Roof t op Air Handlers Nov ember 20 07 RT - P RC 0 31 - E N Int elliP ak™ II Air Handlers Casing A -C, 160 0 0-450 0 0 CFM—60 Hz.
Intr oduction ©20 07 T rane RT -PRC031-EN Int elliP ak™ II Roof t op Air Handlers Designed F or T oda y , T omor r o w and Be y ond Built on the legacy of T rane's industry leading IntelliPak, the IntelliPak II Air Handler platform is de signed for the future.
RT -PRC031 -EN 3 F eat ures and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Controls V ariable Air V olume (V A V) Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 RT -PRC031-EN Standar d Feat ur es • 1600 0-450 0 0 CFM (Casings A, B, C) industrial/ commercial Ro ofto p Air Handlers • ASHRAE 90.1 - 20 1 0 Efficiency Compliant • IBC (International Buil di.
RT -PRC031 -EN 5 Features and Benefits Optional Feat ur es Contr ols • Demand control ventilation (energy saving CO 2 economizer control) • T winning of up to four units for applications on co mmo.
6 RT -PRC031-EN Features and Benefits Field Installed A ccessor ies • Roof curbs • Wireless zone sensor • Programmable sensor s with night setbac k—CV and V A V • Sensors without night setba.
RT -PRC031 -EN 7 Features and Benefits Application Flexibility • Chilled w ater or no coo ling alternatives • A variety of c hilled water coil offerings to meet a diverse range of capacity require.
8 RT -PRC031-EN Features and Benefits pac k ages to mi nimize custom programming requirem ents and enable system se tup and control through simpl e editing of parameter s in the standard applications softw are.
RT -PRC031 -EN 9 Features and Benefits 2. interface with T rane T racer™ building manageme nt system 3. interface with a generic (non- T rane) bu ilding management system. All setup parameters are preset from the factory , requiring less star t-up time duri ng installation.
10 RT -PRC031-EN Features and Benefits Supply F ans with Inlet Guide Va n e s T rane airfoil fans with inlet guide vanes pre-rotate the air in the direction of the fan wheel, decreasing static pressure and horsepower , essentially unloadin g the fan wheel.
RT -PRC031 -EN 11 V A V Units Only Note: When noted in th is sequence “Human Interface P anel, ” the reference is to both the unit mounted and remo te mounted Human Interface P anel. All setpoint adjustments can be accomplished at the unit or Remote Human Interface Pa ne l.
12 RT -PRC031-EN Controls Variable Ai r Volume (VAV) Only temperature from se tpoint, i.e., the fur ther away from se tpoint, the faster the fresh air damper will open. Note : The economiz er is only allowed to functio n freely if one of the following conditions is met.
RT -PRC031 -EN 13 Controls Variable Ai r Volume (VAV) Only overheat. The supply air temperature setpoint is adjust ed based on the temperature of the critical zone(s). This can ha ve the effect of improving comfor t and/or lowering energ y usage. The user -defined parameters are the same as for outdoor air rese t.
14 RT -PRC031-EN CV Units Only Occupied Zone T emper atur e Control Cooling/Economiz er During Occup ied cooling mode, t he economiz er (if provided) an d mec hanical cooling a re used to control zon e temperature. The zone temperature cooling setpoint is user - defined at the Human Interface Panel or from the BAS/Network.
RT -PRC031 -EN 15 Controls Constant Volume (CV) Only Electr ic Heating The individual stages of electric heat will be sequenced on the z one demand. The number of available stages will depend on the unit s ize and heat capacity selected.
16 RT -PRC031-EN Common to V A V and CV Units S p a ce P re s s ure C o n t ro l - Statitr ac™ A pressure transdu cer is used to measure an d repor t direct space (building) static pressure. The user - defined contro l parameters used i n this control sc heme are space static pressure setpoint , space pressure deadband and exhaust enable point.
RT -PRC031 -EN 17 Controls VAV and CV – Return VFD - Max (if so equipped) 4. EMERG_SHUTDO WN: – Supply F an - Of f – Supply F an IGV / Su pply Fan VFD - Closed/Min (if so equipped) – Exhaust F.
18 RT -PRC031-EN Controls VAV and CV – Supply F an IGV/ Supply F an VFD - Max (if so equipped ) – Exhaust Fa n - On; Exhaust Dampers Open (if so equipped) – O A Dampe rs - Open; Return Damper - .
RT -PRC031 -EN 19 Controls VAV and CV 8. Supply Air Static Pressure Setpoint 9. Minimum Ou tside Air Flow Setpoint 1 0. Morning W arm Up Setpoint 1 1 . Economiz er Dry Bulb Enable Setpoint 12. Supply Air R eheat S etpoint 13. Minim um Outside Air Position Setpoint 1 4.
20 RT -PRC031-EN Controls VAV and CV function and the supp ly fan. The air handler unit will cycl e through the evening as heat ing/coo ling (if enabled) is requ ir ed in the space. When the tim e cloc k switc hes from night setbac k to o ccupied mode, all heating/cooling fun ctions begin normal operation.
RT -PRC031 -EN 21 Controls VAV and CV If there is a call for economiz er cooling, the outdoo r air damper may be opened furthe r to satisfy the cooling request.
22 RT -PRC031-EN Exhaust/Retur n F an Options When is it necessary to provide building exhaust? Whenever an outdoor air econ omizer i s used, a building generall y requires an exhaust system. The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or under -pressurization of the building .
RT -PRC031 -EN 23 Applications Considerations The T rane 1 0 0 percent modulating exhaust system with Statitrac provides ef ficient control of buildin g pressure in most applications simply because 1 .
24 RT -PRC031-EN Applications Considerations T able 1 Supply Airf low Co nfigur ation Cabinet Configuration Supply Airflow Discharge Direction Type Acceptable Application With Bag Final Filters With C.
RT -PRC031 -EN 25 Applications Considerations When using an IntelliP ak II Air Handler for horizontal supply an d/or return, an additional pressure drop must be added to the supply external static to account for the 90 degree turn the air is makin g. This additiona l pressure drop depends on airflow and air handler siz e, but a range of 0.
26 RT -PRC031-EN Applications Considerations will help reduce soun d transmission. The ASHRAE publication "A Practical Guide to Noise and V ibration Control for HV AC Systems" also pro v ides valuable i nformation. There are several other sources of unit sound, i.
RT -PRC031 -EN 27 Applications Considerations Duct Design It is impor tant to note that the rated capacities of the ai r handler can be met only if the air handler is properly installed in the field. A well-designed duct system is essential in m eeting these capacities.
28 RT -PRC031-EN This section outlines a step-by -step procedure that may be used to select a T rane air handler . The sample selection is based on the following conditions: Summer Design: • Summer outdoo r design conditions - 95 DB/7 6 WB ambient temperature • Summer ro om design conditions -78 DB/65 WB • T otal cooling load - 980 MBH (81 .
RT -PRC031 -EN 29 Selection Procedure at 95°F is approximatly 1336 MBH total coolin g and 969 MBH sensible cooling capacity . Step 6 - Det er mine Leaving Air T emper atur e Unit sensible heat capacity cor rected for supply air fan motor heat = 969 MBH S ensible - 1 09.
30 RT -PRC031-EN Selection Procedure Exhaust F an Motor Sizing The exhaust/r eturn fan is selected based on total return system nega tive static pressur e and exhau st fan CFM. Return system neg ative static includes return duct static, and any other job site applicable static pressure drop.
RT -PRC031 -EN 31 DIGIT 1 — UNIT T YPE W Self-Contained (P ackaged Air Handler) DIGIT 2 — UNIT FUNCTI ON E Electric Heat F Natural Gas H eat LH o t W a t e r H e a t S Steam He at X No Heat DIGIT .
32 RT -PRC031-EN Model Number Description A Return w/o Statitrac CV Only C Return w/ VFD w/ Bypass w/ Statitrac E Return w/ VFD w/o Bypass w/ Statitrac DIGIT 18 — EXHA UST/RETURN F AN MO T OR SELECTION 0N o n e D 7 .
RT -PRC031 -EN 33 Model Number Description DIGIT 37 — SER VICE ENHANCEMENTS 0 Single Side Access Door s A Dual Side Access Doors B Single Side Access Door s / Marine Lights C Dual Side Access Doors .
34 RT -PRC031-EN T able 3 General D ata (All dimensions in inches) Casing A Casing B Casing C Supply Fans Std CFM Number/Size/T ype Number of Motors HP Range CFM Range/CFM at Max SP T otal SP R ange-(In. WG) 1/25/ DW AF 1 15 - 50 16000-31000/22000 7.5 1/32/ DW AF 1 15 - 60 20000-38000/32000 7.
RT -PRC031 -EN 35 General Data Filters Standard 2" High Efficien cy Throwaway Filters Number/Size Fa c e a r e a (F t 2 ) 21 - 20X24X2 5 - 12X24X2 80 21 - 20X24X2 5 - 12X24X2 80 21 - 20X24X2 5 - .
36 RT -PRC031-EN General Data T able 4 Gas Heat Inputs/Input Ranges TWO-STAGE G AS HEAT Standard Gas Heat Input (MBH) Low Gas Heat Inputs (MBH) High Fire Heat Input (MBH) Modulat ing Gas Heat Range (M.
RT -PRC031 -EN 37 T able 6 Enthalpy of Sat ur ated Air Wet Bulb Temperature Btu per Pound 41 15.70 43 16.66 42 16.17 43 16.66 44 17.15 45 17.65 46 18.16 47 18.68 48 19.21 49 19.75 50 20.30 51 20.86 52 21.44 53 22.02 54 22.62 55 23.22 56 23.84 57 24.48 58 25.
38 RT -PRC031-EN T able 9 Chilled W ater Coil Capacities—2 Ro w 5W Entering Dry Bulb/Wet Bulb 80/67 F Entering Water 45 F Water Temperature Rise F 10 F Without Turbulators With Turbulators Air Flow .
RT -PRC031 -EN 39 Performance Data—Chilled Water Coil Capacities T able 1 0 C hilled W ater Coil Capacities—4 Row W Entering Dry Bulb/Wet Bulb 80/67 F Entering Water 45 F Water Temperature Rise F .
40 RT -PRC031-EN Performance Data—Chilled Water Coil Capacities T able 1 1 Chilled W ater Coil Capacities—6 Row WD Entering Dry Bulb/Wet Bulb 80/67 F Entering Water 45 F Water Temperature Rise F 1.
RT -PRC031 -EN 41 Performance Data—Chilled Water Coil Capacities T able 12 Chilled W ater Coil Capacities—8 Row WD Entering Dry Bulb/Wet Bulb 80/67 F Entering Water 45 F Water Temperature Rise F 1.
42 RT -PRC031-EN T able 13 Supply F an P erfor mance ST AND ARD CFM — Casing A (25") CFM Total Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.50 1.75 2.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP R PM BHP RPM BHP 16000 1030 (i) 6.
RT -PRC031 -EN 43 Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) CFM Total Static Pressure Std. 6.25 6.50 6.75 7. 00 7.25 7.50 7.75 8.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP R PM BHP RPM BHP 16000 1644 23.
44 RT -PRC031-EN Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) T able 14 Supply F an P erfor mance ST AND ARD CFM — Casing A (25") 0 5000 .
RT -PRC031 -EN 45 Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) T able 15 Supply F an P erfor manc e ST AND ARD CFM —Casing B (32") CFM Total Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.
46 RT -PRC031-EN Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) CFM Total Static Pressure Std. 4.25 4.50 4.75 5. 00 5.25 5.50 5.75 6.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP R PM BHP RPM BHP 23000 1117 23.
RT -PRC031 -EN 47 Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) T able 16 Supply F an P erfor mance ST AND ARD CFM—Casing B (32") 0 5000 1.
48 RT -PRC031-EN Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) T able 1 7 Supply F an Perf orma nce ST AND A RD CFM — Casing C (36") CFM Total Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.
RT -PRC031 -EN 49 Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) CFM Total Static Pressure Std. 4.25 4.50 4.75 5. 00 5.25 5.50 5.75 6.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP R PM BHP RPM BHP 23000 934 22.
50 RT -PRC031-EN Performance Data — Supply Fan without Inlet Guide Vanes (with or without Variable Frequency Drive) CFM Total Static Pressure Std. 8.25 8.50 Air RPM BHP RP M BHP 23000 1275 47.06 1294 48.70 24000 1276 48.66 1296 50.45 25000 1276 50.25 1296 52.
RT -PRC031 -EN 51 T able 18 Supply F an P erfor mance ST AND ARD CFM — Casing A (25") CFM Total Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.50 1.75 2.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 16000 1064 (i) 7.
52 RT -PRC031-EN Performance Data — Supply Fan with Inlet Guide Vanes CFM Total Static Pressure Std. 6.25 6.50 6.75 7. 00 7.25 7.50 7.75 8.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 16000 1657 24.15 1678 24.95 1697 25.68 1719 26.
RT -PRC031 -EN 53 Performance Data — Supply Fan with Inlet Guide Vanes Figur e 20. Supply F an Perf ormance ST AND ARD CFM—Casing A (25") 0 5000 10000 1500 0 20000 2500 0 30000 3500 0 0 1 2 3.
54 RT -PRC031-EN Performance Data — Supply Fan with Inlet Guide Vanes T able 19 Supply F an P erfor mance ST AND ARD CFM — Casing B (32") CFM Total Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.50 1.75 2.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 20000 683 (i) 5.
RT -PRC031 -EN 55 Performance Data — Supply Fan with Inlet Guide Vanes CFM Total Static Pressure Std. 4.25 4.50 4.75 5. 00 5.25 5.50 5.75 6.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 20000 1072 20.24 1093 21.23 1114 22.
56 RT -PRC031-EN Performance Data — Supply Fan with Inlet Guide Vanes Figur e 21 . Supply F an P erfor mance S T ANDARD CFM—Ca sing B (32") 0 5000 10000 15000 20000 25000 30000 35000 40000 45.
RT -PRC031 -EN 57 Performance Data — Supply Fan with Inlet Guide Vanes T able 20 Supply F an P erfor mance ST AND ARD CFM — Casing C (36") CFM Total Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.50 1.75 2.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 23000 559 (i) 5.
58 RT -PRC031-EN Performance Data — Supply Fan with Inlet Guide Vanes CFM Total Static Pressure Std. 4.25 4.50 4.75 5. 00 5.25 5.50 5.75 6.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 23000 929 22.80 952 24.15 975 25.48 998 26.
RT -PRC031 -EN 59 Performance Data — Supply Fan with Inlet Guide Vanes CFM Total Static Pressure Std. 8.25 8.50 Air RPM BHP RP M BHP 27000 1276 52.75 1294 54.50 28000 1279 54.48 1297 56.19 29000 1280 56.01 1299 57.96 30000 1283 57.73 1302 59.69 31000 1288 59.
60 RT -PRC031-EN T able 21 Exhaust F an Perf or mance L O W CFM—Case B , ST AND ARD CFM—Case A (25" F an) CFM Negative Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.50 1.75 2.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 10000 260 (i) (i) Outlined area in dicates nonstandard BHP or R PM selections.
RT -PRC031 -EN 61 Performance Data—Exhaust Fan Figur e 23. Exhaust F an Perf ormance L OW CF M—Case B, S T AND ARD CFM—Case A (25" F an) 0 5000 10000 15000 20000 25000 30000 0 1 2 3 4 5 9 0.
62 RT -PRC031-EN Performance Data—Exhaust Fan T able 22 Exhaust F an Perf or mance L O W CFM—Case C; S T ANDARD CFM — Case B (28" F an) CFM Negative Static Pressure Std.
RT -PRC031 -EN 63 Performance Data—Exhaust Fan Figur e 24. Exhaust F an P erf or mance L OW CFM— Case C; S T ANDARD CFM—Case B (28" F an) 0 5000 10000 15000 200 00 25000 30000 35000 40000 4.
64 RT -PRC031-EN Performance Data—Exhaust Fan T able 23 Exhaust F an Perf or mance ST AND ARD CFM—Case C (32" F an) CFM Negative Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.50 1.75 2.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 23000 272 (i) (i) Outlined area in dicates nonstandard BHP or R PM selections.
RT -PRC031 -EN 65 Performance Data—Exhaust Fan T able 24 Exhaust F an Perf or mance ST AND ARD CFM—Case C (32" F an) 0 5000 10000 15000 20000 25000 30000 35 000 40000 45000 50000 55000 0 1 2 .
66 RT -PRC031-EN T able 25 Retur n Fan P erfor mance ST ANDARD CFM—Case A (36.5" F an) CFM Negative Static Pressure Std. 0.25 0.50 0.75 1. 00 1.25 1.50 1.75 2.0 0 Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP M BHP RPM BHP 16000 614 (i) (i) Outlined area in dicates nonstandard BHP or R PM selections.
RT -PRC031 -EN 67 Performance Data—Return Fan Figur e 25. Retur n F an P erf or mance ST AND ARD CFM—Case A (36.5" F an) 0 5000 10000 15000 20000 25000 30000 35000 40000 0 1 2 3 4 5 6 7 8 9 1.
68 RT -PRC031-EN Performance Data—Return Fan T able 26 Retur n F an P erfor mance ST AN DARD CFM—Case B and Case C (40" F an) CFM Negative Static Pressure Std.
RT -PRC031 -EN 69 Performance Data—Return Fan Figur e 26. Retur n F an P erfor mance ST AND ARD CFM—Case B and Case C (40" F an) 0 50 00 10000 15000 20000 25000 300 00 35000 40000 45000 0 1 2.
70 RT -PRC031-EN T able 27 Natur al Gas Heating Capacities 1 Air Temper ature Ri se vs. Unit C FM CFM Case Gas Heat Module s Heat Input (MBh) Heat Output (MBh) 18000 20000 22000 24000 26000 30000 34 000 38000 42000 46000 A, B, C LOW 850 680 34.8 31.3 28.
RT -PRC031 -EN 71 Performance Data—Heat T able 30 Hot W ater Coil Heating Capacities (Q/ITD) Water Flow High Capac ity Low Capac ity (GPM) 40 80 120 160 200 30 60 100 140 175 Casing Airflow (CFM) WPD (ft.) 0.3 1.0 2.1 3.7 5 .6 0.2 0.6 1.5 2.8 4.3 A, B, C 16000 7.
72 RT -PRC031-EN T able 33 Chille d W ater Coil Airside Pressur e Drop (in H 2 0) Chilled Water Coil Airside Pressure Drop (in H 2 O) 2 row 4 row 6 row 8 row Casing CFM 80 fpf 108 fpf 144 fpf 168 fpf 80 fpf 108 fpf 144 fpf 168 fpf 80 fpf 108 fpf 144 fpf 168 fpf 80 fpf 108 fpf 144 fpf 168 fpf A, B, C 16000 0.
RT -PRC031 -EN 73 Performance Data—Component Static Pressure Drops/ Fan Drive Selections T able 35 Component Static Pr essure Dr ops (in. H 2 O) Standard Filter Section (Cooling Coil) Final Filter S.
74 RT -PRC031-EN Performance Data—Component Static Pressure Drops/ Fan Drive Selections T able 36 Supply Air F an Dr ive Selections Casing Low/ Std RPM Horse Power (HP) 15 HP 20 HP 25 HP 30 HP 40 HP 50 HP 60 HP 75 HP Drive No. Drive No. Drive No. Drive No.
RT -PRC031 -EN 75 Performance Data—Component Static Pressure Drops/ Fan Drive Selections T able 37 Exhaust Air F an Driv e Selections Casing Low/ Std RPM Horse Power (HP) 7.5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 40 HP 50 HP 60 HP Drive No. Drive No. Drive No.
76 RT -PRC031-EN Electr ical Service Sizing T o correctly siz e electrical service wiring for a unit, fi nd the appropriate calculations listed be low. Ea c h type of unit has its own set of calculations for MCA (Minimum Circuit Ampacity), MO P (Maximum Overcurrent P rotection), and RDE (Recommended Dual Element fuse size).
RT -PRC031 -EN 77 T able 39 Electr ical Service Sizing D ata—Mot ors Supply Fan Motors Motor Horsepower 460 V 575 V FLA FLA 15 19.3 15.4 20 25.5 20.4 25 30.5 24.5 30 37.5 30 40 48.5 39 50 61 49.2 60 72 58 75 88 70 Exhaust/Return Fan Motors Motor Horsepower 460 V 575 V FLA FLA 7.
78 RT -PRC031-EN Electrical Data T able 42 V oltage Utilization Range Unit Voltage 460/60/3 414-506 575/60/3 517-633 T able 43 Electr ical Service Sizing D ata - Con venience Ou tlet T ransf ormer Nominal Tons Voltage 460 575 FLA Add FLA Add 90-150 3.
RT -PRC031 -EN 79 Figur e 27 . Unit T op/F ron t Vie w Dimensional D ata.
80 RT -PRC031-EN Dimensional Data T able 44 U nit Dimensions (In.)—One-Pi ece Unit ONE-PIECE Dimension s Lifting Lug Locations Unit D imensions Air Han dler Side Unit Width Casing Blank S e c t i o .
RT -PRC031 -EN 81 Dimensional Data T able 45 Downflo w/Hor izontal Airf lo w Configur ation Dimensions (In.) DOWNFLOW Opening Dimensions Return Opening—with or without Exhaust Fan Return Opening—w.
82 RT -PRC031-EN Dimensional Data Figure 28. Electr ical Entry Details/Bottom View 16 60 3 4 71 1 4 76 1 4 81 1 4 46 1 16 48 1 16 61 3 4 44 Ø3 5 8 Ø1 1 16 Ø 7 8 6 5 16 5 5 16 Marine lights customer.
RT -PRC031 -EN 83 Dimensional Data Figure 29. Piping Enclo sur e Piping.
84 RT -PRC031-EN Dimensional Data Figure 30. Chilled W ater Piping Locati ons.
RT -PRC031 -EN 85 Dimensional Data Minimum Clearance Details Figure 31 . Minimum Required Clear ance (i) (i) Unit drawing is repre sentative only and may no t accurately depict all models. T able 46 Minimum Required Clearance Unit Option Selection (Door Swing Ft.
86 RT -PRC031-EN Dimensional Data Do wnflo w Roof Curb Figur e 32. Optional Roof Curb (Downflo w) T able 47 Downf low Roof Curb Dimensio ns (In.) Dimensions Casing Blank Section A B C D E F G H I J A,.
RT -PRC031 -EN 87 Dimensional Data Field Installed Sensors — V a r iable Air V olume (V A V) Figur e 33. Field Installed V A V Zone Sensors SINGLE SETPOIN T SENSOR WITH S Y STEM FUNCTION LIGHT S (BA Y SENS021*) PROGRAMMABLE NIGHT -SETBA CK SENSOR (BA Y SENS020*) Notes: 1.
88 RT -PRC031-EN Dimensional Data Field Installed Sensors — Constant V olume (CV) Figure 34. Field Installed CV Zone Sensors PROGRAMMABLE NIGHT -SETBA CK SENSOR (BA Y SENS0 19* ) DU AL SETPOINT , MA.
RT -PRC031 -EN 89 Dimensional Data Field Installed Sensors — V A V and CV Figur e 35. Field Installed V A V and CV Zone Sensors REMO TE MINIMUM POSITION POTENTIOMETER CONTROL (BA Y ST A T023*) TEMPERA TURE SENSOR (BA Y SENS0 1 6*) Notes: 1. Remote sensors are available for use with al l zone sensors to provide re mote sensing c apabilities.
90 RT -PRC031-EN Dimensional Data Field Installed Sensors — V A V and CV Figur e 36. Field Installed V A V and CV Zone Sensors Note: The d i mens i ons a re the s a me f or both the sensor a nd the re c e i ver . 2.90 in. (73.5 mm) 1.08 in. (2.75 mm) 4.
RT -PRC031 -EN 91 Notes: 1. W eights shown i nclude the following fe atures: standard coils, 0 -25% Fresh Air , throwaway filters, low cfm supply fan, mi nimum m otor sizes (high efficiency), constan t volume, 460 XL, No heat 2. W eights shown represen t approximate operatin g weights and hav e a + 5% accuracy .
92 RT -PRC031-EN Weights AB C Size Wt (lbs.) Size Wt (lbs.) Size Wt (lbs.) 4 Row W Chilled W ater Coil - 80 FPF 1523 1523 1523 4 Row W Chilled W ater Coil - 108 FPF 1622 1622 1622 4 Row W Chilled W at.
RT -PRC031 -EN 93 Weights AB C Size Wt (lbs.) Size Wt (lbs.) Size Wt (lbs.) Control Box - Main Control Box - Main 454 454 454 Convenience Ou tlet 36 36 36 T able 50 Roof Curb W eights Casing Blank Installed Weight Shippi ng Weight A, B, C None 1066 1334 4 Ft 1147 1415 8 Ft 1228 1497 T able 49 Component W eights (Lbs.
94 RT -PRC031-EN A full range of fact ory installed options are available, allowing for the air handler design that best suits eac h individual appli cation. Chilled W ater Cooling • ARI certified type 5W , W , or WD coils pro vided with w ater modulating valve and actuat or .
RT -PRC031 -EN 95 Options to 1 0 0 percent supply ai r . The fan operates in conjun ction with the supply fan. The relief damper modulates in response to economiz er damper position on Constant V olume air ha ndlers.
96 RT -PRC031-EN Options • MERV 1 4, 90-95 percent, high temperature rated, cartridge, final filter opti on—A vailable on gas and electric heat units with eight foot blank section unit casing option onl y . T wel ve-inc h deep cartri dge filters are U.
RT -PRC031 -EN 97 Options with V A V air handlers to control duct static pressure. Option includes vanes and static pressure controls. Airfoil supp ly fans with inlet vanes are an efficient w ay to mec hanically modulate airflow .
98 RT -PRC031-EN Options Pro vided for those cases where non-T racer building management system is used. The GBA S module pro vides a binary input for Demand Limiting, four (4 ) analog inpu ts for setpoint adjustment and fi ve (5) relay outputs for diagnosti c repor ting.
RT -PRC031 -EN 99 Options no service mode interface is allowed remotely for safety reasons. • T rane LonT alk ® Communication Interface kit—For future opportunities and upgrade flexibility , this.
10 0 R T -PRC031-EN Genera l Units shall be specifi cally designed for outdoor air hand ler installation on a roof curb and be completely factory assembled and tes ted, piped, internally wired and shipped in one piece. Air handlers shall be available as either no cooli ng or c hilled water cooling units.
RT -PRC031 -EN 101 Mechanical Specifications Cooling S yst em Chilled W at er Coil Coils shall be of type 5W , W , or WD and have a tube in shee t design with 5/8” OD, 0.020” copper tubing mec hanically bonded to aluminum fins. Header s shall be constructed of copper tubing wit h steel pipe connections.
10 2 RT -PRC031 -EN Mechanical Specifications Filters Gener al Filter options shall m ount integral within the unit and be accessible by a hinged access door with a single point latc hing device.
RT -PRC031 -EN 10 3 Mechanical Specifications MERV 1 4, 90-95 P erc ent, Lo w Pr essur e Dr op, T otally Incinerable, Car tri dge, Final Filt er Option Note : A vailable on cooling only units with four or eight-foot blank section, as well as steam and hot water units with eight-foot bl ank section, unit casing only .
10 4 RT -PRC031 -EN Mechanical Specifications Retur n Air Gener al Return air options shall include 1 0 0 percent modulating return fan and 1 0 0 percent mod ulati ng return with direct space building pressurization control. Return fans shall be either standard or low airflow .
RT -PRC031 -EN 10 5 Mechanical Specifications Economizer Cont rol with Comparati ve Ent halpy Used with the fresh air economizer , two enthalpy sensor s are provided to compare total heat content of the indoor air and outdoor air to determine the most ef ficient air source when economizin g.
10 6 RT -PRC031 -EN Mechanical Specifications temperature control and V A V Supply Air temperature con trol. • V A V z one sensor shall be provided wi th supply air single temperature setpoint a nd A UT O/ OFF system switc h. Status indication LED lights shall include: System On, Heat, Coo l an d Ser vi ce .
.
WWW.T rane.com For more information, contact your loc al T rane office or e-mail us at comfort@trane.com Literature O rder Number RT -PRC031-EN Date November 2007 Super sedes New T rane has a policy of continuous product and pro duct data improvement and re serves the right to c hange design and specifications without notice.
Een belangrijk punt na aankoop van elk apparaat Trane RT-PRC031-EN (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Trane RT-PRC031-EN heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Trane RT-PRC031-EN vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Trane RT-PRC031-EN leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Trane RT-PRC031-EN krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Trane RT-PRC031-EN bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Trane RT-PRC031-EN kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Trane RT-PRC031-EN . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.