Application Data Control Selection Guide for Fan Coil Air Conditioners 42 Series Fan Coil Units Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 3 Ta b 7 a PC 201 Catalog No.
CONTENTS Page CONTROL SELECTION GUIDE ............... 3 ST ANDARD WIRING P ACKAGES ............ 4 - 8 Manual Fan Control ......................... 4 Thermostatic Fan Control, 2-Pipe Systems ............................ 4 Thermostatic Fan Control, 2-Pipe System with Safety Cycle .
CONTROL SELECTION GUIDE Use this guide to make sure that all necessary components are provided for and that the components are compatible with the required control system.
ST ANDARD WIRING P ACKAGES IMPOR T ANT : W iring diagrams shown depict typical control functions. Refer to unit wiring label for spe- cific functions. Manual Fan Control — On all V ertical Cabinet units, the standard fan-speed switch is furnished unit-mounted and wired.
Thermostatic Fan Control, 2-Pipe System with Safety Cycle — This control is used for high humidity situations in which condensate problems can occur if fan is turned of f while chilled water is still running through the coil. The wiring provides fan cycling from HIGH to LOW on the cooling cycle and from LOW to OFF on the heating cycle.
ST ANDARD WIRING P ACKAGES (cont) Thermostatic 2-Pipe Auxiliary Electric Heat with V alve Control — This system, also called T wi- light or Intermediate Season electric heat, goes a long way towards solving the spring and fall control problems of 2-pipe systems.
Thermostatic 2-Pipe T otal Electric Heat with- V alve Control — With this system, the complete heat- ing requirement for the space is provided by the electric heater; the water system is never changed over for heating. It is there- fore possible, just as with 4-pipe systems, to have heating or cooling at any time of the year .
ST ANDARD WIRING P ACKAGES (cont) Thermostatic V alve Control, 4-Pipe — The 4-pipe system provides the ultimate in economy and room tem- perature control. Both hot water and chilled water are avail- able at any time. Normally an automatic changeover thermostat is used, but a manual changeover thermostat is also suitable.
ELECTRIC HEA T Application — Electric heaters are available for in-stallation on Carrier fan coil units in the following applications. TOT AL ELECTRIC HEA T — This system provides com- plete heating during the heating season; no boiler is re- quired.
REMOTE-MOUNTED CONTROLS Standard 3-Speed Switch — This standard switch has 4 positions: OFF , HIGH, MEDIUM, and LOW . Switch has auxiliary contact that is energized when switch is in HIGH, MEDIUM or LOW position. Some of the options common with the 3-speed switch are: 1.
AL TERNA TE W ALL THERMOST A TS W all Thermostat (Honeywell Model T4039) with Manual 3-Speed Fan Switch and ON-OFF Switch T emperature range is approximately 55 to 95 F in 10° F increments from 75 F midpoint. Scale is marked warmer - cooler . Thermostat mounts in 4-in.
UNIT -MOUNTED CONTROLS OFF HI MED LO Standard 3-Speed Switch — Switch has OFF , HIGH, MED and LOW positions. Switch is also equipped with aux- iliary connection energized when switch is in HIGH, MED or LOW position.
T wo-Pipe Thermostat, Model TF103 — This single- pole, double-throw (SPDT) thermostat has snap-action con- tacts. The standard temperature range is 60 - 90 F . Four-Pipe Thermostat, Model TH104 — W ith this thermostat, heating and cooling are sequenced (automatic changeover) with 6 degree separation between HEA TING ON and COOLING ON.
BASIC DEFINITIONS Unit Hand — When facing the supply air outlet from the front of the unit (air blow- ing in your face), your right hand will be the right hand side of the unit and your left hand the left hand side of the unit. Same End Connection (2 Pipe or 4 Pipe) — All piping connections are on the same end (side) of the unit.
Hydronic Coil Arrangement FIELD PIPING CONNECTIONS* VERTICAL FLOOR UNITS — 42VB, VE, VF Pipe into cabinet end compartment (opening in bottom and back).
V AL VE P ACKAGES General — T able 1 lists acceptable pneumatic valves for installation on 42 series fan coil units. There are limitations on physical size of pneumatic valves, quantity and type of matching components, required control interface. See Fig.
LEGEND For Fig. 1 Component Sizing — 1 ⁄ 2 9 nominal (for 5 ⁄ 8 9 OD copper tubing) or 3 ⁄ 4 9 nominal (for 7 ⁄ 8 9 OD copper tubing). Manual Air V ent — Standard component - Brazed into high point of hydronic cooling and/or heating coil circuit.
V AL VE P ACKAGES (cont) T wo-W ay Motorized Control V alve The 2-way motorized valve motor drives valve open and a spring returns valve to normally closed position (no water flow with unit OFF). Supply connection at coil will be swage fit for field braze (standard) or union (option).
Three-W ay Motorized Control V alve On the 3-way motorized valve flow is normally closed to coil and open to system return. Motor closes bypass flow to system return while opening flow through coil. W ater bypasses coil and flows directly to system return when unit is OFF.
V AL VE P ACKAGE ARRANGEMENTS 20.
LEGEND — Ball V alve — Ball V alve with Memory Stop — Gate Shut Off V alve — Balancing V alve — Circuit Setter — Motorized 2-W ay V alve — Motorized 3-W ay V alve * When aquastat is used for automatic changeover , bypass is re- quired as indicated by dashed line.
V AL VE P ACKAGE ARRANGEMENTS (cont) LEGEND ITEM DESCRIPTION Pneumatic Control V alve, 2-Way Code 18(typical) -2* ( 1 ⁄ 2 -o r 5 ⁄ 8 -in. ODF tubing conn) or Code 18(typical) -3* ( 7 ⁄ 8 -in. ODF tubing conn) Pneumatic Control V alve, 3-Way Code 18(typical) -14* ( 1 ⁄ 2 -o r 5 ⁄ 8 -in.
T able 1 — Acceptable Field-Furnished Pneumatic V alves MANUF ACTURER V AL VE NUMBER TYPE MODE SIZE (in.) (OD Male Flare) CAP ACITY (CV) RA TING HONEYWELL VP517A 3-W A Y MIXING 7 ⁄ 8 3.0, 4.0, 6.3 VP522A&B 3-W A Y SEQUENCING 5 ⁄ 8 or 7 ⁄ 8 1.
PIPING COMPONENTS SYMBOL/SKETCH DESCRIPTION C V F ACTOR RA TING STEAM USE 1 ⁄ 2 3 ⁄ 4 PSI F MANUAL AIR VENT : Threaded brass needle valve with screwdriver slot for adjustment. Application - Body brazed into high point of heating and cooling coils for bleeding air from coil.
SYMBOL/SKETCH DESCRIPTION C V F ACTOR RA TING STEAM USE 1 ⁄ 2 3 ⁄ 4 PSI F PRESSURE TEST PORT : Brass body 1 ⁄ 4 service access fitting with removable depressor type core. Application - Installed on both sides of the coil to allow for pressure sensing.
PIPING COMPONENTS (cont) SYMBOL/SKETCH DESCRIPTION C V F ACTOR RA TING STEAM USE 1 ⁄ 2 3 ⁄ 4 PSI F STRAINER: Y -type body with 50 mesh stainless steel screen. Application - Used for removal of small particles from system water during normal system operation.
SYMBOL/SKETCH DESCRIPTION C V F ACTOR RA TING STEAM USE 1 ⁄ 2 3 ⁄ 4 PSI F 2-W A Y MOTORIZED V AL VE: Electric 2-position flow control valve (open/closed).
C V F ACTOR vs W A TER PRESSURE DROP C V F ACTOR: The flow rate in gallons per minute (gpm) through a piping component when the pressure drop ( D P) in pounds per square inch (psi) across the component is 1.0 (psi). Pressure drop (ft-H 2 O) = 2.31 x psi (pressure drop) GRAPH EXAMPLE: D P for 2.
29.
COPPER W A TER TUBE AND JOINT MA TERIAL PRESSURE RA TINGS JOINT MA TERIALS A 50-50 Lead-T in at 200 F Note 1 D 95-5 T in-Antimony at 200 F Note 2 B 50-50 Lead-T in at 150 F E 95-5 T in-Antimony at 150 F C 50-50 Lead-T in at 100 F F 95-5 Tin-Antimony at 100 F 1.
CORRECTION F ACTORS FOR GL YCOL (Equivalent water flow method for all 42 Series Models) This method allows you to calculate cooling and heating performance without adjusting capacities for glycol concentration.
T able 2 — Standard Accessories and Options ST ANDARD ACCESSORIES AND OPTIONS UNIT SERIES — 42 Ceiling — Horizontal Floor — V ertical Ducted — Horizontal Belt Drive Stack — V ertical CA CE.
Een belangrijk punt na aankoop van elk apparaat Carrier 42 SERIES (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier 42 SERIES heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier 42 SERIES vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier 42 SERIES leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier 42 SERIES krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier 42 SERIES bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier 42 SERIES kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier 42 SERIES . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.