1. Important Safety W arnings 2 2. Control P anels 3 2.1 Front P anel 3 2.2 Battery Access Panel (Co ver Removed) 4 2.3 Rear Panel 5 3. Installation 6 3.1 UPS Location 6 3.2 Mounting Bracket Installation 6 3.3 Grounding Connection 6 3.4 UPS Input And Output Hard wire Connection 6 3.
2 SA VE THESE INSTR UCTIONS. This manual contains important instructions and warnings that should be follo wed during the installation and maintenance of all T ripp Lite SmartOnline 3-Phase 20kV A and 30kV A UPS Systems. UPS Location Warnings • Installyour UPS in acontrolled en vironment.
2. Control P anels 3 Note: F amiliarize yourself with the location and function of the features on your UPS system befor e installing and operating it. “ON” Button: 1. This buttonturns theUPS System's in verter ON. “OFF” Button: 2.
4 1 2 3 4 5 6 7 Individual models may vary slightly from diagram. 2.2 Battery Access P anel (Cover Removed) 2. Control P anels ( continued ) Internal Battery Packs: 1. Thesesupply backup runtime toconnected equipment. Eachpack consists oftwo strings (onepositiveand onenegativ e).
Individual models may vary slightly from diagram. 5 Manual Bypass Switch: 1. This dialis used toput the UPS in“BYP ASS” mode, whichmust be donebefore performing anymaintenance on theUPS withthe connected load supported.
6 Mov e your UPS over short distances using its wheels. Note: The wheels ar e not designed to pro vide long-term support for the UPS system after f inal installation.
7 WIRING CONNECTION Connectyour wiring to theinput and outputterminal blocks locatedon the rear panelof your UPS(see figurebelow). CA UTION! Qualified personnel should follo w all procedures prescribed by N.
8 Momentarilypress the “SELECT” buttononthe front panelto browsethrough differentpowerreadings onthe LCD Display . BYP ASS OUTPUT R: XXXV R: XXX.XV S: XXXV S: XXX.XV T: XXXV T: XXX.XV (Bypass&Output Vo ltage) OUTPUT LO AD R: XXX% XXX.
9 Condition LCD Display Message Overload Shutdown ONBYP ASS O VERLO AD 150% SHUTDO WN... VERSION: XXXXXXX UPS Output Short Circuit ONBYP ASS SHOR T CIRCUIT! SHUTDO WN... VERSION: XXXXXXX Overtemperature ONBYP ASS HIGHTEMP! SHUTDO WN... VERSION: XXXXXXX DCBUS Overv oltage ON BYP ASS DCBUS O.
3 V + - 10 Thisfemale DB9 port connectsyour UPS viaan RS-232 cableto a workstationor serverequipped withTrippLite software.Theport uses RS-232 communicationsto report UPS statusand powerconditions.
X 1 2 3 4 5 6 X 11 Thisoptional feature is onlyfor those applicationswhich require connectionto a facility'sEmergencyPowerOff(EPO) circuit.Whenthe UPS System isconnected to this circuit,it enables emergenc y shutdownof theoutput.
UPS System Batter y Back Co nnec to r White wir e Blue wire UPS System Batter y Back Co nnec to r Fu se Block Bracket Red wire (+ ) Black wire (–) 12 Qualifiedservice personnelshould familiarizethemselves withthe battery packwiring diagram prior toadding or replacingbatteries.
13 Placethe UPS System inBypass Mode orcompletely turn itoff, dependingon preference. (See section5.4, Operation of Manual Bypass Switch , or4.2, T urning the UPS Off .) 1 Remov e battery accesspanel, located on theFRONTof theUPS system.
14 Slide the battery string with the RED cable into an empty slot within the battery compartment as sho wn. Make sure that the string is oriented as shown in the diagram 7A . Note: If the auxiliary battery connector is in the way , remove its mounting screw and position the cable to allow adequate room to add the battery strings 7B .
240 15 D ANGER! B A TTER Y CARTRIDGE FUSES MUST BE INSERTED LAST DUE TO THE DANGER OF PO TENTIAL ARCING OF CONNECTORS. FUSE REPLA CEMENT The fuses protect against shor t circuit damage . If a heavy overload or shor t cir cuit is encountered, a fuse will blow .
16 Y our SmartOnline 3-Phase UPSSystem is cov ered by thelimited warranty describedbelow . Extended warranty(2-, 3- and4-year) and start-upservice programsare av ailable. Formore information, callTrippLiteCustomer Service at(773) 869-1234.
17 Model: SU20K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz V oltage Correction Range 88-144/166-250V AC Input Cur rent (Per Phase, On-Line) 60A Inr ush Cur rent <300A Power Factor (Full Load) >0.
200901138 93-2624 18 Model: SU30K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz V oltage Correction Range 88-144/166-250V AC Input Cur rent (Per Phase, On-Line) 90A Inr ush Cur rent <300A Power Factor (Full Load) >0.
Een belangrijk punt na aankoop van elk apparaat Tripp Lite 120/208V (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Tripp Lite 120/208V heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Tripp Lite 120/208V vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Tripp Lite 120/208V leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Tripp Lite 120/208V krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Tripp Lite 120/208V bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Tripp Lite 120/208V kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Tripp Lite 120/208V . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.