Gebruiksaanwijzing /service van het product RAS-09LKV-UL van de fabrikant Toshiba
Ga naar pagina of 114
R 410 A FILE NO. SVM-10019 SE R VICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit <High W all, Heat Pump T ype> <Heat Pump T ype> RAS-09LKV-UL RAS-09LAV-UL RAS-12LKV-UL RAS-12LAV-UL Feburary.
– 2 – CONTENTS 1 . SAFETY PRECA UTIONS .......................................................................... 3 2 . SPECIFIC A TIONS ..................................................................................... 6 3 . REFRIGERANT R410A .
1. SAFETY PREC A UTIONS Installing, staring up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
DANGER • FOR USE BY QUALIFIED PERSONS ONLY. • TURN OFF MAIN POWER SUPPLY BEFORE.ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK. • CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
CAUTION CAUTION • Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water. • After unpacking the unit, examine it carefully for possible damage. Report any damages to your distributor.
FILE NO. SVM-10019 Unit model Indoor RAS-09LKV-UL RAS-12LKV-UL Outdoor RAS-09LAV-UL RAS-12LAV-UL Cooling capacity (Btu/h) 9000 12000 Cooling capacity range (Btu/h) 3750 -10580 2750 - 13950 Heating cap.
– 7 – 120 100 80 60 40 20 0 100 95 90 85 80 75 70 65 60 55 50 105 90 91 93 95 97 99 100 102 104 106 108 109 111 113 115 Capacity Ratio (%) Capacity Ratio (%) Capacity Ratio: 100% = 9000 Btu/h (RAS-09LKV-UL) 12000 Btu/h (RAS-12LKV-UL) RAS-09LKV-UL RAS-12LKV-UL 2-2.
– 8 – 3. REFRIGERANT R410A This air conditioner adopts the ne w refr igerant HFC (R410A) which does not damage the ozone la y er . The working pressure of the new refrigerant R410A is 1.
– 9 – T able 3-2-1 Thic knesses of annealed copper pipes Nominal diameter (in.) 1/4 3/8 1/2 Outer diameter (mm) 6.35 9.52 12.70 Thi c kness in. (mm) R410A R22 0.0315 ( 0.8 0 ) 0.0315 (0.80) 0.0315 (0.80) 2. Joints F or copper pipes, flare joints or soc ket joints are used.
– 10 – A ØD d) Flare Processing Make certain that a clamp bar and copper pipe ha v e been cleaned. By means of the clamp bar , perf or m the flare processing correctly . Use either a flare tool f or R410A or conv en- tional flare tool. Flare processing dimensions diff er according to the type of flare tool.
– 11 – 43 to 45 45 to 46 B A C D T able 3-2-6 Flare and flare nut dimensions f or R22 Fig. 3-2-2 Relations between flare nut and flare seal surface 2. Flare Connecting Procedures and Precautions a) Make sure that the flare and union por tions do not ha ve an y scar or dust, etc.
– 12 – 3-3. T ools 3-3-1. Required T ools The ser vice por t diameter of pac ked v alve of the outdoor unit in the air-w ater heat pump using R410A is changed to pre vent mixing of other refrigerant. T o reinf orce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare n ut ( F or ∅ 1/2 in.
– 13 – Connect the charge hose to pack ed valv e ser vice por t at the outdoor unit’ s gas side. Recov er the refr iger ant, and check no refrigerant remains in the equipment. (F or refr igerant charging, see the figure belo w .) Connect the charge hose to the vacuum pump adapter .
– 14 – Gauge manifold [ Cylinder with siphon ] [ Cylinder without siphon ] OUTDOOR unit Gauge manifold OUTDOOR unit Refrigerant cylinder Electronic balance Refrigerant cylinder Electronic balance Siphon 1. Be sure to mak e setting so that liquid can be charged.
– 15 – Nitrogen gas cylinder Pipe Flow meter M Stop valv e F rom Nitrogen cylinder Nitrogen gas Rubber plug 2. Characteristics required for flux • Activated temper ature of flux coincides with the brazing temperature . • Due to a wide eff ective temperature r ange, flux is hard to carbonize .
– 16 – 4. CONSTRUCTION VIEWS 4-1. Indoor Unit FILE NO. SVM-10019.
4-2. Outdoor Unit 10-7/8 (275) 2-23/32 ( 69 ) 3-17/32 ( 90 ) 3-17/32 ( 90 ) 23-5/8 ( 600 ) 17-5/32 ( 436 ) WIRE GUARD 12-19/32 (320) 4-1/4 ( 108 ) 4-15/16 ( 125 ) 3-3/8 ( 86 ) 1 ( 25 ) Water Drain Out.
– 18 – 5. WIRING DIA GRAM 5-1. RAS- 09LKV-UL / RAS-09LAV-UL FILE NO. SVM-10019 Outdoor T erminal Block POWER SUPPL Y Indoor T erminal Block L1 L2 S L1 L2 S Heat Exchanger BLK WHI RED GRN&YEL (.
5-2. RAS-12LKV-UL /RAS-12LAV-UL – 19 – FILE NO. SVM-10019 1 1 2 2 1 1 2 2 1 1 2 2 3 3 4 4 5 5 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 .
– 20 – 6. SPECIFICA TIONS OF ELECTRICAL P AR TS 6-1. Indoor Unit L = 10 m H, 16A 2 Outdoor f an m otor 3 Suction tem p. sensor (T S sensor) 10k Ω (25°C) 4 Discharge tem p. sensor (T D sensor) 62k Ω (20°C) 5 Outside air tem p. sensor (T O sensor) 10k Ω (25°C) 6 Heat exchanger tem p.
– 21 – 7. REFRIGERANT CYCLE DIA GRAM 7-1. Refrigerant Cyc le Diagram RAS-09LKV-UL / RAS-09LAV-UL NO TE : • The maximum pipe length of this air conditioner is 66ft (20 m). When the pipe length exceeds 50ft (15m), the additional Deo xidized copper pipe Outer dia.
– 22 – RAS-12LKV-UL / RAS-12LAV-UL NO TE : • The maximum pipe length of this air conditioner is 66ft (15 m). When the pipe length exceeds 50ft (15m), the additional Max. : 66ft (20m) Deo xidized copper pipe Outer dia. : 3/8 in. (9.52mm) Thickness : 1/32 in.
7-2. O p eration Data <Coolin g > Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution Indoor Outdoor P Psia (MPa) T1 °F (°C) T2 °F (°C) (rps) 80/67 98/75 137 to 160 54 to 57 99 to 102 (26.
– 24 – 8. CONTROL BLOCK DIA GRAM 8-1. Indoor Unit M.C.U. Indoor Unit Control Unit From Outdoor Unit 208/230-1-60 Serial Signal Communication (Operation Command and Information) Serial Signal Transmitter/Receiver Converter (D.
– 25 – 8-2. Outdoor Unit (In ver ter Assembl y) 208/230-1-60 MICRO-COMPUTER BLOCK DIA GRAM Driver circuit of P.M.V. Heat exchanger temp.sensor Suction temp.
– 26 – 9. OPERA TION DESCRIPTION 9-1. Outline of Air Conditioner Contr ol This air conditioner is a capacity- v a r ia b le type air conditione r , which uses AC or DC motor f or the indoor for motor and the outdoor f an moto r .
– 27 − 9-2. Operation Description 1 . Basic ope r ation ........................................................................................................... 28 1. Ope r ation control .........................................................
– 28 – Item 1. Basic ope r ation Operation flow and applicable data, etc. 1. Operation control Description Receiving the user ’ s operation condition setup , the operation statuses of indoor/outdoor units are controlled. 1) The operation conditions are selected by the remote controller as shown in the belo w .
− 29 − Ope r ation ON Setup of remote controller Indoor fan motor control / Louver control / Operation Hz Control (Requierment) Indoor unit control Sending of operation command signal Outdoor .
– 30 – Item 2. Indoor f a n motor control Operation flow and applicable data, etc. <In cooling operation> (This operation controls the f an speed at indoor unit side.) The indoor f an (cross flow fan) is oper ated by the phase- control induction motor .
– 31 – Item 2. Indoor f a n motor control Operation flow and applicable data, etc. <In heating operation> Description 1) When setting the f an speed to L, L+, M, M+ or H on the remote controller , the operation is per- f or med with the constant speed shown in Fig.
– 32 – Item 3. Outdoor f a n motor control Operation flow and applicable data, etc. The blo wing air volume at the outdoor unit side is controlled. Receiving the operation command from the controller of indoor unit, the controller of outdoor unit controls f an speed.
– 33 – Item 4. Capacity control Operation flow and applicable data, etc. The cooling or heating capacity depending on the load is adjusted. According to diff erence between the setup value of tempera- ture and the room temperature, the capacity is adjusted b y the compressor re volution.
– 34 – Item 6. Release protective control by tempera- ture of indoor heat exchanger Operation flow and applicable data, etc. <In cooling/dry operation> (Pre vent-freezing control f or indoor.
– 35 – Item Operation flow and applicable data, etc. Description 7. Defrost control (Only in heating operation) (This function remov es frost adhered to the outdoor heat e xchanger .
Horizontal blowing Inclined blowing Blowing downward Air direction Inclined blowing Horizontal blowing Initial setting of "Cooling storage position" Louver : Directs downward ( 35.3 ° ) Heating operation/ AUTO (HEAT) Initial setting of “Heating storage position” Louver : Directs downward (80.
– 37 – Item 9. EC O ope r ation Operation flow and applicable data, etc. When pressing [ECO] b utton on the remote controlle r , a Economic ope r ation is pe r f o r med . <Cooling operation> This function operates the air conditioner with the diff erence between the set and the room temperature as sho wn in the f ollowing figure.
– 38 – Item 10. Temporary operation Operation flow and applicable data, etc. Pressing [RESET] button starts the temporar y opera- tion of [A UT O] operation. When keeping [RESET] button pressed f or 10 seconds or more, the temporary [COOL] operation is perf or med.
– 39 – Item 12. Pulse Modulating valve (P.M.V.) Operation flow and applicable data, etc. This function controls throttle amount of the refrigerant in the refr iger ating cycle. According to operating status of the air conditioner , this function also controls the open degree of v alve with an e xpansion v al v e with pulse Modulation.
– 40 – Item 13. Self-Cleaning Operation flow and applicable data, etc. 1. Purpose The Self-Cleaning operation is to minimize the growth of mold, bacteria etc.
Item 13. Self-Cleaning function Operation flow and applicable data, etc. • Self-Cleaning diagram Description Operation displa y ON OFF OFF FCU f an ON ON OFF r pm is depend on presetting. (500RPM) FCU lou v er OPEN OPEN (12.7º) CLOSE Timer display ON or OFF ON ON or OFF depend on presetting of timer function.
Item Operation flow and applicable data, etc. Description − 42 − FILE NO. SVM-10019 14. Remote-A or B selection 1. Purpose This operation is to operate only one indoor unit using one remote controller .
Item Operation flow and applicable data, etc. Description . − 43 − FILE NO. SVM-10019 . 17 . One-Touch One touch comfort is the fully automated operation that is set according to the preferable condition in a region.
Item Operation flow and applicable data, etc. Description . − 44 − FILE NO. SVM-10019 19. FILTER When the elapsed time reaches 1000 hours after Indicator conditioner operation, the FILTER indicator lights. After cleaning the filters, turn off the FILTER indicator.
– 45 – 9-3. A uto Resta r t Function (Default setting from factory is ON). This indoor unit is equipped with an automatic restar ting function which allows the unit to restar t operating with the set operating conditions in the e vent of a po wer supply being accidentally shut down.
– 46 – 9-3-3. Power Failure During Timer Operation • If Timer operation is set and the power supply shut down accidentally, the previous Timer setting will be cancelled. • Daily-Timer operation will be not affected by power supply failure, if the remote controller is Operation Press [RESET] b utton for more than three seconds.
1 1 1 1 Infrared signal emitter Start/Stop button Mode select button (MODE) Temperature button (TEMP) Fan speed button (FAN Swing louver button (SWING) Set louver button (FIX) On timer butto n (ON) Of.
– 48 – 4. DRY OPERATION (COOLING ONLY) For dehumidification, a moderate cooling performance is controlled automatically. 1. Press MODE : Select Dry .
− 49 − 9. PRESET OPERATION Set your preferred operation for future use. The setting will be memorized by the unit for future operation (except air flow direction). 1. Select your preferred operation. 2. Press and hold PRESET for 3 seconds to memorize the setting.
– 50 – 9- 4 - 3 . Name and Functions of Indications on Remote Cont r oller [Displa y] All indications, e xcept f or the clock time indicator , are display ed by pressing the button. 1 T ransmission mark This transmission mark indicates when the remote controller transmits signals to the indoor unit.
– 51 – 10. INST ALLA TION PROCEDURE 10-1. Installation Diagram of Indoor and Outdoor Units Before installing the wireless remote controller • Loading Batteries 1. Remove the battery cover. 2. Insert 2 new batteries (AAA type) following the (+) and ( − ) positions.
– 52 – FILE NO. SVM-10019 Fig. 10-2- 1 Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be e xposed to a strong wind. Use ∅ 5/16 in. ( ∅ 8 mm) or ∅ 3/8 in. ( ∅ 10 mm) anchor bolts and nuts. · · A P ar ts name Refrigerant piping Liquid side : ∅ 1/4 in.
– 53 – Pa rt No. 1 2 3 P ar t name (Q ’ ty) Installation plate x 1 Wireless remote control x 1 Battery x 2 P ar t name (Q ’ ty) Remote control holder x 1 Filter x 1 Pa rt No.
– 54 – 10-2-3. Installation/Ser vicing T ools Changes in the product and components In the case of an air conditioner using R410A, in order to pre vent an y other refr iger ant from being charged accidentally , the ser vice por t diameter of the outdoor unit control v alve (3 wa y valv e) has been changed.
– 55 – 10-3. Indoor Unit 10-3-1. Installation Location • A location which pr o vides enough spaces around the indoor unit as sh o wn in the dia g r am. • A location where there are no obstacle near the air inlet and outlet. • A location which all o ws easy installation of the piping to the outdoor unit.
– 56 – When the installation plate is directly mounted on the wall 1. Securely fit the installation plate onto the wall b y scre ws with the upper and lower catches, that hold the indoor unit, f acing out. 2. T o mount the installation plate on a concrete wall use anchor bolts.
– 57 – CA UTION • Be sure to ref er to the wir ing system diagr am labeled inside the front panel. • Chec k local electr ical regulations f or any specific wiring instr uctions or limitations .
– 58 – 3/16 in. No gap Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap. If applied, deterioration and drain leakage of the drain plug may occur. How to attac h the drain cap 1. Inse r t h e xagonal wrench 3/16 in.
– 59 – CA UTION • Bind the auxiliar y pipes (two) and connecting cab le with f acing tape tightly . In case of leftward piping and rear-leftward piping, bind the auxiliar y pipes (two) only with f acing tape. Fig. 10-3-18 • Carefully arrange the pipes so that none of the pipes stic k out of the rear plate of the indoor unit.
– 60 – 10-4. Outdoor Unit 10-4-1. Installation Location • A location which pr o vides enough space around the outdoor unit as shown in the diagr am. • A location which can bear the w eight of the outdoor unit and does not allow an increase in noise le v el and vibration.
FILE NO. SVM-10019 Do not apply excess torque. Otherwise, the nut may crack depending on the conditions. Outer dia. of copper pipe Tightening torque Ø1/4 in. (Ø6.35 mm) 10 to 13 lbf.ft (14 to 18 N·m) Ø3/8 in. (Ø9.52 mm) 24 to 31 lbf.ft (33 to 42 N·m) Ø1/2 in.
1. The supply voltage must be the same as the rated voltage of the air conditioner. 2. Prepare the power source for exclusive use with the air conditioner.
Packed valve at liquid side Service port (V alve core (Setting pin)) Packed valve at gas side V acuum pump V acuum pump adapter for counter-flow prevention (For R410A only) Charge hose (For R410A only.
– 64 – 10-7. OTHERS 10-7-1. Gas Leak Test Check the ß are nut connections for the gas leak with a gas leak detector or soap water . Check places for ß are nut connection (indoor unit) Check places for the outdoor unit. V alve cover 10-7-2. Test Operation To switch the TEST RUN (COOL) mode, press RESET button for 10 seconds.
Remote cont r oller A- B selection T o separate using of remote controller f or each indoor unit in case of 2 air conditioner are installed nearly . Remote cont r oller B Setup. 1. Push RESET button on the indoor unit to turn the air conditioner ON. 2.
– 66 – 11. HO W T O DIA GNOSE THE TR OUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Theref ore, diagnose troubles according to the troub le diagnosis procedure as descr ibed below . (Ref er to the check points in servicing wr itten on the wiring diagrams attached to the indoor/outdoor units.
– 67 – CA UTION A high v oltage (equivalent to the suppl y volta g e) is also energized to ground thr ough the sensor s, PMV and other low-v oltage cir cuits. The sensor leads and other wires are covered with insulated tubes f or pr otection. Nevertheless, care must be taken to ensure that these wires are not pinched.
– 68 – 11-1. First Confirmation 11-1-1. Confirmation of P ower Supply Confir m that the po wer break er operates (ON) normally . 11-1-2. Confirmation of P ower V oltage Confi r m that p o w er v oltage is A C 208 − 230 ± 10%. If power v oltage is not in this range , the unit ma y not operate nor mally .
– 69 – 11-2. Primar y J udgment T o diagnose the troubles , use the follo wing methods. 1) Judgment b y flashing LED of indoor unit 2) Self-diagnosis by service check remote controller 3) Judgment of troub le by e very symptom Firstly use the method 1) f or diagnosis.
– 70 – 11-4. Self-Diagnosis b y Remote Controller (Chec k Code) 1. If the lamps are indicated as shown B to E in T ab le 11-3-1, ex ecute the self-diagnosis by the remote controller .
– 71 – FILE NO. SVM-10019 11-4-2 Caution at Servicing 1. After using the service mode of remote controller finished, press the [ ] button to reset the remote controller to normal function. 2. After finished the diagnosis by the remote controller, turn OFF power supply and turn its ON again to reset the air conditioner to normal operation.
FILE NO. SVM-10019 Block distinction Operation of diagnosis function Check code Block Check code Cause of operation Air conditioner status Display flashing error Serial signal 1) Defective wiring of the Indoor unit Flashes when 1) to 3) The outdoor unit never and connecting connecting cable or operates error is detected.
Block distinction Operation of diagnosis function Check code Block Check code Cause of operation Air conditioner status Display flashing error Outdoor P.C. Current on inverter circuit All OFF Flashes after 1. Remove connecting lead wire of the board is over limit in short time.
Block distinction Operation of diagnosis function Check code Block Check code Cause of operation Air conditioner status Display flashing error Compressor drive output error.
Block distinction Operation of diagnosis function Check code Block Check code Cause of operation Air conditioner status Display flashing error Compressor does not rotate. All OFF Flashes after 1. Remove connecting lead wire of the Because of missed wiring, error is detected compressor, and operate again.
– 76 – Operation Measure Item by symptoms Check item Conceivab le pr inciple cause Pa r t s (DB01,C27,T01 and IC02) are defective. FILE NO. SVM- 10019 11-5. Judgement of Trouble by Every Symptom 11-5-1. Indoor unit (Including remote controller) T ur n off pow er supply once, and 5 second later , tur n it on again.
(2) Operation is not turned on though Indoor P.C. board is replaced <Confirmation pr ocedure> NO T ur n off pow er supply once, and 5 second later , tur n it on again.
– 78 – (3) On l y the indoor motor fan does not operate <Prima r y c he c k> 1. Is it possi b le to detect the p o w er supply v oltage ( A C208 – 230V) bet w een and on the te r minal b lo c k? 2.
FILE NO. SVM- 10019 ( RAS-12LKV-UL ) Start to operate indoor unit in cooling operation at airflow level “LOW”. Turn off indoor unit and remove connector from motor. Then start to operate indoor unit with remote controller. Turn off indoor unit and remove connector from motor.
Turn off indoor unit and rotate cross-flow fan by hand when the unit is on standby. At this time, is it possible to detect DC 1V or more between 5 + and 3 – of motor connector (CN 31). Is it possible to change airflow level to “HIGH”? Is it possible to rotate cross-flow fan by hand properly? Fan motor operates normally.
– 81 – Indoor fan starts rotating when power supply is turned on. Measure voltage between 3 (GND : BLACK) and 5 (V line : YELLOW) of motor connector (CN31) while indoor fan motor is rotating. DC 1.0V or more P.C. board is defective. 6 (Blue) 5 (Yellow) 4 (White) 3 (Black) 2 – 1 (Red) Motor is defective.
– 82 – NO YES Push the [ ] button. Is transmission mark indicated? The unit does not beep at all. Operation lamp on indoor unit is not indicated. Is receiver on indoor unit exposed to direct sunlight? Avoid direct sunlight. Keep indoor unit away from fluorescent light.
– 83 – Refer to the chart in 11-6. Gas leak P.M.V. is defective. Miswiring of connecting wires of indoor/outdoor units Clogging of pipe and coming-off of TC sensor Gas circulation amount is down. Measure gas pressure. Gas shortage Gas leak Pipe clogging Thermo.
– 84 – NO NO NO NO YES YES YES YES YES Gas leakage, disconnection of TS/TC sensors (Check code 02, 1C) Discharge temp . error , gas leakage (Check code 03, 1E) 1C 1E Gas amount check and v alve clogging check Remov e TC sensor connector from the P .
11-7. How to Diagnose Trouble in Outdoor Unit YES Turn ON the unit by remote controller and wait for 3 min. Check component parts of control board assembly by visual. (damage, burn,.. Etc.) Check Power Supply (Voltage Rate ±10%) Replace fuse. NO YES YES YES Turn OFF power supply.
– 86 – YES Does outdoor fan operate normally? Replace control board. YES YES Compressor is normal Check voltage of the compressor connector (AC150V-270V)? Turn ON power s upply. NO Remove connector CN300 of outdoor fan motor. Check winding resistance by ohmmeter are correct? Check rotor locking by rotate Turn OFF power supply.
FILE NO. SVM-10019 – 87 – (2) Inspection pr ocedures 1) When a P .C. board is judged to be defectiv e, check f or disconnection, burning, or discolora- tion of the copper f oil patter n or this P .C. board. 2) The P .C. board consists of the follo wing 2 par ts a.
11-8-2. 8 P .C . Board Layout 100 30 40 50 60 70 80 90 20 10 0 01 0 2 0 3 0 4 0 5 0 Resistance value (k ) Temperature ( C) TD : Discharge temp. sensor TA : Room temp. sensor TC : Heat exchanger temp. sensor TO : Outdoor temp. sensor TE : Outdoor heat exchanger temp.
– 89 – ( RAS-12LKV-UL ) 100 30 40 50 60 70 80 90 20 10 0 01 0 2 0 3 0 4 0 5 0 Resistance value (k ) Temperature ( C) TD : Discharge temp. sensor TA : Room temp. sensor TC : Heat exchanger temp. sensor TO : Outdoor temp. sensor TE : Outdoor heat exchanger temp.
– 90 – 11- 8 -3. Indoor Unit (Other Parts) 11- 8 -4. Outdoor Unit No. 1 P ar t name Room temp . (T A) sensor Heat e xchanger (TC) sensor Checking pr ocedure Disconnect the connector and measure the resistance v alue with tester . (Nor mal temp .) No.
– 91 – 11- 8 -5. Che c king Method f or Ea c h P a r t No. 1 P ar t name Electrolytic capacitor (F or boost, smoothing) Checking pr ocedure 1. T ur n OFF the po wer supply breaker . 2. Discharge all three capacitors completely . 3. Chec k that safety v alve at the bottom of capacitor is not brok en.
– 92 – 11- 9 . H o w to Simp l y J ud g e Whether Outdoor F an Motor is Good or Bad 1. Symptom • Outdoor f an motor does not rotate. • Outdoor f an motor stops within sev eral tens seconds though it star ted rotating. • Outdoor f an motor rotates or does not rotate according to the position where the fan stopped, etc.
– 93 – 12. HO W T O REPLA CE THE MAIN P ARTS W ARNING • Since high v oltages pass through the electr ical par ts , tur n off the po wer without f ail bef ore proceeding with the repairs. Electric shocks ma y occur if the power plug is not disconnected.
– 94 – No. P a rt name F ront panel Pr ocedures 4) Press "PUSH" pa r t under the front panel and remov e hooks of the front panel from the installation plate. Remarks Press Front panel Installation plate 5) Remov e the front panel fixing scre ws.
– 95 – No. P a rt name Electric par ts bo x assembly Procedures 1) F o ll o w the procedure up to 3) in abo v e. 2) Remov e screw of ear th lead attached to the end plate of the e vapor ator .
– 96 – No. P a rt name Horizontal louver Procedures 1) Remov e shaft of the hor izontal louv er from the back body . (First remov e the left shaft, and then remov e other shafts while sliding the horizontal louv er leftward.) Ev aporator (Heat e xchanger) 1) Fo llow to the procedure in the item .
– 97 – No. P a rt name 1) F o ll o w to the procedure in the item . 2) Rem o v e the two screws used to secure the bearing base. 3) Remove the bearing base. <Caution at assembling> • If the bea r ing is out from the housing, push it into the specified position and then incorporate it in the main bod y .
– 98 – No. P a rt name F an motor Procedures 1) F oll o w to the procedure till item . 2) Loosen the set screw of the cross flo w fan. 3) Rem o v e t w o fixing scr e ws of the motor cover and them remove the motor cover. 4) Remove two more fixing screws of the motor band and remove the motor band.
– 99 – No. P a rt name Cross flow f an Pr ocedures <Caution at reassembling> 1) To incorporate the fan motor incorporate the motor into the position in the following figure, and then install the fan motor.
– 100 – No. P a rt name Common procedure Pr ocedure 1) T ur n the pow er supply off to stop the operation of air-conditioner . 2) Remov e the front panel. • Remov e the 2 fixing screws . 3) Remov e the electr ical par t base . Remarks Replace ter minal b lock, microcomputer ass’y and the P .
– 101 – 12-3. Outdoor Unit No. P a rt name Common procedure Procedure 1. Detachment NO TE W ear gloves f or this job. Otherwise, you ma y injure y our hands on the parts, etc. 1) Stop operation of the air conditioner , and tur n off the main s witch of the breaker f or air conditioner .
– 102 – No. P a rt name F ront cabinet Procedure 1. Detachment 1) P erf or m step 1 in . 2) Rem o v e the fixing scr e ws (screw 2 pcs.) used to secure the front cabinet and i n v e r ter c o v e r , the scr e ws (screw 3 pcs.
− 103 − No. P a rt name In ver ter assemb ly P r ocedure Remarks 1) P erf or m work of item 1 in . 2) Rem o v e scr e w (ST1 T Ø 4 × 10L 2 pc s .) of the upper par t of the front cabinet. • If removing the in v er ter cover in this condition, P .
– 104 – No. P a rt name Control board assemb ly Pr ocedure 1. Disconnect the leads and connectors connected to the other par ts from the control board assembly . 1) Leads • 3 leads (b lack, white, or ange) connected to ter minal b lock. • Lead connected to compressor : Disconnect the connector (3P).
– 105 – No. P a rt name Side cabinet Procedure 1. Side cabinet (right) 1) P erf or m step 1 in and all the steps in . 2) Rem o v e the fixing scr e w used to secure the side cabinet and heat exchanger. 3) Remove the fixing screw (screw 2 pcs.
– 106 – No. P ar t name Compressor Procedure 1) P erf or m work of item 1 of and , , , . 2) Extract refrigerant gas. 3) Remov e the par tition board. (screw 3 pc s .) 4) Remov e the sound-insulation mater ial. 5) Remov e ter minal cov er of the compressor , and disconnect lead wire of the compressor from the ter minal.
– 107 – No. P a rt name Electronic e xpansion valv e coil Procedure Wire guard 1. Detachment 1) P erf or m work of item 1 of . 2) Remov e the front cabinet, and put it down so that wire guard side directs d o wn w ard. P erform w ork on a corrugated car dboard, c l oth, etc.
– 108 – No. 11 P art name Pr ocedure Remarks TE sensor (outdoor heat e xchanging temperature sensor) • Attachment Install the sensor onto the straight pipe part of the condenser output pipe.
– 1 09 – 13. EXPLODED VIEWS AND P AR TS LIST 13-1. Indoor Unit ( E-Part ) FILE NO. SVM-10019 Location Part Location Part No. No. No. No. 401 43T50326 TEMPERATURE SENSOR 405 43T69641 PC BOARD ASSY;.
FILE NO. SVM-10019 – 110 – 13-2. In door Unit Location Part Location Part No. No. No. No. 201 43T21397 LOUVER MOTOR 215 43T39328 MOTOR BAND (LEFT) 202 43T21409 FAN MOTOR (RAS-09LKV-UL) 216 43T3932.
– 111 – 13- 3 . Outdoor Unit (RAS-09LAV-UL) FILE NO. SVM-10019 Location Part Location Part No. No. No. No. 1 43T00535 FRONT CABINET 18 43T46351 REACTOR 2 43T00459 LEFT CABINET 21 43T20319 PROPELLE.
– 112 – 13- 4 . Outdoor Unit (RAS-12LAV-UL) FILE NO. SVM-10019 Location Part Location Part No. No. No. No. 1 43T00535 FRONT CABINET 18 43T58306 REACTOR 2 43T00459 LEFT CABINET 21 43T20319 PROPELLE.
– 113 – 13- 5 . P .C. Boa r d L a y out FILE NO. SVM-10019 Location Part Location Part No. No. No. No. 701 43T62320 HEATSINK 705 43T50328 TEMPERATURE SENSOR 702 43T69847 PC BOARD (RAS-09LAV-UL) 70.
– 56 – FILE NO. SVM-03005 TOSHIBA CARRIER (THAILAND) CO.,L TD. 144/9 MOO 5, BANGKADI INDUSTRIAL P ARK, TIV ANON ROAD, T AMBOL BANGKADI, AMPHUR MUANG, P A THUMTHANI 12000, THAILAND.
Een belangrijk punt na aankoop van elk apparaat Toshiba RAS-09LKV-UL (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Toshiba RAS-09LKV-UL heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Toshiba RAS-09LKV-UL vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Toshiba RAS-09LKV-UL leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Toshiba RAS-09LKV-UL krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Toshiba RAS-09LKV-UL bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Toshiba RAS-09LKV-UL kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Toshiba RAS-09LKV-UL . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.