Manufa cturer res erves the right to discon tinue, or chang e at any time , specificat ions or designs witho ut notic e and wit hout inc urring obligati ons.
2 (FIELD PROVIDED AND INST ALLED) Fig. 2 — 38HDF ,HDR Unit Dimensions NOTE: Dimensions shown in feet-inches. Dimensions in ( ) are m illimeters. UNIT MODELS CHASSIS SIZE (Referen ce) ABC D E FG H J .
3 Step 2 — Rig and Mount Unit MOUNTING ON GROUND — M ount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly ont o unit. Acce ssory stacking ki ts can be used when units are to be stac ked. See i nstallati on instruct ions provided with the accessory kit.
4 Only use factory specified liquid-line filter driers with rated working pressures less than 600 psig. NOTE: Do not install a suction-line filter dri er in liquid line. MAKE PIPING SWEA T CONNECTIONS — Remove plasti c caps from liquid a nd suction servi ce valves.
5 Table 1B — 38HDR 018-060 P hysical D ata LEGEND *Unit shipped with full factory charge. See ARI (Air Conditioning and Refrigeration Institute) capacity tab le for proper charge and piston for each f an coil type. †V alve connection size is 7 / 8 inch.
6 Step 4 — Make Electrical Connections CO N TR O L CI R C UI T W IR I N G — Control voltage i s 24 v (40 va minimum). See Fig. 5 and unit label diagram for fi eld- supplied wiring details. Route control wire through opening in unit side panel to connection in unit control box.
7 Table 2 — 38HDF Electric al Data LEGEND *P er missible limits of the v oltage range at which unit will operate satisf actorily . NO TES: 1. Control circuit is 24 v on all units and requires an exter nal power source. 2. All m otors and compres sors contain inter nal overload protection.
8 Table 3 — 38HDR E lectrical Data LEGEND *P er missible limits of the v oltage range at which unit will operate satisf actorily . NO TES: 1. Control circuit is 24 v on all units and requires an exter nal power source. 2. All m otors and compress ors contain inter nal overload protection.
9 LEGEND NO TES : 1. Com pressor and fan motors are t hermally protected. 2. W ire in accordance with National Electrical Code (NEC) and local codes . Replace any original wires with 90° C wire or its equiv alent. 3. Us e minimum 60° C wire f or field power wiring.
10 LEGEND NO TES: 1. Compr essor and f an motors are thermally protected. 2. W ire in accordance with National Electric al Code (NEC) and local co des. Replace any original wires with 90° C wire or its equi valent. 3. The CLO locks out the COMP to prev ent shor t cycling on COMP overloads and safet y devi ces.
11 ST AR T -UP Preliminary Chec ks 1. Check that all internal wiring connections are tight and that all barri ers, covers, and panels ar e in place. 2. Field electrical power source must agree with unit name - plate rating. 3. All service val ves must be open.
12 T o troubleshoot: 1. Apply voltmeter acros s crankcase heat er leads to see if heater voltage i s on. Do not touch heater . Carefully feel area around crankcas e heater; if warm, c rankcase heater is functioning. 2. W ith power off and heater leads disconne cted, check across leads with ohmmet er .
13 Table 4 — Pres sure vs. Tempera ture Cha rt — Pu ron® Refrig erant ( R-410A) Subcooling Met hod — For 38HDR units only , the sub- cooling method is used to check and adjust charge during the cooling season. Refer to T able 5 and the fol lowing procedure: NOTE: For use with residential fan coils and the 40QA060 under ceiling unit only .
14 Table 5 — Subcooling Charging Table Compressor Lock out Switch — The 38HDR units are provided with a compressor lockout protective device. If the compressor shuts down due to any safety device, a current loop monitoring the compressor current senses no c urrent flow .
15 Fig. 9 — T rouble shooting the Cooling Cycle.
Manufa cturer reser ves the right to discon tinue, or change at any time, specificat ions or designs w ithout not ice and without incurrin g obligations.
Een belangrijk punt na aankoop van elk apparaat Carrier 38HDR018-060 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier 38HDR018-060 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier 38HDR018-060 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier 38HDR018-060 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier 38HDR018-060 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier 38HDR018-060 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier 38HDR018-060 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier 38HDR018-060 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.