External Bypass Unit for UPS PROTECT C.6000R
Typ / Type MBS 6000
AEG Power Solutions GmbH Änderung / Revision 01 / Schenuit/ Schneider Datum / Date 09.07.2009
Operating instructions 8000019069 BAL, en

The external, manually operated bypass unit is an option for the PROTECT C.6000R UPS series in a rack version with 2U. It is used for disconnecting the UPS, for example for maintenance purposes, whilst the connected loads continue to be supplied without interruption. As well as solely bypass operation, an additional switch setting permits UPS test operation. Separately fused non-heating appliance connectors make it possible for the loads to be supplied directly from the MBS 6000. LEDs with various colours clearly signal which operating status has been selected.
Scope of delivery:
♦ External bypass unit MBS 6000 ♦ 2 connection cables to the UPS ♦ Operating instructions
Prerequisite:
♦ AEG UPS in the PROTECT C.6000R series
Technical data:

UPS Bypass Switch USV Handumgehungsschalter
NORMAL
SERVICE
BYPASS
The external bypass is used for changing over between
¾ "NORMAL" operation (default switch position),
i.e. secure load supply with UPS back-up.
¾ "TEST" operation (service position),
i.e. load supply directly from the mains, additional mains supply to the UPS for service purposes.
¾ "BYPASS" operation (bypass position),
i.e. load supply directly from the mains, additional complete isolation of the UPS (Attention! UPS output may still be live due to its internal voltage source!)
If there is a mains failure during "TEST" and "BYPASS" operation then the supply to the connected loads will be interrupted.
if external bypass switch will be operated ! (refer to the UPS operating instructions)
During subsequent installation in the rack, take care that the unit is located close to the UPS so as firstly to establish the causal connection between the two and secondly to facilitate connection and subsequent replacement of the UPS.

If you have already taken the UPS into operation then switch it off as the first step. Now disconnect the UPS from the mains by disconnecting the mains connector.
¾ Before you perform the installation described below, make sure
that none of the cables are live.
¾ Make sure that the external bypass switch is in its default
position "NORMAL".
zum USV Eingang to UPS Input
Fuse 250V/10A Fuse 250V/10A
AC Input to UPS Output
Fuse 250V/10A Fuse 250V/10A
Rear view of MBS 6000
connection cable provided with the UPS and plug the mains connector into a suitable shockproof socket. In particular for types with high power ratings, make sure that the fuse in your sub-distribution system is sufficiently large. | Two connection cables are supplied with the external bypass.
Make the following connections: Connect "OUTPUT" to the UPS output. } Connect "INPUT" to the UPS mains input. ~ As the last step, connect your loads. To do this, use the load
connection cables provided with the UPS.
This completes the installation and cabling of the UPS with the external bypass unit. Now start up the UPS system in accordance with the operating instructions.

( NORMAL )
( BYPASS )
( TEST )
Service position · UPS operation · Manual bypass

Type:
Serial no.:
Errors and changes excepted.
59581 Warstein - Belecke
Tel.: +49 (0) 180 523 4787