beckett 7600 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Beckett 7600 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Beckett 7600 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Beckett 7600 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.