CopperTen ® Four-Pair Riser Cable

An integral part of ADC’s TrueNet® Structured Cabling System, CopperTen® is the world’s first UTP structured cabling system to enable 10 Gigabit Ethernet over a full 100 meters. Installed in high-performance networks worldwide, the system’s patent-pending design minimizes alien crosstalk and insertion loss and meets the performance requirements of IEEE 802.3an, ISO 11801 Class EA and TIA/EIA-568-B.2-10 standards.
Patent-pending oblique elliptical offset filler minimizes alien crosstalk •
Manufactured with lead-free materials •
UL Subject 444 •
(UL)-C(UL) Type CMR/CMG •
NEC 800 Type CMR •
TIA/EIA 568-B.2-10 standard •
ISO/IEC 11801 CLASS EA Category 6a horizontal cable requirements •

CopperTen ® Four-Pair Riser Cable
Specifications
CONSTRUCTION CHARACTERISTICS Conductor: 23 AWG solid bare copper Insulation: 100% Polyolefin Separator: Flame retardant polyolefin Jacket: Non-lead, flame retardant PVC Nominal Outer Diameter: 7.5 mm (.295") – 6.6 mm x 8.3 mm (.260" x .325")
5 / 0 8 • 1 0 4 9 7 6 A E CopperTen® Four-Pair Riser Cable
MECHANICAL CHARACTERISTICS Bend Radius During Installation: 8 x outer diameter Installed: 4 x outer diameter Pull Tension: 110 N (25#)
ELECTRICAL CHARACTERISTICS Conductor DC Resistance @ 20° C (68° F) (Max): 9.38 Ω/100 m (28.6 Ω/1000 ft) DC Resistance Unbalance (Max): 2% Mutual Capacitance @ 20° C (68° F) (Max): 5.6 nF/100 m (17 pF/ft) Operating Voltage (Max): 300 VDC Worst Case Cable Skew: 40 ns/100 m (40 ns/ 328 ft) Nominal Velocity of Propagation: 65%
Transport and Storage: -20° to 75° C (-4° to 167° F) Installation: 4° to 50° C (39° to 122° F) Operation: -20° to 75° C (-4° to 167° F)
Environmental CHARACTERISTICS

CopperTen ® Four-Pair Riser Cable
5 / 0 8 • 1 0 4 9 7 6 A E CopperTen® Four-Pair Riser Cable
only. Actual compliance testing is based on swept frequency measurements. The spec values are based on TIA/EIA 568-B.2-10 specifications.

engineering information only. Actual compliance testing is based on swept frequency measurements. The spec values are based on TIA/EIA 568-B.2-10 specifications.
O r d e r i n g I n f o r m a t i o n
4-pair riser data cable
1000' reel 10G-A6TR-XX02 Additional packaging options are available, please contact ADC Technical Assistance Center. * To order jacket color, replace XX with: BL = Blue, GN = Green, WT = White, YL = Yellow, GY = Gray, RD = Red
From North America, Call Toll Free: 1-800-366-3891 • Outside of North America: +1-952-938-8080
Fax: +1-952-917-3237 • For a listing of ADC’s global sales office locations, please refer to our website.
ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, Minnesota USA 55440-1101 Specifications published here are current as of the date of publication of this document. Because we are continuously improving our products, ADC reserves the right to change specifications without prior notice. At any time, you may verify product specifications by contacting our headquarters office in Minneapolis. ADC Telecommunications, Inc. views its patent portfolio as an important corporate asset and vigorously enforces its patents. Products or features contained herein may be covered by one or more U.S. or foreign patents. An Equal Opportunity Employer
104976AE 5/08 Revision © 2008, 2007, 2005 ADC Telecommunications, Inc. All Rights Reserved