2 Impor tant Safety W arnings SA VE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of all T ripp Lite SmartOnline 3-Phase UPS Systems and their batteries.
3 Contr ol P anel There are two separate UPS system modules: a power module and a battery module. Familiarize yourself with the location and function of the features on each module before installing and operating your UPS system. The power module is the only module which includes front panel features.
4 Rear P anels 17 18 Battery Module Rear Panel P ower Module Rear P anel 13 7 6 8 15 4 12 2 14 9 10 5 1 11 3 16 REFER TO USER'S MANU AL FOR TORQUING SPECIFICA TIONS, USE COPPER CONDUCTORS ONL Y .
5 Rear P anels (continued) 10. “Battery S tart” Switch: This momentary rocker switch allows you to “cold-start” your UPS and use it as a stand-alone power source when utility-supplied AC power is not present. The switch enables the UPS’ s DC/AC Inverter .
6 Installation (continued) Operational Mode Selection (DIP Switch #4) The "On-Line" Mode provides on-line operation with zero transfer time. The "Economy" Mode provides line-intera.
7 Installation (continued) EXTERNAL B A TTER Y MODULE CONNECTION (required) Connect the battery module to the power module. Consult the owner's man- ual that came with your battery module. Fully insert the connector on the end of the battery module's cable into the connector on the rear panel of the power module.
8 Operation (Normal Conditions) TURNING THE UPS ON • Make sure the UPS is properly installed (see Installation section) and the Manual Bypass Key is set to NORMAL.
9 Operation (Normal Conditions) (continued) SELF-TESTING When you turn the UPS ON, it will perform a brief (about 25 second) self-test. See figure below for display sequence.* *Note: If starting from battery , the BA TTER Y LED will be lit and the I/P and BYP ASS LEDs will not.
ON INVERTER LOAD = XXX% X.XXKW ON INVERTER IN R = XXXV XX.XHz ON INVERTER OUT = XXXV XX.XHz ON INVERTER BATT = XXXV XXX% PRESS SELECT KEY PRESS SELECT KEY PRESS SELECT KEY PRESS SELECT KEY ON INVERTER IN S = XXXV T=XXXV PRESS SELECT KEY ON BATTERY LOAD = XXX% X.
11 Operation (Special Conditions) (continued) OPERA TION ON O VERLO AD When the UPS detects an output overload, it will commence a countdown (the length of time depending on the severity of the overload). If the UPS is still overloaded at the end of the countdown, the UPS will automatically shut down and go into Bypass Mode.
12 OPERA TION OF MANU AL BYP ASS SWITCH T urn this switch to “BYP ASS” before performing any maintenance on the UPS with the connected load supported. Connected equipmen t will receive filtered AC mains power, but will not receive battery power in the event of a blackout.
13 Comm unications (continued) AS-400 INTERF A CE This female DB9 port connects your UPS to an IBM AS-400 computer via the included AS-400 cable. The port uses AS-400 communications to report UPS status. It can be used to allow an AS-400 to automatically save open files and shut down its operat- ing system during a blackout.
14 Comm unications (continued) REMO TE EMERGENCY PO WER OFF (EPO) This optional feature is only for those applications which require connection to a facility's Emergency Power Of f (EPO)circuit. When the power module is connected to this circuit, it enables emergency shutdown of the output.
15 The specifications listed below are for T ripp Lite model SU10K3/1X which includes two modules: a power module and a battery mod - ule. The two modules are also sold separately with their own individual model numbers: power module (individual model #: SU10K3/1INTPM) and battery module (individual model #: BP240V10R T3U).
1111 W . 35th Street, Chicago, IL 60609 USA 773.869.1234 (USA) • 773.869.1212 (International) www .tripplite.com 2009XXXXX 93-2228_EN.
Een belangrijk punt na aankoop van elk apparaat Tripp Lite 220/230/240V AC / 12W (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Tripp Lite 220/230/240V AC / 12W heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Tripp Lite 220/230/240V AC / 12W vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Tripp Lite 220/230/240V AC / 12W leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Tripp Lite 220/230/240V AC / 12W krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Tripp Lite 220/230/240V AC / 12W bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Tripp Lite 220/230/240V AC / 12W kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Tripp Lite 220/230/240V AC / 12W . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.