• Selection data • Installation • Piping • W ater treatment This manual must only be used by a qualified heating installer/service technician. Before installing, read all instructions, including this manual, the Ultra Boiler Manual and all applicable Supplements.
Part number 550-101-232/0703 2 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Contents Hazard definitions ................................................................................................................
Part number 550-101-232/0703 3 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Part number 550-101-232/0703 4 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Ratings and engineering data Figure 1 Ratings and engineering data (see page 5 for notes).
Part number 550-101-232/0703 5 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems For simplicity , the table on page 4 lists only sy stems using m ultiples of the same Ultra b oiler module. Any combination of Ultra boilers can be installed as a multiple boiler system.
Part number 550-101-232/0703 6 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems 1 . Boiler supply and return tappings are both 1" NPT . Connect to headers with 1” pipe for Ultra-80 and Ultra-105; 1¼" pipe for Ultra-155 and Ultra-230.
Part number 550-101-232/0703 7 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems 06-24-03 CONFIDENTIAL REVIEW & COMMENT ONL Y Placement and mounting information Placement, general 1 . Locate multiple boilers in boiler room according to: • Figure 3 (side-to-side), or • Figure 4 (back-to-back).
Part number 550-101-232/0703 8 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems 06-24-03 CONFIDENTIAL REVIEW & COMMENT ONL Y Easy -Fit ® P iping Figure 6 Single-sid.
Part number 550-101-232/0703 9 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems 06-24-03 CONFIDENTIAL REVIEW & COMMENT ONL Y Figure 8 Piping schematic — Typical pi.
Part number 550-101-232/0703 10 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Figure 9 Typical piping for multiple Ultra boilers, using Weil-McLain Easy-Fit ® Manifo.
Part number 550-101-232/0703 11 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Figure 10 Typical piping for multiple Ultra boilers, Weil-McLain Easy-Fit ® Manifolds, and indirect water heaters 1 Flow/check valve (each boiler) 2 Isolation valves (when used) 3 Caps 4 Easy-Fit ® Manifold (supply), sized per Fig.
Part number 550-101-232/0703 12 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Figure 11 Typical piping for multiple Ultra boilers, using Weil-McLain Easy-Fit ® Manifolds and heat exchanger Use isolation heat exchanger for: 1.
Part number 550-101-232/0703 13 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Figure 12 Manifolding combution air piping Combustion air & vent piping installation Vent piping 1.
Part number 550-101-232/0703 14 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Figure 13 Connecting gas supply piping Gas piping Connecting gas supply piping 1 . Remove jacket front panel and refer to Figure 13 to pipe gas to boiler .
Part number 550-101-232/0703 15 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Figure 14 Common gas piping, with manifolded gas header Common gas piping installation 4 . Size gas piping from meter outlet to entrance of gas header in acc ordance with T ables 1 and 2 belo w .
Part number 550-101-232/0703 16 GA S - FIRED WA TER BOILER — Installation Manual — Multiple-boiler S ystems Additional instructions Air for boiler room ventilation 1. Follow instructions in Ultra Boiler Manual to ensure the boiler room provides sufficient air infiltration.
Een belangrijk punt na aankoop van elk apparaat Weil-McLain Boiler (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Weil-McLain Boiler heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Weil-McLain Boiler vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Weil-McLain Boiler leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Weil-McLain Boiler krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Weil-McLain Boiler bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Weil-McLain Boiler kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Weil-McLain Boiler . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.