Gebruiksaanwijzing /service van het product 38AQS008 van de fabrikant Carrier
Ga naar pagina of 20
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS .................1 INST ALLA TION ............................1 - 9 Step 1 — Complete Pre-Installation Checks ..1 • UNCRA TE UNIT • INSPECT SHIPMENT • CONSIDER SYSTEM REQUIREMENTS Step 2 — Rig and Mount the Unit .
T able 1A — Physical Data (English) UNIT 38AQS008 60 Hz 50 Hz OPERA TING WEIGHT (lb) Aluminum Coils (Standard) 540 594 Copper Coils (Optional) 608 662 RIGGING WEIGHT (lb) Aluminum Coils (Standard) 590 644 Copper Coils (Optional) 658 712 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Quantity .
T able 2 — Refrigerant Piping Sizes LINEAR LENGTH OF PIPING — ft (m) UNIT 38AQS 0-25 (0-7.6) 25-50 (7.6-15.2) 50-75 (15.2-22.9) 75-100 (22.9-30.5) Line Size (in. OD) L S L S LSLS 008 1 ⁄ 2 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 LEGEND L— Liquid Line O D— Outside Diameter S— Suction Line NOTES: 1.
UNIT 38AQS008 UNIT W/ALUMINUM COIL UNIT W/COPPER COIL WEIGHT CHART (WITH ALUMINUM COIL) WEIGHT CHART (WITH COPPER COIL) Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg 60 Hz 1 ⬘ -8 ⬙ [508.
All field wiring must comply with NEC (U.S.A.) and lo- cal requirements. Install field wiring as follows: 1. Install conduit through side panel openings. 2. Install power lines to connections as shown in Fig. 8. W rap connections with electrical tape.
LEGEND NEC — National Electrical Code TXV — Thermostatic Expansion V alve *Accessory item. †Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Re- fer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes.
T able 4 — Electrical Data UNIT 38AQS NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y MINIMUM DISCONNECT Min Max RLA LRA FLA MCA MAX FUSE OR HACR BRKR AMPS FLA LRA 008 208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177 460-3-60 414 508 15.
T able 5A — Accessory Electric Heater Data (60 Hz) UNIT 40RMQ HEA TER P ART NO. V -PH-Hz NOMINAL kW HEA TER AMPS MCA* MOCP* 008 CAELHEA T001A00 240-3-60 5 12.0 25.6 30 CAELHEA T002A00 480-3-60 6.0 12.3 15 CAELHEA T003A00 575-3-60 5.0 1 1.9 15 CAELHEA T004A00 240-3-60 10 24.
2 CORNER POST RACEWA Y THERMOST A T FIELD CONNECTION POWER WIRING CONNECTIONS Fig. 6 — Fusible Plug Locations LEGEND NO TE: The 8 o’clock position is shown abo ve . Fig. 7 — TXV Sensing Bulb Location TXV — Ther mostatic Expansion V al ve LEGEND Fig.
ST ART -UP Preliminary Checks 1. Check that all internal wiring connections are tight and that all barriers, covers, and panels are in place. 2. Field electrical power source must agree with unit name- plate rating. 3. Ensure all service valves are open.
Should room temperature continue to fall, circuit R-W is made through second-stage thermostat bulb. If optional elec- tric heat package is used, a relay is energized, bringing on supplemental electric heat. When thermostat is satisfied, con- tacts open, deenergizing contactor and relay; motors and heat- ers deenergize.
5. Remove crankcase heater from compressor base. 6. Remove compressor holddown bolts and lift compres- sor of f basepan. 7. Remove compressor from unit. 8. Clean system. Add new liquid line filter drier (biflow type). 9. Install new compressor and position in unit.
Fig. 16 — Cooling Mode Operation Fig. 17 — Heating Mode Operation 13.
TROUBLESHOOTING CHART , COOLING CYCLE LEGEND TXV — Thermostatic Expansion V alve 14.
TROUBLESHOOTING CHART , HEA TING CYCLE LEGEND N.C. — Normally Closed 15.
.
.
Manufacturer reserves the right to discon tinue, or change at any time, specifications or designs without notice and wit hout inc urring obligation s. PC 111 Catalog No.
ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST AR T -UP? (Y/N) CHECK POWER SUPPL Y .
Manufacturer reserves the right to discon tinue, or change at any time, specifications or designs without notice and wit hout inc urring obligation s. PC 111 C atalog No.
Een belangrijk punt na aankoop van elk apparaat Carrier 38AQS008 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier 38AQS008 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier 38AQS008 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier 38AQS008 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier 38AQS008 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier 38AQS008 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier 38AQS008 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier 38AQS008 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.