Gebruiksaanwijzing /service van het product 52S van de fabrikant Carrier
Ga naar pagina of 56
SER VICE TECHNICIAN GUIDE P ACKAGED TERMINAL AIR CONDITIONERS AND HEA T PUMPS CONTENTS Page INTRODUCTION ................................. 2,3 SUMMAR Y OF DANGERS, W ARNINGS, AND CAUTIONS ... 2 GENERAL DISASSEMBL Y ........................... 4-9 TO DISCONNECT POWER FOR CORD-CONNECTED UNIT .
INTRODUCTION The focus of this manual is to provide basic information on service procedures, safety , troubleshooting, clean- ing, and component replacement for service technicians. It is intended for use only by HV AC service tech- nicians who have successfully completed instruc- tion and received T ype I Certification from the U.
FIGURE 2 — MODEL NUMBER NOMENCLA TURE FIGURE 3 — SAMPLE DA T A INFORMA TION PLA TE 3.
GENERAL DISASSEMBL Y This section includes common procedures for disassem- bly and reassembly of 52S units. These instructions are general in nature and include procedures the tech- nician may be called upon to perform when accessing certain components of the 52S unit.
TO REMOVE THE LA TERAL DUCT EXTENSION, FOR UNITS EQUIPPED WITH THE LA TERAL DUCT ACCESSOR Y P ACKAGE 1. Remove the front panel as shown in Figure 1. 2. Remove the four 1 3 ⁄ 4 -in. screws that secure the chassis to the wall sleeve (see Figure 6). There are 2 screws on each side.
TO ACCESS INDOOR-AIR SECTION COMPONENTS n DISASSEMBLING THE LA TERAL DUCT ADAPTER, FOR UNITS EQUIPPED WITH THE LA TERAL DUCT ACCESSOR Y P ACKAGE 1. Remove the lateral duct adapter end cap, shown in Figure 10, by removing the two 1 ⁄ 2 -in. screws 2.
n TO REMOVE THE AIR DISCHARGE GRILLE 1. Remove the 2 screws on each end of the air discharge grille as shown in Figure 14. 2. Lift and rotate back the bottom edge of the discharge grille and remove it.
n TO REMOVE THE DISCHARGE DECK 1. Remove the 2 discharge deck screws shown in Figure 17. Also remove the screw located at the top left corner of the outdoor coil tube sheet. 2. Gently pull the left side panel out and lift the end of the discharge deck that the screws were re- moved from, up and forward, to remove.
n TO REMOVE THE ST A TOR — After pulling the top of the condenser orifice away from the condenser coil, grasp the top of the stator and slide it up and out of the stator track.
GENERAL CLEANING Maintaining proper performance of 52S systems (Figure 21) requires conscientious cleaning and care of components. Specific components require periodic clean- ing and/or replacement, .
TOOLS NEEDED The following list includes the recommended tools, de- vices, and cleaning solutions for use in cleaning the 52S unit components. V acuum Cleaner with Crevice T ool Attachment, or Soft Plastic Bristle Brush Mild Household Detergent Phillips Head Screwdriver 5 ⁄ 16 -in.
n CLEANING THE VENT AIR FIL TER 1. Remove the unit chassis from wall sleeve as described in the General Disassembly section of this manual. See Figure 6. 2. Swing open vent door . The filter is located directly behind the vent door . See Figure 23. 3.
SEASONAL CLEANING n ACCESSING THE INDOOR AND OUTDOOR COILS — The minimum cleaning recommendation for indoor and outdoor coils is once per season. T o access the coils for a thorough cleaning, it is necessary to remove the Air System. T o accomplish this task, per- form the following steps: 1.
n CLEANING THE INDOOR AND OUTDOOR COILS Coil fins are sharp and may cut hands. Wear heavy protective gloves when cleaning coils. 1. Use a vacuum cleaner or soft bristle brush to remove surface fibers and dirt from each of the faces of the coil. Both the inner and outer surfaces of the coils must be cleaned.
n CLEANING THE INDOOR F AN AND F AN SCROLL — Once the indoor fan wheel and the indoor fan scroll have been accessed, proceed with the cleaning instructions detailed below: 1. Insert a piece of 9.5-in. by 9.5-in. cardboard between the blower wheel and the opening in the blower scroll to prevent fungus and other debris from falling into the coil.
COMPRESSOR A cutaway view of the rotary compressor with key com- ponents labeled is shown in Figure 32. The motor sta- tor is rigidly attached to the compressor shell. The rotor is pressed onto the eccentric shaft, which is supported by 2 bearings. Both the discharge valve and discharge muf fler are attached to the motor bearing.
The rotary compression process (Figure 33), starts at top dead center as shown in (1). Suction gas flows through the suction inlet and into the cylinder area. As the shaft rotates through 90 degrees, the rolling pis- ton moves to position A as shown in (2).
SYMPTOM g POSSIBLE CAUSE f COMPRESSOR ST ARTS AND RUNS BUT CYCLES ON THE OVERLOAD COMPRESSOR ST ARTS AFTER CYCLING THE OVERLOAD SEVERAL TIMES COMPRESSOR WILL NOT ST ART .
5. Next, test the resistance individually of each wire to the shell of the compressor . The paint on the com- pressor can prevent good contact between the probe and the metal. The paint should be removed from a small section of the shell of the compressor to ensure good contact by the meter probe.
n REMOVING THE COMPRESSOR — Follow the steps below to remove the compressor: 1. Disconnect all power to unit. 2. Remove unit from wall sleeve as detailed in the GENERAL DISASSEMBL Y section. The unit weighs up to 150 pounds. Seek assistance or use a lifting device when removing unit from wall sleeve.
10. For Heat Pump Units remove the capillary tube only . 11 . For Heat/Cool Units the filter drier is installed in the liquid line, in place of the strainer . T rim the saved liquid line tube from Step 9, to be 1.5 in. long (saving the crimped portion), and braze it into the filter drier , Part No.
HEA TERS The heater in 52S units is located directly behind the evaporator coil. The heater assembly includes the heater (2.3 kW , 3.4 kW or 5 kW), a primary limit switch, and a secondary limit switch (Figure 41). The primary and secondary limit switches are safety switches that regulate heater operation.
3. Remove the unit from the sleeve as detailed in the GENERAL DISASSEMBL Y section. 4. Remove the discharge air grille and the discharge air deck as detailed in the GENERAL DISASSEMBL Y section. Save screws. 5. Once the air discharge deck is removed, the heater assembly is exposed.
OPERA TING CONTROLS The controls and components used in the 52S cooling only or heat/cool units are as follows: the selector switch, the indoor thermostat, the dual capacitor , the temperature limiter , the vent lever , and the fan cycle switch (Figure 45).
DESCRIPTION OF SWITCH SETTINGS n OFF BUTTON — The OFF button terminates unit operation. n F AN ONL Y BUTTON — Push button for air circula- tion without heating or cooling. n HIGH HEA T OR HIGH COOL — Push button and rotate temperature knob to desired comfort level.
SEQUENCE OF OPERA TION n HEA T/COOL UNITS (Figure 50) Fan Mode — With the selector switch set to F AN and the fan switch set to fan cycle, contacts L1 to LO and FCS1 to LS are made. Cooling (Low) — With the selector switch set to low speed cooling and the fan switch set to fan cycle, contacts FCS2 to LO, COMP to FCS1, and COMP to IT3 are made.
COMPONENT OPERA TION AND TROUBLESHOOTING n TOOLS NEEDED V olt-Ohmmeter Flat and Phillips Screw Drivers 5 ⁄ 16 -in. Nut Driver Side Cutting Pliers Before cleaning, servicing, performing maintenance or removing the chassis from the wall sleeve, discon- nect all power to the unit to avoid the possibility of electrical shock and personal injury.
n INDOOR THERMOST A T (Heat Pump Units) (cont) (Figure 54) — T o verify operation of the heat pump in- door thermostat switch, a continuity test may be per- formed as follows: 1. T urn off unit power as described in GENERAL DISASSEMBL Y section. 2. Remove wire leads from thermostat.
n CAP ACITOR — The 52S units use a dual capacitor . One part of the capacitor is used with the fan motor . The other part of the capacitor is used by the compressor . Run circuits on single-phase compressor motors use capacitors which dramatically af fect the motor opera- tion.
ELECTRICAL COMPONENTS REMOV AL AND REPLACEMENT n INDOOR THERMOST A T — T o remove the indoor thermostat, perform the following steps: 1. T urn of f unit power as described in GENERAL DISASSEMBL Y section. 2. Remove the thermostat knob. 3. Remove control box escutcheon (Figure 58) to expose 2 Phillips head mounting screws.
n CAP ACITOR — T o remove the capacitor , perform the following steps: 1. T urn of f unit power as described in GENERAL DISASSEMBL Y section. 2. Open the control box (Figure 61) as detailed in the GENERAL DISASSEMBL Y section of this manual.
F AN MOTOR The fan motor is a permanent split capacitor (PSC) type motor . This motor is common in air-conditioning sys- tem applications. A PSC motor does not require the use of a relay and always has a run capacitor connected between the run and start windings of the motor .
SYMPTOM g POSSIBLE CAUSE f MOTOR HUMS BUT DOES NOT ST ART MAKES NO NOISE AND DOES NOT ST ART ST ARTS BUT STOPS AFTER SHORT TIME ST ARTS BUT RUNS SLOW RUNS ON ONE SPEED, NOT ON OTHERS DEFECTIVE BEARING.
F AN MOTOR REPLACEMENT Perform the following steps to remove and reinstall the fan motor: 1. DISCONNECT ALL POWER TO UNIT . 2. Remove the unit from the sleeve as detailed in the GENERAL DISASSEMBL Y section and place the unit on a large flat surface.
FIELD TEMPERA TURE CHAR TS See Figures 67 - 82 for field temperature data. FIGURE 67 — 52S 7,000 BTU UNIT FIELD TEMPERA TURE CHAR T — LOW COOL — 50% RH 35.
FIGURE 68 — 52S 7,000 BTU UNIT FIELD TEMPERA TURE CHAR T — HIGH COOL — 50% RH 52S SERIES 36.
FIGURE 69 — 52S 7,000 BTU UNIT FIELD TEMPERA TURE CHAR T , LOW HEA T MODE (47 F OUTDOOR TEMPERA TURE) 37.
FIGURE 70 — 52S 7,000 BTU UNIT FIELD TEMPERA TURE CHAR T , HIGH HEA T MODE (47 F OUTDOOR TEMPERA TURE) 52S SERIES 38.
FIGURE 71 — 52S 9,000 BTU UNIT FIELD TEMPERA TURE CHAR T — LOW COOL — 50% RH 39.
FIGURE 72 — 52S 9,000 BTU UNIT FIELD TEMPERA TURE CHAR T — HIGH COOL — 50% RH 52S SERIES 40.
FIGURE 73 — 52S 9,000 BTU UNIT FIELD TEMPERA TURE CHAR T , LOW HEA T MODE (47 F OUTDOOR TEMPERA TURE) 41.
FIGURE 74 — 52S 9,000 BTU UNIT FIELD TEMPERA TURE CHAR T , HIGH HEA T MODE (47 F OUTDOOR TEMPERA TURE) 52S SERIES 42.
FIGURE 75 — 52S 12,000 BTU UNIT FIELD TEMPERA TURE CHAR T — LOW COOL — 50% RH 43.
FIGURE 76 — 52S 12,000 BTU UNIT FIELD TEMPERA TURE CHAR T — HIGH COOL — 50% RH 52S SERIES 44.
FIGURE 77 — 52S 12,000 BTU UNIT FIELD TEMPERA TURE CHAR T , LOW HEA T MODE (47 F OUTDOOR TEMPERA TURE) 45.
FIGURE 78 — 52S 12,000 BTU UNIT FIELD TEMPERA TURE CHAR T , HIGH HEA T MODE (47 F OUTDOOR TEMPERA TURE) 52S SERIES 46.
FIGURE 79 — 52S 14,000 BTU UNIT FIELD TEMPERA TURE CHAR T — LOW COOL — 50% RH 47.
FIGURE 80 — 52S 14,000 BTU UNIT FIELD TEMPERA TURE CHAR T — HIGH COOL — 50% RH 52S SERIES 48.
FIGURE 81 — 52S 14,000 BTU UNIT FIELD TEMPERA TURE CHAR T , LOW HEA T MODE (47 F OUTDOOR TEMPERA TURE) 49.
FIGURE 82 — 52S 14,000 BTU UNIT FIELD TEMPERA TURE CHAR T , HIGH HEA T MODE (47 F OUTDOOR TEMPERA TURE) 52S SERIES 50.
WIRING SCHEMA TICS Refer to Figures 83 - 87 for typical 52S unit wiring schematics. NOTE: Figures 83 - 87 should not be substituted for the schematic located next to the unit control box.
LEGEND CAP — Capacitor COMP — Compressor FCS — Fan Cycle Switch FM — Fan Motor HTR — Heater IT — Indoor Thermostat L— Power Supply Line OL — Overload PL — Plug PLS — Primary Limit .
LEGEND CAP — Capacitor COMP — Compressor CR — Cooling Relay EQUIP GND — Equipment Ground FM — Fan Motor FR — Fan Relay HR — Heating Relay IFT — Indoor Frost Thermostat L— Power Suppl.
LEGEND CAP — Capacitor COMP — Compressor FCS — Fan Cycle Switch FM — Fan Motor HTR — Heater IT — Indoor Thermostat L— Power Supply Line OL — Overload PL — Plug PLS — Primary Limit .
LEGEND CAP — Capacitor COMP — Compressor CR — Cooling Relay EQUIP GND — Equipment Ground FM — Fan Motor FR — Fan Relay HR — Heating Relay IFT — Indoor Frost Thermostat L— Power Suppl.
MOST FREQUENT PT AC SER VICE QUESTIONS 1. Can remote thermostats be used on standard (AA) models? No, only for use on remote control (RC) models. 2. Which remote thermostats are acceptable for use on .
Een belangrijk punt na aankoop van elk apparaat Carrier 52S (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier 52S heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier 52S vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier 52S leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier 52S krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier 52S bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier 52S kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier 52S . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.