Gebruiksaanwijzing /service van het product B3CH 048 and 060 van de fabrikant York
Ga naar pagina of 16
GENERAL YORK Model BCH units are single package heat pump s designed for outdoor installation on a roof top or a slab. Supplemental electric heaters are available as field-installed accessories. The units are manufactured under ISO 9002 Quality System Certification.
035-12984-001-A-0204 2 Unitary Products Group General ................................................................................ 1 Inspection ............................................................................ 1 Reference ..............
LIMIT ATIONS These units must be installed in accordance with national and local or municiple safety codes: Refer to T able 1 for Unit Application Data. If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and / or the customer's expense.
size and type. Dirty filters reduce the capacity of the unit and result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in T able 3. CONDENSA TE DRAIN Plumbing must conform to local codes. Use a sealing compound on male pipe threads.
035-12984-001-A-0204 Unitary Products Group 5 FIG . 3 - TYPICAL FIELD WIRING CONTROL WIRING POWER WIRING NOMINAL HEA TER SIZE KW VOL TAGE UNIT MODEL SIZE, NOMINAL TONS 45 MINIMUM SUPPL Y AIR CFM 7 10 .
heater accessory installation instruction for the heater electrical data. The minimum air flow limitations across these heaters are listed in T able 2. OPTIONAL ECONOMIZER RAIN HOOD The following procedure should be used when assembling an economizer rain hood onto a unit.
035-12984-001-A-0204 Unitary Products Group 7 FIG . 5 - ENTHALPY SET POINT ADJUSTMENT MODELS BCH 048 060 SUPPL Y AIR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd.,mm/in.) F AN MOTOR HP (Direct-Drive Units) F AN MOTOR HP (Belt-Drive Units) 305 x254 12 x 10 0.75 NA 305 x 254 12 x 10 NA 1.
035-12984-001-A-0204 8 Unitary Products Group FIGURE 6 - DIMENSIONS & CLEARANCES Front 610mm (24") Back 25mm (12") (Less Economizer) 914mm (36") (With Economizer) Left Side (Filter .
035-12984-001-A-0204 Unitary Products Group 9 DET AIL “B” UNIT WITH FIXED OUTDOOR AIR / BAROMETRIC RELIEF RAINHOOD 111 “ 260 “ 89 “ 210 A B 454 “ 184 “ 416 “ 260 “ 11 7 “ 1340 “ L.H. END VIEW REAR VIEW L.H. END VIEW REAR VIEW 638 “ 41 “ 698 267 “ 1 140 “ 502 “ “ CONDEN- SA TE DRAIN CONN.
035-12984-001-A-0204 10 Unitary Products Group T ABLE 4 - SUPPL Y AIR PERFORMANCE - BCH048 MODEL AIR FLOW m 3 /s / CFM Available External S tatic Pressure -Pa/ IWG* 223 / 0.90 248 / 1.00 273 / 1.10 298 / 1.20 322 / 1.30 347 / 1.40 372 / 1.50 RPM W atts RPM W atts RPM W atts RPM W atts RPM W atts RPM Watt s RPM Watt s 060 1.
035-12984-001-A-0204 Unitary Products Group 11 MODEL BCH POWER SUPPL Y VOL TAGE LIMIT ATIONS COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA TOT AL UNIT AMP ACITY , AMPS MAX. FUSE SIZE, (SEE NOTE 1) AMPS MAX. HACR BREAKER SIZE, AMPS MIN.
screw fully clockwise and then energize and de-energize terminals “R” to “G”. With terminals “R” to “G” energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained. 1 1. Replace the filter section access panel.
During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 13mm ( in.) long, 1mm ( in.) apart and are mounted on a white base. See Figure 8. LOCKOUT CONTROL Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode: 1.
3. Using an inclined manometer , determine the pressure drop across a dry indoor coil. Since the moisture on an indoor coil may vary greatly , measuring the pressure drop across a wet coil under field conditions would be inaccurate. T o ensure a dry coil, the compressors should be de-energized while the test is being run.
035-12984-001-A-0204 Unitary Products Group 15.
Unitary Products Group 5005 Y ork Drive, Norman, Ok 73069 Subject to change without notice. Printed in U.S.A. Copyright by Y ork International Corporation 2004.
Een belangrijk punt na aankoop van elk apparaat York B3CH 048 and 060 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen York B3CH 048 and 060 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens York B3CH 048 and 060 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding York B3CH 048 and 060 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over York B3CH 048 and 060 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van York B3CH 048 and 060 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de York B3CH 048 and 060 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met York B3CH 048 and 060 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.