Read and follow the information in this Operating Manual. This will prevent accidents, retain your right to Guarantee claims and keep your generator set properly maintained.
manufacturer. The generator set may only be operated, main- tained and repaired by competent persons who are aware of the possible dangers.
For the Guarantee Conditions, see the Vetus Diesel Service and Guarantee Book.
The relevant instructions for preventing accidents and other gen- erally accepted safety and operating instructions must be taken into account.
This generator set is exclusively intended for applications as stated in the delivery specifications, and should only be used for this purpose. Any other use is in conflict with its intended purpose. The manufacturer cannot accept any liability for dam- age as a consequence of this. Any risks are carried exclusively by the user.
Any modifications made to the generator set by the user relieve the manufacturer of any liability to claims for damage as a con- sequence of this.
Similarly, work on the injection and control system can effect the engine performance and exhaust emissions. Conformance with the legal definitions concerning environmental protection can then no longer be guaranteed.
Use in accordance with its purpose also means following the operating, maintenance and repair instructions as stated by the



Vetus Generator Sets have been specially developed for use in ships. A wide range of types are available to fulfil every specific requirement.
Your generator set is designed for installation in your ship. This means that some of the components described in this Manual are not necessarily fitted to your generator set.
We have tried to make the differences clear, so that you can easily find the operating and maintenance information related to your generator set.
Please read this Manual before using the generator set, and fol- low the operating and maintenance instructions.
We are always available to answer any questions you may have.
Yours sincerely, Vetus den Ouden N.V.
Dear Customer,

Safety Measures 1
You will find this symbol alongside all information concerning safety. Be sure to follow this informa- tion carefully.
Inform other people who operate the generator set of this safety information.
General regulations and laws concerning safety and the preven- tion of accidents should also be taken into account.

See the ‘Overall Dimensions’ drawing for the identification of the most important generator set connections.
To identify specific engine components, consult the separate engine manual.
Which type of generator set suits which type of engine is described in ‘Technical Data’. This also provides a summary of the manuals for the various engines.
Generator panel for GHS14TIK, GHS24TIK, GLS14TIK and GLS25TIK

2 5 6 7 8
5 6 7 8
Control Panel for GHS4 Control Panel for GHS6.5, GHS8, GHS14, GHS24, GLS6.5, GLS14 and GLS25
1 Operating hours counter 2 Circuit breaker 3 Contact box 4 Connection box 5 ‘Outside water temperature’ warning lamp 6 ‘Oil pressure’ warning lamp 7 ‘Coolant temperature’ warning lamp.
8 ‘Charge current’ warning lamp 9 ‘Pre-heating’ warning lamp 10 ‘In operation’ warning lamp. 11 ‘ON’ push-button switch 12 ‘Pre-heating’ push-button switch 13 ‘START’ push-button switch 14 ‘STOP’ push-button switch
‑‑9

Following the recommendations below will result in a longer operating life, better performance and more economical opera- tion of your generator set.

Running-in
Before starting the engine for the first time, carry out the follow- ing operations:
In order to achieve a long operating life for your engine, take care with the following for the first 50 operating hours:
Only refuel when the engine is stopped. Do not spill fuel. Prevent unnecessary pollution.

After repair work Check that all safety equipment is fitted and all tools have been removed from the engine and/or generator. When starting with pre-heater plugs, do not use any extra starting aids (Quick-start sprays, etc.). This could cause an accident.
Starting without Pre-heating - GHS4 - Press the ‘ON’ button briefly; the ‘In Operation’, ‘Oil Pressure’ and ‘Charge’ warning lamps will light up. Press the ‘START’ button and release it as soon as the engine fires.
Starting The generator set is started from the control panel or at the generator set itself.

If the engine will not start after repeated efforts, a large quantity of water could collect in the exhaust silencer/water lock as a consequence. Excess water in the exhaust silencer can also prevent the engine starting. If necessary, drain water from the silencer.
Starting with Pre-heating - GHS6.5, GHS8, GHS14, GHS24, GLS6.5, GLS14 and GLS25 - Press the ‘ON’ button briefly; the ‘In Operation’, ‘Oil Pressure’ and ‘Charge’ warning lamps will light up and the electric fuel pump will start operating. If the engine is cold, operate the pre-heating. Press the ‘Pre-heat’ button and keep it down for 10 seconds.. Press the ‘START’ button and release it as soon as the engine fires.
The green LED above the ‘ON’ button will remain on, to indicate that the engine is running. Check that the ‘Charge’ warning lamp is off. Cooling water should now flow from the exhaust, if this is not the case, stop the generator set immediately. The ship’s electrical equipment can be switched on after a few minutes.

None of the 4 warning lamps should light up while the engine is running. Protection devices for oil pressure, coolant temperature and out- side water supply will switch the generator set off automatically if a fault occurs. The ‘Charge’ warning lamp will light up when the dynamo no longer charges, but the engine will continue to run.
Stopping when the Electrical System (12 Volt) breaks down.
GHS4, GHS14, GHS24, GLS6.5, GLS14 and GLS25: When the electrical system (12 Volt) breaks down, the engine will stop immediately.
GHS6.5 and GHS8: When the electrical system (12 Volt) fails, the system will con- tinue to run. The engine can be stopped by pressing the black button on the fuel pump.
Stopping Switch off all the ship’s electrical equipment. Allow the generator set to run for about 1 minute without load. Press the ‘STOP’ key until the ‘In Operation’ light goes off. Then release the ‘STOP’ button. The engine has now stopped.
When the generator set is not going to be used for a longer time, it is recommended that the outboard tap is closed and the main switch is turned to the OFF position.

Introduction The guidelines below apply to daily and periodic maintenance. Carry out maintenance at the time stated. The time intervals stated are for normal operating conditions. If conditions are poor, carry out maintenance more often. Failure to carry out maintenance can lead to breakdowns and permanent damage to engine or generator. No claim can be made on the Guarantee if maintenance has been neglected.

Every 400 hours, or at least 1x a year
Check oil level •
Check engine speed (RPM)/Fuel pump adjustment page 47
Check coolant level •
Check valve clearance •
Check cooling water filter •
Replace fuel filter •
Every 800 hours, or 1x every 2 years.
Re-torque the cylinder head bolts •
Clean the heat exchanger •
Drain water from the fuel filter •
Check the outboard water pump •
Change the engine oil •
Change the coolant •
Check the V-belt or drive belt •
Check engine speed (RPM)/Fuel pump adjustment page 47
Check valve clearance •
*) For carrying out this maintenance work, consult the manual for the engine concerned. It is possible that not all maintenance work described will be required on your generator set, this depends on the type of engine.
Drain water from the fuel filter •
Change the engine oil •
Check V-belt or drive belt •
Replace oilfilter • · Generator page 50 · Replace oilfilter •

Checking the Engine Speed The frequency of the mains voltage is not the same all over the world. This frequency can either be 50 or 60 Hz. F or example, the fre- quency in Europe is usually 50 Hz, while in the United States it is 60 Hz. The frequency of the generator set will be the same as the mains frequency in your cruising area.
The speed of the generator will decrease as the load increases. So adjust the generator as follows:
All GHS generator sets: The RPM for a generator without load is about 3100 rpm (51.5‑Hz).
All GLS generator sets: The speed for a generator without load is about 1550 rpm (51.5‑Hz) or about 1850 rpm (61.5 Hz).
N.B.: If you want to connect your on-board network to a dockside connection outside your usual cruising area, take care to check that both voltage and frequency are the same as that for your generator set.
Allow the engine to run until it is warm (coolant temperature about 60 degrees C (140 deg. F ) or higher) before checking the speed and adjusting, if necessary.
Check the speed using a rev. counter, or use a frequency meter connected to the electrical installation. The correct speed can be set using the adjusting screws on the fuel pump.

Every 400 operating hours.
Consult a VETUS FARYMANN Specialist! 5
B
Adjusting the GHS6.5, GHS8, GHS14 and GLS6.5 Fuel Pump Unscrew both lock nuts and adjust the set screws until the cor- rect speed has been reached. Then tighten up the lock nuts again. Turn set screw A when the speed has to be increased; turn set screw B when the speed has to be reduced.
This can only be adjusted inside the fuel pump itself. When adjustment is required, it is recommended that you let it be done by a Vetus F arymann Service Specialist.
Seal · Increasing the speed · Reducing the speed


Unscrew both lock nuts and adjust the set screws until the cor- rect speed has been reached. Then tighten up the lock nuts again. Turn set screw A outwards when the speed has to be increased; turn set screw B outwards when the speed has to be reduced.
Unscrew both lock nuts and adjust the set screws until the cor- rect speed has been reached. Then tighten up the lock nuts again. Turn set screw A outwards when the speed has to be increased; turn set screw B outwards when the speed has to be reduced.

Maintenance Generator Every 800 operating hours.
GHS6.5, GHS8 Only:
Cleaning the generator The generator and AVR (Automatic Voltage Regulator) should be kept as clean as possible. Many electrical faults can be caused by dirt collecting. Remove any dirt and dust from the generator. Blow through the generator using oil-free compressed air. Take care no dust is blown into the windings. The inside and outside of the generator should always be kept free of water, oil and dirt.
Slip Rings and Carbon Brushes Check the slip rings and carbon brushes for wear. Replace worn carbon brushes with new ones of the right type and size. Check to see that the carbon brushes run in the centre of the slip rings.
Check that all electrical connections are correctly and firmly fixed.
The bearing is sealed and lubricated for life, so requires no fur- ther maintenance.

Preparation for Summer
Consult the separate engine Manual for taking it out of service for the winter. It is not necessary to carry out any specific work on the generator at the start of the winter lay-up.
Consult the separate engine Manual for preparation for use again at the start of the summer cruising season.
GHS4, GHS14, GHS24, GLS6.5, GLS14 and GLS25: It is not necessary to carry out any specific work on the generator to prepare it for operation again.
GHS6.5 and GHS8: Check the slip rings for possible corrosion, sand them clean if necessary. F or this, use very fine 400 - 500 Grade) sanding cloth. Further specific work is not required at the start of the cruising season.

When a fault occurs, check the following before carrying out the tests in the Table:

2 No load, Voltage too high or too low
Possible Cause • Loss of residual magnetism.
Possible Cause • Engine runs irregularly due to lack of fuel, faulty or wrongly set fuel pump.
Solution • Ensure the supply of enough clean water-free fuel, or: Have the fuel pump checked
by a specialist and repair or re-adjust as required.

6 Load, voltage oscillates
Possible Cause • Short-circuit in on-board cir- cuit.
Solution • Trace the short-circuit and repair.
Possible Cause • Engine runs irregularly due to lack of fuel, faulty or wrongly set fuel pump.
Solution • Ensure the supply of enough clean water-free fuel, or: Have the fuel pump checked
by a specialist and repair or re-adjust as required. • Repair the connections.
Possible Cause • Over-loaded.

Fault Finding, generator Fault Finding Table GHS6.5, GHS8, GHS14, GHS24, GLS6.5, GLS14 and GLS25
2 No load, Voltage too high or too low
Possible Cause • Loss of residual magnetism.
Solution • Connect a 12 Volt battery for a short period to regenerate the field; plus (+) to ‘X’ and minus (-)
Possible Cause • Incorrect engine speed.
to ‘XX’ or, plus (+) to ‘F1’ and minus
Possible Cause • Engine runs irregularly due to lack of fuel, faulty or wrongly set fuel pump.
Solution • Ensure the supply of enough clean water-free fuel. Have the fuel pump checked
by a specialist and repair or re-adjust as required. • Readjust the stability.

6 Load, voltage oscillates
Possible Cause • Engine runs irregularly due to lack of fuel, faulty or wrongly set fuel pump.
Solution • Ensure the supply of enough clean water-free fuel. Have the fuel pump checked
Possible Cause • Incorrect engine speed.

Fault Finding, generator
Possible Cause • Over-loaded.

General Nominal speed 3000 RPM Noise Level — 75 dB(A) 75 dB(A) 78 dB(A) 78 dB(A) Noise Level, with cabinet 68 dB(A) 65 dB(A) 65 dB(A) 70 dB(A) 70 dB(A) @ 3000 RPM Max. Temperature raw water 30°C (86°F) Max. Ambient Temperature 40°C (104°F) Max. Tilt lengthwise 15° Max. Tilt crosswise 25° Weight, without sound cabinet — 120 kg 125 kg 220 kg 200 kg (265 lbs) (276 lbs) (485 lbs) (441 lbs) Weight, with sound cabinet 95 kg 180 kg 185 kg 295 kg 275 kg (209 lbs) (397 lbs) (408 lbs) (650 lbs) (606 lbs)
Engine Specifications Mark Vetus/Farymann Vetus/Mitsubishi Type F1.03 M2.C5 M2.06 M3.09 M3.09
Consult the Manual for the engine concerned for complete engine specifications.
Manual for engine type : F1.03 : STM0061 M2.C5/M2.06/M3.09 : 340102.04 (English) M4.17 : STM0119 (English) VH4.65 : STM4994 (English)

General Nominal speed 3000 RPM 1500 RPM Noise Level 78 dB(A) 78 dB(A) 73 dB(A) 73 dB(A) 73 dB(A) 73 dB(A) Noise Level, with cabinet 70 dB(A) 70 dB(A) 57 dB(A) 57 dB(A) 57 dB(A) 57 dB(A) @ 3000 RPM @ 1500 RPM Max. Temperature, raw water 30°C (86°F) Max. Ambient Temperature 40°C(104°F) Max. Tilt lengthwise 15° Max. Tilt crosswise 25° Weight, without sound cabinet 345 kg 315 kg 170 kg 315 kg 295 kg 415 kg (761 lbs) (694 lbs) (375 lbs) (694 lbs) (650 lbs) (914 lbs) Weight, with sound cabinet 436 kg 395 kg 245 kg 395 kg 375 kg 505 kg (961 lbs) (871 lbs) (540 lbs) (871 lbs) (827 lbs) (1112 lbs)
Engine Specifications Mark Vetus/Mitsubishi Vetus/Hyundai Type M4.17 M4.17 M3.09 M4.17 M4.17 VH4.65
Consult the Manual for the engine concerned for complete engine specifications.

Generator Specifications Mark Syncro Markon Markon Stamford Stamford Type * BWG430 BWG830/ BWG830/ BCI162G BCI162E SL105G SL105G Power, at power factor 0,8 4 kVA 6,5 kVA 8 kVA 14 kVA 14 kVA 3,2 kW 5,2 kW 6,4 kW 11 kW 11 kW Voltage 1 x 230 V 1 x 230 V 1 x 230 V 1 x 230 V 3 x 400 V Current 14 A 22,5 A 27,5 A 46 A 3 x 15,4 A Frequency 50 Hz Number of poles 2 Overload Power Maximum start current for electro-motor 1.5x nominal generator current Power factor Between 0.8 inductive and 1 Operating range Minimum 4% of the nominal speed (RPM) Voltage Control +/- 5% +/- 3,5% +/- 3,5% +/- 2% +/- 2% Insulation Class H Protection Grade IP22 Protection Grade in sound cabinet IP44
N.B.: All the information above is based on generator sets
with a frequency of 50 Hz.
*) BWG430: Brushless, self-exciting alternating current generator with capacitor control.
BWG830: Self-regulating, self-exciting alternating current generator with automatic voltage regulator (AVR).

Generatorspecifications Mark Stamford Stamford Syncro Stamford Stamford Stamford Type * BCI182K BCI162G BWG615E BCI184E BCI164D BCI184F
Power, at power factor 0,8 24 kVA 24 kVA 6,5 kVA 14 kVA 14 kVA 25 kVA 19,2 kW 19,2 kW 5,2 kW 11,2 kW 11,2 kW 20 kW Voltage 1 x 230 V 3 x 400 V 1 x 230 V 1 x 230 V 3 x 400 V 3 x 400 V Current 85 A 3 x 28,5 A 22,5 A 50 A 3 x 16 A 3 x 36 A Frequency 50 Hz Number of poles 2 2 4 Overload Power Maximum start current for electro-motor 1.5x nominal generator current Power factor Between 0.8 inductive and 1 Operating range Minimum 4% of the nominal speed (RPM) Voltage control +/- 2% +/- 2% +/- 2% +/- 2% +/- 2% +/- 2% Insulation Class H Protection Grade IP22 Protection Grade in sound cabinett IP44
N.B.: All the information above is based on generator sets
with a frequency of 50 Hz.
*) BCI162G, BCI162E, BCI182K, BWG615E, BCI184E, BCI164D and BCI184F: Brushless, self-regulating self-exciting alternating current gen- erator with automatic voltage regulator (AVR).

Type GHS4SI GHS6.5SI GHS8SI GLS6.5SI GLS14SI (BWG430) (BWG830) (BWG830) (BWG615E) (BCI184E) Winding Resistances Rotor 1,8 Ω 11,9 Ω 11,9 Ω 1,15 Ω 0,64 Ω Stator, Main Winding per section 0,6 Ω 0,28 Ω 0,28 Ω 0,45 Ω 0,20 Ω Stator, Auxiliary Winding 2,8 Ω 1,77 Ω 1,77 Ω 20 Ω 20 Ω Rotor, Auxiliary Winding 0,21 Ω 0,21 Ω
Generator Protection Main circuit Automatic F use (Circuit Breaker) 16 A 20 A 25 A 20 A 50 A
Type GHS14SI GHS14TI GHS24SI GHS24TI GLS14TI GLS25TI (BCI162G) (BCI162E) (BCI182K) (BCI162G) (BCI164D) (BCI184F) Winding Resistances Rotor 1,09 Ω 0,89 Ω 1,4 Ω 1,09 Ω 0,56 Ω 0,74 Ω Main (stator) winding per section 0,10 Ω 0,42 Ω 0,095 Ω 0,21 Ω 0,3 Ω 0,13 Ω Auxiliary Winding, stator 19 Ω 18 Ω 20 Ω 19 Ω 19 Ω 22 Ω Auxiliary Winding, rotor 0,27 Ω 0,26 Ω 0,21 Ω 0,27 Ω 0,26 Ω 0,23 Ω
Generator Protection Main circuit Automatic F use (Circuit Breaker) 50 A 3 x 16 A 80 A 3 x 32 A 3 x 16 A 3 x 36 A
N.B.: All the above information is based on generator sets with a frequency of 50 Hz.

Consult the relevant engine Manual for specifications and quanti- ties of the liquids above.