GENERAL REFERENCE St andard Register TOLL FREE T elephone: 877-318-9675 TOLL FREE Fax: 877-379-7920 INSPECTION SPLIT -SYSTEM HEA T PUMPS OUTDOOR UNITS INST ALLATION MANUAL 035-15410-002-B-0404 MODELS .
2 Unitary Products Group 090 = 7-1/2 T on 120 = 10 T on T ABLE OF CONTENTS INST ALLATION OPERATION ° ST ART -UP MAINTENANCE LIST OF FIGURES LIST OF T ABLES.
LIMIT ATIONS LOCATION 1. The outdoor units must be installed outside the building. The outdoor fans are the propeller type and are not suitable for use with duct work. 2. The outdoor and indoor units should be installed as close together as possible and with a minimum number of bends in the refrigerant piping.
CLEARANCES WARNING: Do not permit overhanging structures or shrubs to obstruct air discharge. COMPRESSORS CAUTION: Do Not loosen compressor mounting bolts. COMPRESSOR CRANKCASE HEA TER CAUTION: Do not attempt to start the compressor without at least eight hours of crankcase heat or compressor damage will occur .
Both the manual and auto changeover thermostats have non- adjustable, voltage-type anticip ators for both cooling and heat - ing. WIRE SIZING REFRIGERANT PIPING GENERAL GUIDELINES Unitary Products Group 5 035-15410-002-B-0404 FIG . 3 - TYPICAL FIELD WIRING 200/230-3-60 0.
6 Unitary Products Group FIG . 4 - UNIT DIMENSIONS AND CLEARANCES - 7-1/2 & 10 TON All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. Overhead (T op) 1 Front (Piping and Access Panels) Left Side Right Side Rear Bottom 2 1 Units must be installed outdoors.
LINE SIZING ° Oil return will be critical during: The cooling cycle when the outdoor unit is above the indoor unit (detail 1 of Figure 5). The heating cycle when the indoor unit is above the outdoor unit (detail 4 of Figure 5). EXAMPLES: #1 - 7-1/2 T on System 125 feet of 1-3/8" OD, type “L” copper tubing (125 feet x 1.
(29 feet x 8.0 psi/100 feet) ............................................. 2.3 p si 7 feet of 1-3/8" OD, type “L” copper tubing (horizontal) (7 feet x 2.8 psi/100 feet) ............................................... 0.2 p si Fitting* .......
NOTE: Use only copper tubing that has been especially cleaned and dehydrated for refrigerant use. If the tub - ing has been open for an extended period of time, it should be cleaned before being used. NOTE: 1. The matched air handlers are shipped with a small R-22 charge and they should be checked for leaks before instal - lation.
BALANCE POINT SETTING The outdoor design temperature, The building heat loss at the outdoor design temperature, and The heating capacity of the system at the outdoor design temperature.
Unitary Products Group 11 035-15410-002-B-0404 FIG . 7 - REFRIGERANT FLOW DIAGRAM.
12 Unitary Products Group FIG . 8 - CHARGING CUR VE EFB090 FIG . 9 - CHARGING CUR VE EFB120.
GENERAL CAUTION: Reversing valves and check valves are precise mechanical devices and will not tolerate any me - chanical abuse such as hammering. If a refrigerant system isn't properly cleaned after a compressor burn-out, scale may build up at these devices and prevent them from operating properly .
IN ALL THREE RESET METHODS DESCRIBED ABOVE, A FIVE MINUTE TIME DELA Y WILL T AKE PLACE AFTER THE RESET BEFORE THE UNIT WILL REST AR T . 8. Supplemental electric heat (if installed) will be controlled by second stage TH2 of the thermostat. The supplement al electric heat circuit is controlled through low voltage termi - nals W , 60 and 66.
CRANKCASE HEA TER CAUTION: DO NOT A TTEMPT TO ST ART THE COMPRES - SOR WITHOUT A T LEAST 8 HOURS OF CRANKCASE HEA T OR COMPRESSOR DAM - AGE WILL OCCUR. PRE-ST ART CHECK 1. Have sufficient clearances been provided? 2. Has all foreign matter been removed from the interior of the unit (tools, construction or shipping materials, etc.
Untiary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright © 2004 by Y ork International Corporation.
Een belangrijk punt na aankoop van elk apparaat York E2FB120 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen York E2FB120 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens York E2FB120 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding York E2FB120 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over York E2FB120 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van York E2FB120 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de York E2FB120 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met York E2FB120 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.