About Xantrex Xantrex T echnol ogy Inc. is a world-leadin g supplier of ad va nced power electronics and controls with products from 50 watt mobile units to one MW utility-scale systems for wind, solar , batteries, fuel cells , microt urbines, and backup power applications in both gri d-connected and stand-alon e system s.
973-0031-01-01 Rev A iii About This Guide Purpose The purpose of this Owner ’ s Guide is to provide explanations and procedures for installing, op erating, maintaining, and troubleshooting the Sin e W ave Plus Long AC Conduit Box.
About T his Guide iv 973-0031-01-01 Rev A Conventions Used The following conventio ns are used in this guide. Abbreviations and Acronyms Related Information Y ou can find more information about Xa ntr ex T echnology Inc. as well as its products and services at www .
Safety 973-0031-01-01 Rev A v Important Safety Instructions 1. Before installing the Lo ng AC Conduit Bo x, read all in structions and cautionary markings on the Long AC Condu it Box and all appropriate sections of this guide. 2. Do not expo se the Long AC Conduit Box to rain, snow , or spray .
Safety vi 973-0031-01-01 Rev A Explosive gas precautions 1. W orkin g in the vicinity of lead-ac id ba tteries is dangerous. Batteries generate explosive gases during normal operation. Therefore, you must read this guide and follow the instructions exactly before installing th e Long AC Conduit Box.
973-0031-01-01 Rev A vii Important Safety Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - v 1 Introduction Introduction - - - - - - - - - - - - - -.
Contents viii 973-0031-01-01 Rev A 3 Operation The AC Bypass Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 Operating the AC Bypass Sw.
973-0031-01-01 Rev A ix Figure 1-1 The Sine Wave Plus ACCB-L Basic- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Figure 1-2 The Sine Wave Plus Long AC Condui t Box (ACCB.
x.
973-0031-01-01 Rev A xi Table 1-1 Operational and Environmental Sp ecifications for the ACCB-L, ACCB-L-L1, and ACCB-L-L2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -.
xii.
1 Intr oduction Chapter 1, “Introduction” provide s a basic introduction to the design and purpose of the Sine W ave Plus Long AC Conduit Box (ACCB-L).
Introduction 1–2 973-0031-01-01 Rev A Introduction The Sine W ave Plus Long AC Conduit Box (ACCB-L and ACCB-L-L1) connects to the AC side of a Sine W a ve Plus inve rter and accepts AC conduit runs.
Introduction 973-0031-01-01 Rev A 1–3 Figure 1-2 T he Sine W ave Plus Long A C Cond uit Box (ACCB-L-L1, and ACCB-L-L2) ACCB-L-L1 ACCB-L-L2 ACCB-L-L2 is created by installing the ACCB-L2-PCK to the ACCB-L-L1.
Introduction 1–4 973-0031-01-01 Rev A Specifications The following table contains the specifications for the ACCB-L, the ACCB-L-L1, and the ACCB-L-L2. The ACCB-L-L2 is not available pre-built from the factory , but is created by field-installing an ACCB-L2-PCK into a ACCB-L-L1 model.
Specifications 973-0031-01-01 Rev A 1–5 Ratings 120/240 V ac/60 hz., split- phase, 60 Amp pass-thru 120/240 V ac/60 hz., split- phase, 60 Amp pas s-thru 120/240 V ac/60 hz., split- phase, 60 Amp pass-thru Regulatory Certified by CSA to UL 1741- 2001 (First Edition) and CSA C22.
Introduction 1–6 973-0031-01-01 Rev A A C Bypass Switch Assembly The AC bypass switch assembly in th e ACCB-L-L1 is designed for 120 V ac applications and comes with two 60-a mp circuit breakers (one SPST and one DPST). The breaker pair is equipped with a lockout rocker that allows only one breaker to be ON at any given tim e.
Block off Plates 973-0031-01-01 Rev A 1–7 Blockoff Plates Upper and Lower Blockoff Plates are includ ed to enclose the open portions of the Long AC Conduit Box chassis. In the even t that an inverter is removed for service, the Blockoff Plates secure the enclosure to prevent accidental contact with any AC power within the Long AC Conduit Box.
1–8.
2 Installation Chapter 2, “Installation” provides in stallation and wiring instructions for the Sine W ave Plus Long AC Conduit Box. The following topics are covered in this chapter .
Installation 2–2 973-0031-01-01 Rev A Preparing for the Installation Code Compliance Governing installatio n codes vary depending on th e location and typ e of installation.
Configuration Planning 973-0031-01-01 Rev A 2–3 Configuration Planning W iring scenarios will depe nd upon the configuratio n of the overall system (i.e., Off Grid or On Grid , and output requirements). Pre-installation and mounting instructions apply to all configurations.
Installation 2–4 973-0031-01-01 Rev A Pre-Installation Location Be sure to allow sufficient space for the Long AC Conduit Box to be mounted directly adjacent to the inverter ’ s AC side . Be sure to leave room for expansion if necessary . Also consider the additional weight and ven tilation space requirements of the Long AC Conduit Box .
Pre-Installation 973-0031-01-01 Rev A 2–5 V entilation Requirements Minimum clearance for ventilation around the Long AC Conduit Box must be at least 12 inches (305 mm) at the top, the ends, and in front.
Installation 2–6 973-0031-01-01 Rev A Removing and Replacing the Cover Remove the top cover to install additional breakers and to connect the AC wiring of the Long AC Conduit Box to the Sine W ave Plus Inverter .
Pre-Installation 973-0031-01-01 Rev A 2–7 Installing or Removing the Blockoff Plates The unit is shippe d with both upper and lower blockof f plates installed. If yo u are installing a single-inverter system, remove the upper blockof f plate only . If you are installing a dual-inverter system, then remove the lower blockoff plat e also.
Installation 2–8 973-0031-01-01 Rev A Knockout Pr eparation Knockout preparatio n should be done before mou nting either the inverter or the Long AC Conduit Box. 1. Remove the appropriate knockouts from the AC side of the inverter for cabling from the Long AC Conduit Box terminal block to the inverter terminal block.
Pre-Installation 973-0031-01-01 Rev A 2–9 Figure 2-6 Knock outs Locations Top Front Cover 3/4" and 1" Dual-Knockouts (x6 ea ) Outside wall of ACCB-L Base Inside wall of ACCB-L (closest to .
Installation 2–10 973-0031-01-01 Rev A Installing Additional Break ers If additional AC circuit breakers are to be installed for specific AC loads or a generator disconnect, then install them per the manufacturer ’ s instructions on the DIN Rail in the space to the left of the factory-installed AC Bypass Breaker .
Mounting 973-0031-01-01 Rev A 2–11 Mounting The Long AC Conduit Box is de signed to mo unt directly to the AC side of a Sine W ave Plus inverter . However , the SW Plus inverter can weig h up to 136 pounds (62 kg). The ACCB-L weighs up to 27 lbs (12.
Installation 2–12 973-0031-01-01 Rev A 3. Lift the inverter and place the mountin g holes in the rail directly over the mounting hooks on the pane l and lower into place. 4. Install four ¼-20 phillips screws provid ed with the panel, into the mounting holes of the Long AC Cond uit Box, but do no t fully tighten.
Mounting 973-0031-01-01 Rev A 2–13 Mounting on Plywood T o mount the Long AC Conduit Box on plywood: 1. W ith the help of another person, lift the invert er and mount it into place. Secure it to the plywood with #10 wood screws (14 total - length to penetrate 1½ inches or more into the studs.
Installation 2–14 973-0031-01-01 Rev A W iring - General The ACCB-L comes with a ground bar only . The ACCB-L-L1 is pre-wired at the factory and ready for conn ection to one Sine W ave Plus Inverter/Charg er. The factory-installed wires are labeled to assist with the installation procedure.
Wiring - General 973-0031-01-01 Rev A 2–15 W ire Sizes and Disconnect Requirements The AC Input/Output T erminal block in the ACCB-L-L1 accept wires sized #2/0 to 14 A WG . The ground bar i n both models has nine holes and accepts #4 to 14 A WG wires.
Installation 2–16 973-0031-01-01 Rev A Figure 2-11 ACCB -L Approved Internal Components DIN Rail (part of chassis - all models) Note: The ACCB-L comes with the Ground bar only. Some other mechanical components can be pur- chased from Xantrex (if part numbers were given above) or from the local electrical distributor.
Wiring - General 973-0031-01-01 Rev A 2–17 Figure 2-12 ACCB -L-L1 Internal Components (F actory installed) DIN Rail (part of chassis - all models) AC Input/Output Terminals Ground Bar AC Bus Bar (L1.
Installation 2–18 973-0031-01-01 Rev A Figure 2-13 ACCB-L-L1 Internal Components with the Optional ACCB-L2-PKG Installed ACCB-L2-PCK - Field-installed AC Bypass Switch Assembly (for Inverter #2) (L2.
Wiring for Off-Grid Applications 973-0031-01-01 Rev A 2–19 W iring for Off-Grid Applications The following illustrations show the wi ring examples for six basic off-grid configurations using th e ACCB-L-L1 with a minimum number of breakers installed for clarity .
Installation 2–20 973-0031-01-01 Rev A The following illustration shows the comp lete wiring for the ACCB-L-L1 and SW Plus Inverter in an off-grid configurat ion. This ill ustration includes the use of field-installed circuit breakers in the AC CB-L-L1 for AC distri bution, instead of using a separate sub panel.
Wiring for Off-Grid Applications 973-0031-01-01 Rev A 2–21 Step-down Configurations (240 V ac to 120 V ac) The following illustration sh ows the complete wiring for the ACCB-L-L1, TX Autotransformer, and a SW Plus Inverter for a Step-down Configura tion to use a 240 V ac-Only Generator .
Installation 2–22 973-0031-01-01 Rev A The following illustration shows the co mplete wiring for the ACCB-L-L1, TX Autotransformer , and a SW Plus Inverter for a Step-down Configuration to use a 240 V ac-Only Generator . This co nfiguration uses the ACCB-L-L1 as the sub panel.
Wiring for Off-Grid Applications 973-0031-01-01 Rev A 2–23 Step-up Configuration (Deep W ell Pump) (120 V ac to 240 V ac) The following illustration sh ows the complete wiring for the ACCB-L-L1, TX Autotransformer , and a SW Plus Inverter for a Step -up Configuration to provide power for a 2 40 V ac Load.
Installation 2–24 973-0031-01-01 Rev A Dual Inverter Configurations (120 V ac and 240 V ac) The following illustration shows the co mplete wiring for the ACCB-L-L2 (ACCB-L-L1 with ACCB-L2-PCK installed) and dual SW Plus Inverters in an off-grid applicati on.
Wiring for On-Grid Applications 973-0031-01-01 Rev A 2–25 W iring for On-Grid Applications The following illustrations show the comple te wiring to the six basic on-grid configurations. Fo r other possible configura tions, consult a quali fied electrician or a Xantrex certified dealer (See www .
Installation 2–26 973-0031-01-01 Rev A The following illustration shows the comp lete wiring for the ACCB-L-L1 and SW Plus Inverter in an on-grid configura tion. This diagram includes the use of a generator disconnect br eaker and load breakers in the ACCB-L-L1.
Wiring for On-Grid Applications 973-0031-01-01 Rev A 2–27 Step-up Configurations (Utility Backup) (120 V ac to 240 V ac) The following illustration sh ows the complete wiring for the ACCB-L-L1, TX Autotransformer , and a SW Plus In verter for a Step-up Co nfiguration to provide power for a 240 V ac Load.
Installation 2–28 973-0031-01-01 Rev A Dual Inverter Configurations (120 V ac and 240 V ac) The following illustration shows the co mplete wiring for the ACCB-L-L2 (ACCB-L-L1 with ACCB-L2-PCKinstalled) an d dual SW Plus In verters in an on- grid application.
Additional Accessory Wiring 973-0031-01-01 Rev A 2–29 Additional Accessory W iring If you have any of the following accessori es connected (or to be connected) to your inverter , then you will also .
Installation 2–30 973-0031-01-01 Rev A Figure 2-25 Accessory Wiring for Dual -Inverter Configurations See "IMPORTANT" note in Figure 2-24. Inverter Stacking Cable - Series (ISC-S).
3 Oper ation Chapter 3, “Operation” describes th e dif ferent modes and operation of the AC Bypass Switch(es) on the ACCB-L-L1, or for the second AC Bypass Switch (ACCB-L-L2) if installed.
Operation 3–2 973-0031-01-01 Rev A The A C Bypass Switch During normal operation (Figure 3-2 on page 3–3), AC power passes from the single external AC source (generator or gr id) through the invert er to the AC loads. The inverter monitors the incoming po wer and uses this power to keep the batteries charged.
Operating the AC Bypass Switch 973-0031-01-01 Rev A 3–3 Normal Operation External AC power passes to the A C Bypa ss Switch through the inverter to power the load (Figure 3-2). In this configuration, power passes fro m the inverter , through the AC Bypas s Switch, to the connected lo ad.
Operation 3–4 973-0031-01-01 Rev A A C Input/Output Off No power to the load or in verter (Figure 3-4). In this configuration, powe r from both the external sources of AC and the inverter is removed from the loads. This allows th e inverter that is connected to the AC Bypass breaker to be remo ved for service.
973-0031-01-01 Rev A WA–1 W arranty and Return Information Wa r r a n t y What does this warranty cover? This Limited W arranty is provided by Xant rex T echnology , Inc. ("Xantrex") and covers defects in workmanshi p and materials in your Sine W ave Plus Lo ng AC Conduit Box.
W arranty and Return WA–2 973-0031-01-01 Rev A What does this warranty not cover? This Li mited W arranty does not c over normal wear and tear of the product or costs related to the removal, installat ion, or tr oubleshooting of the custom er's electrical systems.
W arranty and Return 973-0031-01-01 Rev A WA–3 Return Material Authorization P olicy Before returning a product direct ly to Xantrex y ou must obtai n a Return Material Authorization (RMA) n umber and the correct factory "Ship T o" address.
W arranty and Return WA–4 973-0031-01-01 Rev A Information About Y our System As soon as you open your Sine W ave Plus Long AC Condui t Box package, record the fo llowing information and be sure to keep your p roof of purchase. If you need to contact Custo mer Servi ce, please record the following details be fore calling.
A abbreviations and acronyms iv AC Bypass Switch Assembly 1–6 AC conduit box - Long (ACCB-L) introduction 1–2 specifications 1–4 AC disconnect breakers 1–2 AC load breakers 2–10 additional a.
Index IX–2 973-0031-01-01 Rev A T tools required for installation 2–2 V V entilation Requirements 2– 5 W warranty out of warranty service WA–3 terms and conditions WA–1 wiring additional acc.
.
Xantrex Technology Inc. 1 800 670 0707 Tel toll free NA 1 360 925 5097 Tel direct 1 800 994 7828 Fax toll free NA 1 360 925 5143 Fax direct customerservice@xantrex.
Een belangrijk punt na aankoop van elk apparaat Xantrex Technology ACCB-L-L1 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Xantrex Technology ACCB-L-L1 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Xantrex Technology ACCB-L-L1 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Xantrex Technology ACCB-L-L1 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Xantrex Technology ACCB-L-L1 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Xantrex Technology ACCB-L-L1 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Xantrex Technology ACCB-L-L1 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Xantrex Technology ACCB-L-L1 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.