6104BAFG R05 Page 1 RESIDENTIAL BURNERS Potential for Fire, Smoke and Asphyxiation Hazards T o the Homeowner or Equipment Owner: Please read and carefully follow all instructions provided in this manual regarding your responsibilities in caring for your heating equipment.
Page 2 6104BAFG R0 6 T able of Contents Hazard Def nitions and Owner ’ s Information ........................................................................................ 3 Information T o Be Used Only By Qualif ed Service T echnicians General Information .
6104BAFG R0 6 Page 3 NO TICE This manual contains information that applies to both AF and AFG burners. These burners may appear to be basically identical, but there are differences in design and performance.
Page 4 6104BAFG R0 6 Do NOT Alter the Original Burner Design Maintain the design to its original con fi guration. Only use parts speci fi ed for AF or AFG Burners Do NOT remove the air guide from the AFG chassis. Do NOT use ‘M’ Series air tube combinations on AF Burn- ers.
6104BAFG R0 6 Page 5 General Speci fi cations Please read and understand the manual supplied with this equipment. This equipment must be installed, ad- justed and put into operation only by a quali fi ed individu- al or service agency that is: Licensed or certi fi ed to install and provide tech- nical service to oil heating systems.
Page 6 6104BAFG R0 6 Carefully inspect the chimney or exhaust vent system. Make sure it is properly sized and in good work- ing condition. Follow the instructions supplied by the appliance manufacturer .
6104BAFG R0 6 Page 7 Inspect/Prepar e Installation Site Combustion air supply The burner cannot properly burn the fuel if it is not supplied with a reliable combustion air source. Follow the guidelines in the latest editions of the NFP A 31 and CSA-B139 regarding providing ad- equate air for combustion and ventilation.
Page 8 6104BAFG R0 6 T able 4. AFG Reduced Firing Rates (with LFRB) Burner head type Low Firing Rate Baf fl e installed F0 up to 0.65 gph F3 or L1 up to 0.85 gph F4 or F6 up to 0.90 gph V1 up to 1.00 gph Prepar e the Bur ner Low Firing Rate Baff e The AFG Low Firing Rate Baf fl e (LFRB) reduces the air fl ow and pressure.
6104BAFG R0 6 Page 9 If the nozzle is already installed, remove the noz- zle line assembly to verify that the nozzle size and spray pattern are correct for the application (per ap- pliance manufacturer ’s information). V erify that the electrode tip settings comply with Figure 3.
Page 10 6104BAFG R0 6 1-3/8” 1-1/8” Check/Adjust ‘Z’ Dimension - ‘F’ heads 1. The important ‘Z’ dimension is the distance from the face of the nozzle to the fl at face of the head (or heat shield, if applicable). This dis- tance for F heads is 1- ⅛ ” (1- ⅜ ” if the air tube has a heat shield).
6104BAFG R0 6 Page 1 1 Figure 5. Check/Adjust ‘Z’ Dimension - L1 & L2 Heads Figure 6. Check/Adjust ‘Z’ Dimension - V1 Heads V1 Adjusting Plate Setting AFG with V1 Head Burner Firing Rates 0 0.75-1.00 1 1.00-1.50 2 1.50-1.75 3 1.75-2.00 4 2.
Page 12 6104BAFG R0 6 Installing the Oil T ank and Supply System Fuel supply level with or above burner – SK8745 Figure 7. – Mounting Burner in Appliance T ilt down 2 o If space between burner air tube and opening exceeds 1/2 inch, pack burner opening with ce- ramic fiber refractory .
6104BAFG R0 6 Page 13 Disconnect electrical power before installing or servicing the burner . Provide ground wiring to the burner , metal con- trol enclosures and accessories. (This may also be required to aid proper control system opera- tion.) Perform all wiring in compliance with the Na- tional Electrical Code ANSI/NFP A 70 (Canada CSA C22.
Page 14 6104BAFG R0 6 GeniSys Model 7505 Control W iring Display Module: For programming and diagnostics Alarm Module: For adding isolated low voltage alarm contacts to the base control. See Alarm Module Instructions for speci fi cations. Figure 10. The control can malfunction if it gets wet, leading to accumulation of oil or explosive oil vapors.
6104BAFG R0 6 Page 15 6. Run : The fl ame is sustained until the call for heat is satis fi ed. The burner is then sent to Motor-Off Delay , if applicable, or it is shut down and sent to Standby .
Page 16 6104BAFG R05 Figure 1 1a. – Interrupted ignition, valve-on delay only (no motor-off delay) Figure 1 1b. – Interrupted ignition, valve-on delay and motor-off delay SAFETY AND OPERA TING LIM.
6104BAFG R0 Page 17 61351 7. RECYCLE. If the fl ame is lost while the burner is fi ring, the control shuts down the burner , enters a 60 second recycle delay , and then repeats the above ignition sequence. If fl ame is lost three times in a row , the control locks out to prevent cycling with repetitious fl ame loss due to poor combustion.
Page 18 6104BAFG R0 Make connections to the control’s terminals as shown in Figures 1 1a and 11 b . Refer to the label on the un- derside of the control for wiring details. Note: Motor-off delay on a 7505P will be disabled if the safety and operating limits as shown in Figures 1 1a and 1 1b interrupt power to the control terminal L1.
6104BAFG R0 Page 19 Startup / Checkout If the burner or control fails any of the following tests, recheck control wiring. If the burner or control still fails any tests, replace the control. Check Safety Features Safe Start Check Place a jumper across the cad cell terminals.
Page 20 6104BAFG R0 Step 4: Recheck smoke level. It should be Zero. This procedure provides a margin of reserve air to accommodate variable conditions.
6104BAFG R0 Page 21 Figure 12. Blower wheel assembly SK9190 Use a Feeler Gauge to set the gap to; AF = 0.125 +1/64 inch AFG = 0.030 +1/64 inch Replace the blower wheel: T urn off all power to the burner before servic- ing. Disconnect the burner motor wires.
21 23 24 6.
6104BAFG R0 6 Page 23 # Part No. Description 1 Burner Housing Assembly 2 Specify* Air Band - Specify # of slots 3 Specify* Air Shutter - Specify # of slots 4 21807U V alve Cordset Not Shown 21887U PD .
Page 24 6104BAFG R0 6 Limited WARRANTY For Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its Beckett burners from Beckett.
Een belangrijk punt na aankoop van elk apparaat Weil-McLain UO-4 CV (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Weil-McLain UO-4 CV heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Weil-McLain UO-4 CV vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Weil-McLain UO-4 CV leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Weil-McLain UO-4 CV krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Weil-McLain UO-4 CV bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Weil-McLain UO-4 CV kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Weil-McLain UO-4 CV . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.