This T raulsen unit is built to our highest quality standards. We build our refrigerators, freezers and heated cabinets this way as a matter of pride. This philosophy has made Traulsen the leader in commercial refrig- eration since 1938.
T ABLE OF CONTENTS The serial tag is a permanently affixed sticker on which is recorded vital electrical and refrigeration data about your T raulsen product, as well as the model and serial number .
-2- II. RECEIPT INSPECTION All T raulsen products are factory tested for perfor- mance and are free from defects when shipped. The utmost care has been taken in crating this product to protect against damage in transit. All interior fittings have been carefully secured and the legs or casters are boxed and strapped inside to prevent damage.
IV . b - FREEZER NORMAL OPERA TION (continued) : factory for six equally spaced defrost cycles within each 24- hour period. At the start of a freezer defrost cycle, both the compressor and evaporator fans are OFF . The microprocessor control will read “ dEF ” (see figure 3).
Fig. 7 Lift-Up Louver Assembly -4- V. CARE & MAINTENANCE V. a - CLEANING THE CONDENSER: The most important thing you can do to insure a long, reliable service life for your T raulsen is to regularly clean the condenser coil.
V. e - CLEANING THE INTERIOR: For cleaning both stainless steel and anodized alumi- num interiors, the use of baking soda as described in section “ V. d” is recommended. Use on breaker strips as well as door gaskets. All interior fittings are remov- able without tools to facilitate cleaning.
-6- LED For ° F LED For ° C 3-Digit (red) LED Display Defrost Icon W ith LED VII. b - CONTROL P ANEL: ° F ° C FREEZER SET VII. c - P ARTS ASSEMBL Y: HOLDER CLIP* 377-60038-00 TRAULSEN VERTICAL CONTROLLER** 337-60064-00 INCLUDES ALL SHOWN EV AP COIL *= Can be ordered separately **=Requires unit Model No.
-7- VII. MICROPROCESSOR CONTROL (continued) VII. d - NOTES T O THE USER: Y ou only have 20-30 seconds between button pushes. If you take longer than 30 seconds, the controller will revert back to displaying the cabinet temperature.If you enter the wrong security code, the controller will revert back to displaying the cabinet temperature.
Listed below are the available parameters in the order they appear , using the down arrow key on the controller . Y ou can use either the up or down arrow keys to scroll through the options.
VII. h - ADJUSTING THE THERMOST A T SET POINT LOW : This parameter sets the low point of the desired cabinet temperature range. T ypically , freezers will range from -6 ° F to -4 ° F (-21 ° C to -20 ° C) and refrigerators will range from 32 ° F to 34 ° F ( 0 ° C to 1 ° C) for this parameter setting.
-10- VII. j - SETTING THE 24-HOUR CLOCK: The internal timeclock must be set in order for the data storage memory to correctly log events and to allow any defrost lock out to occur at the correct time of day . If the clock is not set, the control assumes the time is 12 a.
-1 1- VII. MICROPROCESSOR CONTROL (continued) VII. k - SETTING THE DA TE: The date must be set in order for the data storage memory to correctly log events. Follow the instruc- tions to enter the customer access code on page 7. When the control displays Thermostat Set Point High, press the down arrow key until the control display reads Date.
° F ° C FREEZER SET This parameter allows a service technician to start a defrost cycle at any time. This parameter will override any lockout settings. Follow the instructions to enter the customer access code on page 7. When the control displays Thermostat Set High, press the down arrow key until the control display reads Start Manual Defrost.
-13- The defrost lockout parameters allow the customer to prevent the unit from going into a defrost cycle for two hours during a set timeframe. Customers can set up to four defrost lockout parameters. They are all programmed the same way . The parameters will be set for the time the lockout is to start.
-14- VII. MICROPROCESSOR CONTROL (continued) VII. o - ADJUSTING THE ROOM TEMPERA TURE OFFSET : The room temperature of fset parameter allows a service technician or end user the ability to have the display show a temperature that is within three degrees of the actual temperature being read by the cabinet air sensor .
VIII. TROUBLE SHOOTING GUIDE FIND YOUR PROBLEM HERE REMEDY 1. Condensing unit fails to start. a. Check if cord & plug has been disconnected. b. Check control temperature setting. 2. Condensing unit operates for a. Are doors closing properly? prolonged periods or continuously .
-16- IX. W ARRANTY INFORMA TION ST ANDARD DOMESTIC W ARRANTY TRAULSEN & CO., INC. warrants new equipment to the original purchaser , when installed within the United States against defective material and workmanship for one (1) year from the date of original installation.
XI. P ARTS LIST P ART P ART # DESCRIPTION Bulb, Fluorescent 337-27690-00 Replacement bulb for fluorescent light models Bulb, Incandescent 337-29776-00 Replacement bulb for incandescent light models Bu.
XII. INDEX -18- A B C Cleaning 4, 5 Casters 2 Cord & Plug 3 Clearance 3 Conversion Key Switch 3 Customer Access Code 7 Customer Service Parameters 8 D Daylight Savings T ime 1 1 Defrost 3 Defrost .
T raulsen 4401 Blue Mound Road Fort Worth, TX 76106 Phone: (800) 825-8220 Fax-Svce: (817) 740-6757 W ebsite: www .traulsen.com HOURS OF OPERA TION: Monday thru Friday 7:30 am - 4:30 pm CST Quality Ref.
Een belangrijk punt na aankoop van elk apparaat Traulsen G-Series (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Traulsen G-Series heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Traulsen G-Series vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Traulsen G-Series leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Traulsen G-Series krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Traulsen G-Series bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Traulsen G-Series kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Traulsen G-Series . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.