Gebruiksaanwijzing /service van het product IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 van de fabrikant Western Telematic
Ga naar pagina of 58
WTI Part No.: 13614 Rev . A IPS-800/1600-D20 Series Internet Power Switches Models: IPS-800-D20 IPS-800E-D20 IPS-1600-D20 IPS-1600E-D20 User ’s Guide.
.
i Warnings and Cautions: INST ALL ATION INSTRUCTIONS SECURE RACKING If Secure Racked units are installed in a closed or multi-unit rack assembly , they may require further evaluation by Certification Agencies. The following items must be considered. 1.
ii IPS-800/1600-D20 Series - User ’ s Guide FCC Part 15 R egulation This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
i T able of Contents 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 2. Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii IPS-800/1600-D20 Series - User ’ s Guide Appendices: A. Interface Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-1 A.1. Serial COM / RS232 Port Interface . . . . . . . . . . . . .
1-1 1. Introduction Electronic equipment sometimes "locks-up," requiring a service call just to flip the power switch to perform a simple reboot.
1-2 IPS-800/1600-D20 Series - User ’ s Guide IPS-800-D20, IPS -800E-D20, IPS -1600-D20 and IPS-1600E-D20 Units This User ’ s Guide discusses the IPS-800-D20, IPS-800E-D20, IPS-1600-D20 and IPS-1600E-D20 Internet Power Switches. Throughout this User’ s Guide, all four units are referred to as the "IPS".
2-1 2. Unit Description As shown in Figure 2.1 and Figure 2.2, the IPS back panel includes connectors, LEDs and manual controls described below: BUS A B A-1 A-2 A-3 A-4 B-5 B-6 B-7 B-8 MAIN POWER COM 10BaseT ACT RDY ON DEF 1 2 3 4 5 6 7 8 9 Figur e 2.
2-2 IPS-800/1600-D20 Series - User ’ s Guide ➂ Bus "A" Switched Outlets and Indicator Lights: AC Outlets that can be switched On, Off or rebooted in response to user commands. • IPS-800-D20: Four (4) NEMA 5-15R Outlets with indicator lights.
3-1 3. Quick Start This Quick Start Guide describes a simplified installation procedure for the IPS-800-D20, IPS-800E-D20, IPS-1600-D20 or IPS-1600E-D20 hardware, which will allow you to communicate with the unit in order to demonstrate basic features and check for proper operation.
3-2 IPS-800/1600-D20 Series - User ’ s Guide 3.1.2. Connect your PC to the IPS The IPS can either be controlled by a local PC, that communicates with the unit via cable, controlled via external modem, or controlled via TCP/IP network.
3-3 Quick Start Figur e 3.1: Plug Status Screen - W eb Br owser Interface (Model IPS-800-D20 Shown) Internet Power Switch v1.41h Site ID: (undefined) Plug | Name | Password | Status | Boot/Seq. Delay | Default | -----+------------------+-------------+--------+-----------------+---------+ 1 | (undefined) | (undefined) | ON | 0.
3-4 IPS-800/1600-D20 Series - User ’ s Guide iii. V ia Modem: Use your communications program to dial the number for the phone line which is connected to your external modem.
4-1 4. Installation This Section provides further details regarding installation of the IPS unit. 4.1. Power Supply Connection Connect the IPS unit to an appropriate power supply . Note that the IPS’ s Main Power switch must be "On" in order for the unit to operate.
4-2 IPS-800/1600-D20 Series - User ’ s Guide 4. Connect the power cables to the power inlets. Check to make sure that both cables are firmly seated in the power inlet connectors. 5. Align the power cables with the two notches in the top of the slider plate, and then move the slider plate forward until both cables are held firmly in place.
4-3 Installation 4.3. Serial COM / RS232 Port Connection The COM Port is a male, RS232C DB9 connector , wired in a DTE configuration. In the default state, the COM port is configured for 9600 bps, no parity , 8 data bits, 1 stop bit. The COM Port can be connected to either an external modem or a local PC, but not both items at the same time.
4-4 IPS-800/1600-D20 Series - User ’ s Guide.
5-1 5. Configuration 5.1. System Mode and User Mode In order to restrict access to sensitive command functions, the IPS features two operating modes; System Mode and User Mode. • System Mode: Allows access to all configuration menus, switching functions and status screens.
5-2 IPS-800/1600-D20 Series - User ’ s Guide 5.2. Communicating with the IPS In order to configure the unit or invoke command functions, you must first connect to the IPS and access command mode. As discussed in Section 3, the IPS offers two separate command interfaces: the W eb Browser Interface, and the T ext Interface.
5-3 Confi guration 3. Password Prompt: The IPS will display a prompt, which asks for your name and password. a) User Name: If you have not previously defined a user name, then this field should be left blank. A user name is only required when one has been defined via the General Parameters menu.
5-4 IPS-800/1600-D20 Series - User ’ s Guide c) Via Network: The IPS includes a default IP address (192.168.168.168), which allows you to contact the unit from any network node on the same subnet.
5-5 Confi guration 5.3. Configuration Menus As described in the sections that follow , configuration parameters for the IPS can be selected via the W eb Browser Interface or T ext Interface.
5-6 IPS-800/1600-D20 Series - User ’ s Guide 5.3.1. The General Parameters Menus The General Parameters Menus allow you to select parameters such as the System Password, User Name, Site I.
5-7 Confi guration • User Name: (Optional) The User Name allows you to set up an additional layer of security for web access to command mode by requiring that users correctly enter a name in addition to a password. Note that the User Name is only required when the unit is accessed via the W eb Browser Interface.
5-8 IPS-800/1600-D20 Series - User ’ s Guide • Inactivity Timeout: Determines how long the IPS will wait for additional commands during periods of inactivity . When the T imeout Period elapses, the user will be disconnected from the IPS command mode.
5-9 Confi guration 5.3.2. The Serial Parameters Menu The Serial Parameters Menus are used to configure the IPS's serial COM Port, and allow you to select parameters such as the Baud Rate, Parity and Modem Initialization String.
5-10 IPS-800/1600-D20 Series - User ’ s Guide As shown in Figure 5.5 and Figure 5.6, the Serial Parameters Menus allow you to define the following parameters: • Baud Rate: Baud Rate for the IPS COM Port.
5-11 Confi guration 5.3.3. Plug Parameters Menus The Plug Parameters Menus are used to define Plug Names, Plug Passwords, boot/sequence delay times and Power Up Default values for each of the IPS’ s Switched AC Outlets.
5-12 IPS-800/1600-D20 Series - User ’ s Guide The Plug Parameters Menu allows you to define the following parameters: • Plug Name: (Up to 16 Characters, Default = undefined.
5-13 Confi guration 5.3.3.2. The Boot / Sequence Delay Period. The Boot / Sequence Delay value will be applied differently for Reboot operations as opposed to simple On/Off operations as described below: 1. Reboot Cycles: a) Single Plug: The Boot/Seq.
5-14 IPS-800/1600-D20 Series - User ’ s Guide Figur e 5.9: Network Parameters Menu - W eb Browser Interface NETWORK PARAMETERS: 1. IP Address: 192.168.168.168 2. Subnet Mask: 255.255.255.0 3. Gateway Address: (undefined) 4. Send MSS: 536 5. IP Security MAC Address: 00-09-9b-00-a0-32 Enter Selection, Press <ESC> to Exit .
5-15 Confi guration 5.3.4. Network Parameters Menus The Network Parameters Menus are used to select the IP Address and other network parameters. • W eb Browser Interface: Click the "Setup" button to access the Setup Menus, and then click the "Network Parameters" button.
5-16 IPS-800/1600-D20 Series - User ’ s Guide 5.3.4.1. IP Security Feature The IP Security feature can be used to restrict unauthorized IP addresses from establishing a connection with the IPS. In the default state, the IPS accepts incoming IP connections from all hosts.
5-17 Confi guration Example 1: Deny access to all hosts except 192.1.1.5: Security Mask #1: 255.255.255.255 Mask #1 Action: Deny Security Mask #2: 192.1.1.5 Mask #2 Action: Permit Since 255 is a wild card, Mask #1 blocks all IP Addresses. Mask #2 then specifically grants access to 192.
5-18 IPS-800/1600-D20 Series - User ’ s Guide 5.3.5. The T elnet Parameters Menus The T elnet Parameters Menus are used to enable/disable T elnet access to the IPS command mode and select the TCP port for T elnet connections.
5-19 Confi guration Figur e 5.14: W eb Server Parameters Menu - W eb Browser Interface WEB SERVER: 1. Service: On 2. Server Port #: 80 Enter Selection, Press <ESC> to Exit .
5-20 IPS-800/1600-D20 Series - User ’ s Guide 5.4. Save Configuration Parameters The IPS offers two methods for saving parameters; Saving to Memory , and Saving to an ASCII File. Saving parameters to memory ensures that your user-defined configuration will remain intact if power to the IPS is temporarily interrupted.
6-1 6. Operation As discussed in Section 5, the IPS offers two separate command interfaces; the W eb Browser Interface and the T ext Interface. Note that Both interfaces offer essentially the same com.
6-2 IPS-800/1600-D20 Series - User ’ s Guide 3. Switching Plugs On: Click the "On" radio button next to the desired plug(s), then click "Apply". T o switch all Plugs On, click the "On" radio button in the "All Plugs" row , then Click "Apply .
6-3 Operation 6.2. Operation via the T ext Interface When using the T ext Interface, all switching functions are performed by invoking simple, ASCII commands. ASCII commands are also used to display status screens and to log out of command mode. The T ext Interface includes a Help Menu, which summarizes all available IPS commands.
6-4 IPS-800/1600-D20 Series - User ’ s Guide 6.2.2. Switching and Reboot Commands - T ext Interface These commands can be used to switch or reboot the IPS’ s switched plugs, and can also be used to set plugs to the user-defined Power -Up Default values.
6-5 Operation T o Switch Plugs, or initiate a Boot Cycle, proceed as follows: 1. Switch Plug(s) On: T o power-on a plug, type /ON n and press [Enter]. Where " n " is the number or name of the desired plug. For example: /ON 1 or /ON ROUTER 2.
6-6 IPS-800/1600-D20 Series - User ’ s Guide 6.2.3. Applying Commands to Several Plugs - T ext Interface As described below , switching and reboot commands can be applied to only one Switched AC Outlet, or to an assortment of outlets.
6-7 Operation 6.4. The Automated Mode The Automated Mode allows the IPS to execute switching and reboot commands, without displaying menus or generating response messages. Automated Mode is designed to allow the IPS to be controlled by a device which can generate commands to control power switching functions without human intervention.
6-8 IPS-800/1600-D20 Series - User ’ s Guide 3. "Sure?" Pr ompt Suppressed: All commands are executed without prompting for user confirmation. 4. Error Messages Suppressed: If the [Enter] key is pressed without entering a command, the IPS will not respond with the "Invalid Command" message.
7-1 7. Saving and Restoring Configuration Parameters After the IPS has been properly configured, parameters can be downloaded and saved as an ASCII text file on your local or remote PC.
7-2 IPS-800/1600-D20 Series - User ’ s Guide 7.2. Restoring Saved P arameters This Section describes the procedure for using your communications program to send saved parameters to the IPS. Note: Parameters saved to an ASCII file can only be restored via the T ext Interface.
8-1 8. Upgrading the IPS Firmware When new , improved versions of the IPS firmware become available, the "Upgrade Firmware" function can be used to update the unit. Updates can be installed via the Console Port or Network Port. Notes: • The upgrade procedure can only be performed via the T ext Interface.
8-2 IPS-800/1600-D20 Series - User ’ s Guide 4. Set your communication program for ASCII Mode, then use the program’ s “Send File” function to transfer the upgrade file to the IPS. Select ASCII format, then specify the filename and directory location where the firmware upgrade file resides.
Apx-1 A . Interface Description A.1. Serial COM / RS232 Port Interface Figur e A.1: COM Port Interface.
Apx-2 IPS-800/1600-D20 Series - User ’ s Guide B. Specifications Power Input / Output: Models IPS-800-D20 & IPS-1600-D20 (120 V AC) • AC Input: T wo Separate Circuits; 20 Amps Max. per Circuit ▪ V oltage: 100 - 120 V AC 50/60 Hz ▪ Connectors: T wo (2) IEC320-C20 Inlets • AC Outputs: ▪ Connectors: NEMA 5-15R Outlets.
Apx-3 Appendices C. Customer Service Customer Service hours are from 8:00 AM to 5:00 PM, PST/PDT , Monday through Friday . When calling, please be prepared to give the name and model of the unit, its serial number and a description of its symptoms.
Apx-4 IPS-800/1600-D20 Series - User ’ s Guide T rademark and Copyright Information WTI and W estern T elematic are trademarks of W estern T elematic Incorporated. All other product names mentioned in this publication are trademarks of their respective companies.
Index -1 Inde x # 100Base-T 4-3 10Base-T 4-3 A Activity Indicator 2-2 Automated Mode 5-8, 6-7 to 6-8 B Baud Rate 5-10 Boot/Sequence Delay 5-12 to 5-13 Bus A 2-1 Bus B 2-1 C Cable Keepers 4-1 Circuit B.
IPS-800/1600-D20 Series - User ’ s Guide Index -2 O ON Indicator 2-2 Operation 6-1 to 6-8 W eb Browser Interface 6-1 to 6-2 P Parity 5-10 Passwords 5-4, 6-7 Plug 5-1, 5-12 System 5-1, 5-6 User 5-1, .
.
5 Sterling • Irvine • California 92618 (949) 586-9950 • Toll Free: 1-800-854-7226 Fax: (949) 583-9514 • http://www.wti.com.
Een belangrijk punt na aankoop van elk apparaat Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Western Telematic IPS-800-D20, IPS-800E-D20, IPS-1600-D20, IPS-1600E-D20 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.